PROBLEM
CAUSE
SOLUTION
Refrigeration/Charge level is too low.
Check for leaks, repair, and recharge per
Water on the floor outside
of unit.
High ambient temperature and high am-
bient humidity conditions coupled with
frequent door opening.
Ensure doors close completely.
Condensate pan overflowing.
Remove excess water.
Check for the following:
•
Air infiltration. See
.
•
Doors close completely and seals are
intact. See
.
•
Ice buildup. See
Water on the floor outside
of unit.
(continued)
Unit is not level.
Unit must be level front-to-back and side-to-
side for water to drain properly.
Sealing compound does not form a com-
plete seal.
Refer to
.
Door gasket is damaged.
Refer to
and
Evaporator coil has iced over.
Remove ice. Refer to
Evaporator pan and/or drain line restricted. Remove restriction.
Water on the floor inside
of unit.
Unit is not level.
Unit must be level front-to-back and side-to-
side for water to drain properly.
Evaporator coil has iced over.
Remove ice. Refer to
Return to
Residential Refrigeration
and Front Venting Commercial Refrigeration
Service Manual
Troubleshooting Guide - Refrigeration System
Page 3-3