background image

 

© Pertronic Industries Ltd 

19 

FAAST LT Loop-Based Installation & Maintenance Guide  Iss 1.0, 201701

 

Section E : SYSTEM TEST AND COMMISSIONING: 

E1.

 

Ensure the following items are available: 

a)  FAAST System Pipe Layout Report:- allows the measured values to be referenced to the values calculated in 

PipeIQ. 

b)  FAAST System Bill of Materials Report 
c)  As-built Installation Drawings 
d)  Smoke Pen or other source of smoke with a particulate life cycle

 

of greater than 120 seconds 

e)  Timer or stop-watch - to measure the maximum Transport Time 
f)  Blue-Tak or similar to block holes during Flow tests 
g)  Locally Required Forms 
Note that the Laser detector LEDs, which are controlled by the Fire Panel, must be turned ON to activate the front 
panel Alarm

 

indicators 

 

E2.  Commissioning and Handover 

(reference: FIA Code of Practice for ASDs, Issue 3, Feb 2012)

 

E2a  Commission Testing  

The Commissioning Tests to be performed depend on the ASD system application but should be carried out only 
when  the  building  is  in  its  normal,  intended  running  state.  Appropriate  commissioning  tests  should  also  be 
performed after modifications and/or additions to the ASD system.  

Commissioning  

The commissioning process has several stages which should be performed, recorded and checked as necessary:  

•  Inspection  of  Installation  –  verify  conformity  to  design,  definition  of  system  (see  section  5)  including 
mechanical and electrical installation.  
• Power Up/Configuration – required checks and configuration 
• Commissioning Tests – to include mechanical, functional and performance testing.  
• Signalling - to verify the connections between the ASD and other connected systems (e.g. FAP, BMS).  
• System Check - to verify the detector settings are appropriate for the site 
• System Handover – include relevant documentation and recorded drawings.  

 
E2b  Inspection of Installation 

Inspect  the  installation  to  confirm  that  it  has  been  designed  and  installed  correctly  for  the  application  and 
conforms to the design documentation - in particular;  

  ASD used to replace point-type detectors (Class C) - ensure the installation (particularly Sample Point spacing) 

conforms to the relevant standard (e.g. NZS4512:2010) and the ASD Sensitivity/Alarm thresholds are correctly 
set  to  ensure  that  the  sensitivity  of  individual  holes  meets  the  minimum  performance  requirements  for 
individual points. Note that this may require reference to the approval compliance notes for the particular ASD 
system  and  should  also  take  into  account  any  potential  automatic  adjustments  of  the  Sensitivity/Threshold 
settings, which may occur after commissioning.  

  ASD used for high and enhanced sensitivity (Class A/B)  - ensure that the installation conforms to the design 

specification  (eg.  if  necessary,  measure  the  air  velocities  in  the  protected  area  to  ensure  that  the  design 
spacing is appropriate. 

  ASD  used  as  a  Primary  Sampling  System  (refer  to  Table: 

‘Sensitivity  Class  vs  Detection  Requirements’  on 

page 26), ensure the pipe and sample points are installed correctly onto the Air Handling Unit (AHU) within the 
airflow. If monitoring more than  one  AHU, it  is important to ensure  different  running speeds do  not cause  an 
unbalanced airflow in the pipe, which may affect ASD performance.  

  ASD  used  for  other  installations  (cabinet,  duct  work  or  other  specialist  protection)  -  confirm  that  the  ASD 

system is in accordance with the design.  
Perform a thorough inspection of the mechanical and electrical installation - include;  

  pipe network including correct supports.  

  clear identification of Sampling Points.  

  no obstructions to Sampling Points or remote capillaries.  

  all internal and external electrical wiring has been installed correctly.  

  power supplies are correctly rated and provide the correct emergency battery standby period.  

  correct hole position and sizes.  

Before the ASD is powered up, it is very important to check that the pipe is clear of any foreign articles eg. swarf, 
dust, etc. that will impede or stop the ASD performance.

 

 

E2c  Power Up/Configuration  

It is 

very important that the ASD manufacturer’s technical documentation is followed during system set-up. If there 

is any doubt refer back to the manufacturer for clarification.  
The system should be powered up in accordance with the manufacturer’s recommendations. Prior to carrying out 
any functional and performance tests the ASD equipment should be configured for:  
•  Fire signal Alarm thresholds and detector sensitivity settings to give required sampling point sensitivity.  
•  Alarm and Fault delay periods.  
•  Airflow parameters.  
•  any other defined parameters.

