AS-Interface
Mailbox
Subject to reasonable modifications due to technical advances.
Copyright Fuchs, Printed in Germany
Fuchs Group · Tel.: Germany (6 21) 7 76-0 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91 · Internet http://www.pepperl-fuchs.com
is
s
u
e
d
a
te
1
0
.1
2
.2
0
0
2
32
The coding of requests for commands to reading and writing is following therefore:
9.1.1.1
Values for command
Request
byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
1
command
2
T
0
circuit
3
Request parameter byte 1
…
…
Values for command
command
value
meaning
Req
Len
Res
Len
IDLE
00
16
No order
2
2
READ_IDI
41
16
Read IDI
2
24
WRITE_ODI
42
16
Write_ODI
24
2
SET_PP
43
16
Set_Permanent_Parameter
4
2
GET_PP
01
16
Get_Permanent_Parameter
3
3
WRITE_P
02
16
Write_Parameter
4
3
READ_PI
03
16
Read_Parameter
3
3
STORE_PI
04
16
Store_Actual_Parameter
2
2
SET_PCD
25
16
Set_Permanent_Config
5
2
GET_PCD
26
16
Get_Permanent_Config
3
4
STORE_CDI
07
16
Store_Actual_Configuration
2
2
READ_CDI
28
16
Read_Actual_Configuration
3
4
SET_LPS
29
16
SET_LPS
11
2
GET_LPS
44
16
Get_LPS
2
10
GET_LAS
45
16
Get_LAS
2
10
GET_LDS
46
16
Get_LDS
2
10
GET_FLAGS
47
16
Get_Flags
2
5
SET_OP_MODE
0C
16
Set_Operation_Mode
3
2
SET_OFFLINE
0A
16
Set_Offline_Mode
3
2
SET_DATA_EX
48
16
Set_Data_Exchange_Active
3
2
SLAVE_ADDR
0D
16
Change_Slave_Address
4
2
SET_AAE
0B
16
Set_Auto_Adress_Enable
3
2
GET_LPF
3E
16
Get_LPF
2
10
WRITE_XID1
3F
16
Write_Extended_ID-Code_1
3
2
RD_7X_IN
50
16
Read 1 7.3-slave in.data
3
10
Содержание VBG-CCL-G4F
Страница 78: ...123904 12 02 00...