OPERATING INSTRUCTIONS
4012/16 Gas, February 1998
27
GAS ENGINE START/STOP SEQUENCE (AUTOMATIC)
Fig. 14
IS GAS
PRESSURE
WITHIN
LIMITS?
ENERGISE
GOVERNOR
ENERGISE STARTER
MOTOR & CRANK
TIMER
LOW GAS PRESSIRE
ALARM & LOCKOUT
NO
YES
ENERGISE GAS
VALVES & IGNITION
CONTINUE
CRANKING
CRANK FOR
3 SECONDS
(PURGE SYSTEM)
YES
YES
NO
NO
HAS ENGINE
STARTED?
FAIL TO START
LOCKOUT
MAX CRANKING
TIME REACHED?
DE-ENERGISE
STARTER MOTOR
ENGINE
RUNNING
OVER SPEED
FAULT?
ENGINE
RUNNING
OTHER
ENGINE
FAULT?
STOP
ENGINE?
DE-ENERGISE
GAS VALVES
DE-ENERGISE
GAS VALVES
START SIGNAL
RECEIVED
YES
YES
YES
NO
NO
SWITCH OFF
IGNITION SYSTEM
& DE-ENGERGISE
GAS VALVES