Table 17
- Auto Restart Parameters
DISPLAY MESSAGE
DESCRIPTION
DEFAULT/MIN
/MAX VALUE
ENABLE RESTARTS
Controls the ability of the drive to automatically restart after a fault
and to initialize in AUTO mode.
NO = no auto restarts and unit will initialize in OFF mode
YES = Auto mode on initialization and auto restarts allowed
Default is NO
DRY WELL DELAY
Time in seconds dry well is allowed before unit trips
4/0/9999
RESTART DELAY 1
Delay in seconds before unit restarts after a trip due to:
•
MOTOR OVERLOAD
60/0/9999
RESTART DELAY 2
Delay in seconds before unit restarts after a trip due to:
•
BUS OVERVOLTAGE
•
DRY WELL CURRENT
•
CURRENT UNBALANCE
•
DRY WELL KW
•
RESTARTS 4-20mA
15/0/9999
RESTART DELAY3
Delay in seconds before unit restarts after a trip due to:
•
HALL SENSE HIGH
•
LOW INPUT VOLT
•
HIGH INPUT VOLT
15/0/9999
RESTARTS MOTOR
OVERLOAD
Number of automatic restarts allowed due to motor overload current
set by parameter
OVERCURRENT LIMIT
(see Note 1)
4/0/9999
RESTARTS DRY WELL
Number of automatic restarts allowed due to under current and
minimum power trip (see Note 1)
10/0/9999
RESTARTS CUR
IMBALANCE
Number of automatic restarts allowed due to current imbalance trip
(see Note 1)
10/0/9999
RESTARTS UNDER
VOLTAGE
Number of automatic restarts allowed due to low input voltage trip
(see Note 1)
10/0/9999
RESTARTS OVER
VOLTAGE
Number of automatic restarts allowed due to high input voltage trip
(see Note 1)
10/0/9999
RESTARTS BUS
OVERVOLTAGE
Number of automatic restarts allowed due to DC bus overvoltage
(see Note 1)
10/0/9999
START UP DELAY
Delay in seconds before unit restarts after an input power OFF/ON
cycle.
0/0/9999
RESTARTS SENSOR
CONN FAIL
Number of automatic restarts allowed due to loss of 4-20mA analog
input signal (see Note 1)
10/0/9999
SHORT CYCLE DELAY
Delay in seconds before motor starts after a RUN command.
Prevents the drive from engaging the motor when it is spooling down
during coast-to-stop operation. Delay affects both manual RUN
command from the keypad and RUN command from external signals
in auto mode. Display will count down seconds until RUN during
delay.
3/0/300
Note 1:
The restart counter must be cleared to begin counting the number of restarts from zero. Main Menu item,
Clear Memory, resets the fault counters. See
Section 4
Keypad Main Menu Items,
for more information.
Note 2:
Push the up arrow key and down arrow key simultaneously to interrupt the countdown delay and allow an
auto restart.
Содержание 2XD Series
Страница 10: ...4 P a g e 2 3 Dimensional Drawings Figure 5 SD Series Line Drawing...
Страница 11: ...5 P a g e Figure 6 SD Series Line Drawing if selected with optional breaker see Figure 9...
Страница 12: ...6 P a g e Figure 7 SD Series Line Drawing if selected with optional breaker see Figure 9...
Страница 13: ...7 P a g e Figure 8 SD Series Line Drawing if selected with optional breaker see Figure 9 or Figure 10...
Страница 14: ...8 P a g e Figure 9 SD Series Line Drawing...
Страница 15: ...9 P a g e Figure 10 SD Series Line Drawing...
Страница 16: ...10 P a g e Figure 11 2XD Series Line Drawing...
Страница 80: ...74 P a g e Figure 36 SW1 in SD Systems...