10
is not available for regulators, which are
provided with STANDARD mode of operation
only.
In
Standard
mode the regulator operates in
automatic cycle with parameters preset by
the user. The preset values are available in:
MENU
Boiler Settings
Burner
Settings
.
The fan works continuously with constant
blow-in output preset in the parameter
Blow-
in Output
. The feeder starts periodically and
remains in operation for the duration set in
Feeding Time,
then it stops and remains off
over the time set in
Feeder Interval
.
Cycles of Blow-In and Feeder operation in
OPERATION mode; A
–
Feeder Interval, B
–
Feeding Time.
These parameters should be properly
selected subject to boiler output, and fuel
type and quality. Usually, they are factory
set by the boiler manufacturer.
As the factory settings do not
always comply with the given
boiler type, they should be
adapted to the given boiler and
fuel type.
Burner adjustment instruction:
- set the parameters:
Feeding Time
and
Feeder Interval
so that the required boiler
output (e.g. 15kW) has been reached. Boiler
power is displayed in MENU
→
Information ,
- select the proper
blow-in output
to the set
fuel stream.
Note: boiler power will be properly displayed
provided that the values of service
parameters:
Feeder Efficiency
and
Energy
Density
have been properly entered!
Feeding Time-
OPERAT and
Feeder Interval- OPERAT
should
be so selected that the furnace
does not retrace to the fuel
feeder.
Once the preset boiler temperature has been
achieved, the regulator automatically enters
SUPERVISION mode.
7.7
OPERATION
–
Fuzzy Logic mode
Upon change of boiler regulation mode from
Standard to
Fuzzy Logic,
regulator works in
OPERATION mode and modulates the boiler
output to achieve constant preset boiler
temperature.
Fuzzy logic
regulation mode may be set in:
MENU
Boiler Settings
Burner
Settings Regulation Mode
Please note that
Fuzzy Logic
program is
adapted individually to the given boiler and
fuel type and may work properly only with
this boiler and fuel. Therefore, the
Fuzzy
Logic
mode requires special settings and has
to be activated by the boiler manufacturer in
accordance with sec. 21.1. In case this mode
has not been activated, it will not be
available.
Fuzzy Logic correction
In some instances, Fuzzy Logic mode has to
be adjusted to the fuel quality. To make the
correction, use the following parameters:
FL
fuel correction
and
FL airfl. correction
which
are available in:
MENU
Boiler Settings
Burner
Settings
.
At first adjust the
FL fuel correction.
If fuel is
of poor quality and incompletely burnt fuel
particles are present in ash, reduce the rate
of supplied fuel; in the contrary case -
proceed in analogical manner.
Note: incompletely burnt fuel particles or
lowered furnace may be also caused by
improper boiler operation in SUPERVISION
mode. Therefore, prior to correcting
Fuzzy
logic
it is recommended to adjust parameters
of SUPERVISION mode in accordance with
sec.7.8.
Activation of the
Fuzzy Logic
mode does not release from the
requirement
to
adjust
the
parameters
of
SUPERVISION
mode
–
risk of screw feeder
damage.
Switching off output modulation in Fuzzy
Logic
Содержание KSM 17
Страница 1: ...Operation and maintenance manual for the KSM series boilers with feeders...
Страница 26: ......
Страница 31: ...REGULATOR INSTRUCTION MANUAL ecoMAX 910R1...
Страница 41: ...USER MANUAL OF CONTROLLER INSTALLATION AND SERVICE SETTINGS ecoMAX 910R1...
Страница 47: ...23...
Страница 71: ...47...
Страница 74: ......
Страница 75: ...3 This sign indicates relation to safety issues This sign indicates relations to module functional features...
Страница 102: ......
Страница 103: ......