 

 

Содержание SYSTEM SENSOR FAAST LT Series

Страница 1: ...mum Number of Holes See Table 1A Pipe Spec EN54 20 Compliance to EN61386 Crush 1 Impact 1 Temp 31 Outside Pipe Diameter 25mm or 27mm nom Shipping Weight 6 5kg incl detectors Colour Code Key refer to back page Black applies to both FL01nn and FL20nn Series Blue refers to Important Settings which should be verified Figure 1 Dimensions and Knock Outs PARTS LIST Description Quantity FAAST LT Unit 1 Mo...

Страница 2: ...e front panel labels fitted This allows the installer to select the language required from the Front Panel Labelling Pack Figure 2 shows where to place the labels Figure 2 Front Panel Label Locations When label A is in place remove the protector from the bottom of the clear cover to stick the cover down as shown in Figure 3 Figure 3 Remove backing tape to stick cover down Cable Access Knock out ca...

Страница 3: ...ation Figure 8 Pipe Holes Table 1 Pipe Holes Used for Each FAAST LT Model FAAST LT Model Inlet Pipe Hole Outlet Pipe Hole FL2011EI 1 2 or 1 OR 2 5 FL2012EI 1 2 or 1 OR 2 6 FL2022EI Channel 1 1 2 or 1 OR 2 5 Channel 2 3 4 or 3 OR 4 6 Notes a Unused Pipe Holes MUST be kept sealed b Do NOT glue pipes into Pipe Holes Table 1a Maximum Number of Pipe Holes Allowed Per Channel All figures quoted using hi...

Страница 4: ...ulations b Loop wiring must observe the recommendations of the panel manufacturer Notes use the PipeIQ BOM Report to order the Pipe components required to assemble the system use the PipeIQ Pipe Layout Report to assemble the pipe layout Important follow the Pipe Layout report as closely as practical ensure Pipe Lengths are correct ensure Sampling Point holes are drilled at the stated positions ens...

Страница 5: ...Set ON in ALARM default Setting the Sensor Addresses Each aspiration channel uses loop communications to report its status information to the CIE Fire Panel As a factory default the unit will report Smoke Alarm and sensor information at an associated Detector address and general Alerts and Faults on a different Module address The default addresses are Channel 1 01 Channel 2 02 Figure 11 Address Sw...

Страница 6: ...ed see USB Connection section later in this guide for more information on this and the FAAST LT Advanced Setup and Control Guide EXTERNAL RESET The default setting for the configurable external input is Device Reset terminal block T8 A short circuit connection between these terminals will cause the FAAST LT unit to perform a Reset FRONT PANEL The front panel differs depending on which of the 6 x F...

Страница 7: ...ault check filter check pipe network for blockages INPUT 1 Blink External Input fault Not used with default settings SENSOR 2 Blinks Detector communication fault Check detector addresses and installation replace detector ASPIRATOR ON Air Flow sensor fault Try to restart device 1 Blink Flow initialization fault Check filter check pipe network for blockages try to restart device 2 Blinks Fan fault T...

Страница 8: ... device is ready for the first digit c press DISABLE to increment the LEDs 1 9 press TEST to select a digit The flashing airflow segment turns ON green and the next segment begins to flash indicating set the next digit When the 4th digit is selected all 4 airflow segments turn OFF if the password is accepted the FAULT indicator remains green and the unit enters MAINTENANCE mode if the password is ...

Страница 9: ...ed inside the cabinet at the top of the unit see Figure 10 displayed on Page 4 and are removed as shown in the following sequence Either replace the filter assembly or carefully brush off the accumulated dust Note if replacing the filter remove the foam gasket from the old filter and place onto the new filter When placing the new filter into the slot ensure that the gasket is correctly aligned Ref...

Страница 10: ...ctor or available from http www faast detection com contact us download pipeiq Connection to the FAAST LT a Open PipeIQ v2 or greater on the PC by default PipeIQ opens in Configuration mode b Open a project file mdf to continue use one of the following methods i open an existing project configuration mdf file for the FAAST LT or ii start a New Config and add a FAAST LT detector of the type to be i...

