Operation and maintenance manual for the KSM series boilers with feeders. The producer reserves the right to introduce technical modifications.
3.4.2. Closed water installations
PEREKO heating boilers
fi
red with solid fuels and with automatic
fuel charging with nominal power up to 300 kW can be used in
closed water heating systems provided that:
1. the system has been equipped with membrane expansion
vessel,
2. a device intended for removal of heat excess, that is
two-function cooling valve REGULUS DBV-1 was installed,
3. the safety valve 1.5 bar was installed.
NOTE! Correct selection of protections and suitable expan-
sion diaphragm vessel having in
fl
uence on safety level of
the system and the boiler.
The above equipment should be rigorously inspected min-
imum twice per year. The
fi
rst inspection should be carried
out during seasonal start-up of the boiler with the water
distribution system.
3.4.3. Four-way valve
Design of the heating system should take into account protec-
tion of the boiler against the return of too cold water from the
system. It is recommended to use four-way mixing valve what
allows the increasing temperature of water returning to the
boiler.
Four-way valve mixes hot water from the supply with cooler
water returning from the heating cycle and therefore:
• protects the boiler against low-temperature corrosion and
premature wear,
• improves the e
ffi
ciency of heating of tap water in the DHW
storage tank,
• allows smooth adjustment of the temperature of the heating
water with respect to the needs of the heating system,
• improves the e
ffi
ciency of operation of the whole system.
Designing of the correct diagram of the system for the house
and its execution should be entrusted to a person with appro-
priate quali
fi
cations. Central heating systems may di
ff
er and
therefore it is necessary to stick to the guidelines included in the
central heating design.
3.5. Connection of the boiler to electrical system
Boiler room should be equipped with electrical system with
rated voltage 230/50 Hz in compliance with the applicable reg-
ulations. The system should be terminated with plug-in socket
equipped with protective conductor contact with connected
protective conductor terminal PE to protect against electric
shock.
Содержание KSM 17
Страница 1: ...Operation and maintenance manual for the KSM series boilers with feeders...
Страница 26: ......
Страница 31: ...REGULATOR INSTRUCTION MANUAL ecoMAX 910R1...
Страница 41: ...USER MANUAL OF CONTROLLER INSTALLATION AND SERVICE SETTINGS ecoMAX 910R1...
Страница 47: ...23...
Страница 71: ...47...
Страница 74: ......
Страница 75: ...3 This sign indicates relation to safety issues This sign indicates relations to module functional features...
Страница 102: ......
Страница 103: ......