ION/CME N-Series Digital Drive Developer Kit User Manual
51
3
3.4.3
Conversion Factors, Medium Power Units
The following table provides electrical conversion factors for medium power level N-Series ION units (P/Ns:
DD4X1X0056/06).
These factors convert various integer Magellan IC command arguments (referred to as having units of counts) to
physical quantities such as amperage, volts, etc... For more information on the Magellan motion control IC refer to
the
Magellan Motion Control IC User Guide
. For more information on C-Motion commands refer to the
C-Motion/PRP
II Programming Reference
.
3.4.4
Defaults & Limits, Medium Power Units
The following table provides default values, medium limits and high limits for various specifiable drive-related
parameters for low power level N-Series ION units (P/Ns: DD4X1X0056/06).
I
2
t continuous current limit, step
motor
1.5 A
0.0 A
1.5 A
I
2
t energy limit, Brushless DC
Motor
2.95 A
2
sec
0.0 A
2
sec
2.95 A
2
sec
I
2
t energy limit, DC Brush Motor 3.63 A
2
sec
0.0 A
2
sec
3.63 A
2
sec
I
2
t energy limit, step motor
2.95 A
2
sec
0.0 A
2
sec
2.95 A
2
sec
Unit
Example C-Motion
Commands
Scaling
Example usage
Amps
GetCurrentLoopValue
.733 mA/count*
A command request to read the
ActualCurrent parameter returns a value
12,345. This corresponds to a current of of
12,345 counts * 0.733 mA/count = 9.049
Volts
SetDriveFaultParameter
GetBusVoltage
10.0 mV/count
To set an overvoltage threshold of 50V, the
command value should be 50 V *1,000 mV/
V / 10.0 mV/count = 5,000
Temperature
SetDriveFaultParameter
GetTemperature
.0039 °C/count
To set an overtemperature threshold of
65 °C, the command value should be 65 °C
/ .0039 °C/count = 16,667
I
2
t continuous
current
SetCurrent
.733 mA/count
To set an I
2
t continuous current of 4.0A, the
command value should be 4.0A * 1,000 mA/
A / 0.733 mA/count = 5,457
I
2
t energy
SetCurrent
.0590 A
2
Sec/count
To set an I
2
t energy of 20.0 A
2
Sec, the
command value should be 20.0 A
2
Sec /
0.0590 A
2
Sec/count = 339
Setting
Default Setting
Low Limit
High Limit
Overtemperature limit
75.0 °C
0 °C
75.0 °C
Overtemperature hysteresis
5.0 °C
0 °C
25.0 °C
Overvoltage limit
60.0 V
10.0 V
60.0 V
Undervoltage limit
10.0 V
10.0 V
56.0 V
I
2
t continuous current limit,
Brushless DC motor
5.5 A
0.0 A
5.5 A
I
2
t continuous current limit, DC
Brush motor
7.1 A
0.0 A
7.1 A
Setting
Default Setting
Low Limit
High Limit
Содержание CME N Series
Страница 6: ...vi ION CME N Series Digital Drive Developer Kit User Manual ...
Страница 8: ...viii ION CME N Series Digital Drive Developer Kit User Manual ...
Страница 30: ...30 ION CME N Series Digital Drive Developer Kit User Manual 1 ...
Страница 58: ...58 ION CME N Series Digital Drive Developer Kit User Manual 3 7 6 7 6 PP LQFK ...
Страница 69: ...ION CME N Series Digital Drive Developer Kit User Manual 69 4 ...
Страница 70: ...70 ION CME N Series Digital Drive Developer Kit User Manual 4 ...