FAAST LT Loop-Based Installation & Maintenance Guide Iss 1.0, 201701
Channels and Sensors:
To configure the device, set the parameters in the
Channels and Sensors
tab.
a) Select
Configuration
on the left pane.
b) Click the device. The General parameters configuration screen appears in the right pane.
c) Select the
Channels and Sensors
tab.
Specify the following details.
Fields
Description
Channels:
Enable the required
Channel
(s). The options are:
Channel 1
Channel 2
Note:
The following fields are configured based on the specific
Channel
which is selected
Label:
Specify a label to identify the zones served by the channels
Alarm is Latched
Select either of the following:
Yes
: The device retains the Alarm relay activated state until a Reset is performed
No
: The device automatically de-activates the relay
Fan Speed Mode:
Select either of the following:
Auto
: the device automatically sets the fan speed, at every power ON, to reach the
configured reference flow
Manual
: the device uses the configured manual speed.
Fan Speed:
Drag and set the speed scale for the fan
Note:
The fan speed set here is considered for the calculations of the built network when the
fan speed mode is selected as
Manual
Reference Flow:
Specify the flow value in litre per minute (l/min)
Filter Due Date:
Specify the due date for the air filters. The device displays a filter fault after the due date
Sensors:
The Sensor Enabled state is based on the
Channel Enabled
state:
Sensor 1 enabled
Sensor 2 enabled
Note:
either of the two
Sensors
may be disabled if the device has one channel and two
sensors
Sensor blinking
replicated:
Select either of the following.
Yes
: The channel alarm LED blinks a steady green when the sensor is polled
No
: The channel alarm LED does not blink when the sensor is polled
Common
chamber:
Select either of the following.
Yes
: Alarm is set when one sensor is in the Alarm condition
No
: Alarm is set when both the sensors are in the Alarm condition
d) Save to implement the changes.
To configure the
Advanced
parameters, refer to Advanced Configurable Parameters