Страница 11: ...sure Specify the atmospheric pressure in Pascal Both supplies monitored By default the first power supply is monitored to signal a low power Select Yes to monitor the second power supply Power Restart Alert Alert for The device signals the power restart alert for this period Alert till Reset Select to enable alert until the reset is performed Disable Select to disable the power restart alert Trend...

Страница 12: ...er ON to reach the configured reference flow Manual the device uses the configured manual speed Fan Speed Drag and set the speed scale for the fan Note The fan speed set here is considered for the calculations of the built network when the fan speed mode is selected as Manual Reference Flow Specify the flow value in litre per minute l min Filter Due Date Specify the due date for the air filters Th...

Страница 13: ...activated until a reset is performed No The device automatically deactivates the relay Auxiliary Relay used for Channel 2 Fault Select either of the following Yes The device activates the general fault relay for the faults of channel 1 and faults common to both channels the auxiliary fault relay for faults of channel 2 and for the faults alerts configured to activate auxiliary relay No The auxilia...

Страница 14: ...tically change the device real time clock date when the date is in the daylight saving period 1 hour is added No Select No to disable the daylight saving option Auto Select Auto to automatically set the start date as last Sunday of March 02 00 and the end date as the last Sunday of October 02 00 Start Date Select the start date of daylight saving period End Date Select the end date of daylight sav...

Страница 15: ... each Sampling Point then use the appropriate Alarm Level as assigned during the PipeIQ Design Calculation f Generally the FAAST LT ALARM level will be 3 4 or 5 The PRE ALARM level may be selected from 1 to a setting less than the ALARM level selected g Use the following Table to determine the appropriate Sensitivity setting to use on an F100 or F120 panel h Configure the Module addresses as Type ...

Страница 16: ...Note Click Refresh to obtain the current state of all the relays D1b Smoke Test to perform Smoke Tests a Click Monitoring on the left pane b Select the device to set the actions The Actions tab appears on the right pane c Under Smoke Test set the time for the following two options i Start at a set time Select Start at and select the time to schedule a start time for the smoke test Click Schedule i...

Страница 17: ...ce to set the actions The Actions tab appears on the right pane c Under Restart set the following options i Normal select to restart the device in Normal mode ii Maintenance select to restart the device in Maintenance mode d Click Set to apply the restart settings D1g FAAST LT Clock to set the FAAST Clock a Click Monitoring on the left pane b Select the device to set the actions The Actions tab ap...

Страница 18: ...og tab click the Events List tab i Select Show All Events to view all the events of the device ii Select Period to view all the events within the specified date From and To dates are available from the drop down calendar iii Click Show The list of events appears Note the Show Last drop down list to select the latest 20 50 100 500 events Below the list of events click First Previous Next and Last t...

Страница 19: ...tivity Alarm thresholds are correctly set to ensure that the sensitivity of individual holes meets the minimum performance requirements for individual points Note that this may require reference to the approval compliance notes for the particular ASD system and should also take into account any potential automatic adjustments of the Sensitivity Threshold settings which may occur after commissionin...

Страница 20: ...is the Transport Time for this Sample Point the Maximum Transport Time shall be less than the maximum time specified within the design documentation engineering specifications but must not exceed 90 seconds NZS4512 2010 Where an Alarm indication is used it does not generally include any Alarm delays which are temporarily set to zero for the measurement of Transport Time Measured Transport Time sho...

Страница 21: ...y Class vs Detection Requirements Colour Code Key When using this manual apply the information which applies to the particular FAAST LT model being installed Black applies to both FL01nn and FL20nn Series FAAST LT detector Blue refers to Important Settings which should be verified While all settings are important many can justifiably remain as the default value but items in Blue should be checked ...

Страница 22: ...Humidity Other Power Supply Installed correctly Yes No Pipe Network Installed in Accordance with the PipeIQ design per Pipe Layout Report Yes No Pipe Network Labelled correctly Yes No Describe Any Variations Sensor 1 Module 1 Sensor 2 Module 2 Loop Address L M L M L M L M Sensitivity circle one VEWFD EWFD SFD Class A Class B Class C VEWFD EWFD SFD Class A Class B Class C Threshold Time Delay Day A...

Отзывы: