PROBLEM
CAUSE
SOLUTION
If Evaporator fan is still not running
Replace evaporator fan per
.
No power to/from DC inverter/driver
(12V).
If no power: restore power, replace. Refer to
.
Control not functioning
No power to unit.
Restore power to unit.
Refer to information plate. See
Incorrectly wired harness.
Verify wiring per wiring diagram,
.
Reconnect wires if needed.
No call for cooling.
Check probe connections and verify resistance
readings.
Check control settings.
Replace control.
Lights not functioning
Light switch in off position.
Turn on light switch.
No power to light.
Verify wiring per wiring diagram,
.
Faulty LED strip
Replace LED strip.
Faulty/defective door switch or wiring to
door switch.
Check wiring for continuity of switch contacts.
Replace switch if faulty.
Door switch plunger bracket missing or
misaligned.
Install bracket and/or align properly.
Light stays on when door is
closed.
Manual switch is on.
Turn off manual switch.
Faulty/defective door switch or wiring to
door switch.
Check wiring and continuity of switch contacts.
Replace switch if faulty.
Door switch plunger bracket missing or
misaligned.
Install bracket and/or align properly.
Eliwell Control: LED
Controller display is flash
-
ing “E1”
Probe 1 error. Reading out-of-range of
operating values.
Check probe connections to control.
Check probe resistance readings per
Check probe wiring.
Return to