AS-Interface
Advanced Diagnostics for AS-i Masters
Subject to reasonable modifications due to technical advances.
Copyright Fuchs, Printed in Germany
Fuchs Group · Tel.: Germany (6 21) 7 76-0 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91 · Internet http://www.pepperl-fuchs.com
is
s
u
e
d
a
te
1
0
.1
2
.2
0
0
2
24
There are two different ways to parameterize the AS-i master for this feature:
• Every configuration error during normal operation in protected mode releases
the off-line phase.
• For each slave address can be chosen whether a configuration error on this ad-
dress will release the off-line phase or not. This information is stored in the List
of Off-line Slaves (
LOS
).
The user himself can decide how the system reacts to a configuration error on
the AS-Interface. The AS-i master can release the off-line phase in critical situ-
ations, i. e. only with certain slave addresses, while in less critical situations (if
one of the other AS-i slaves have a configuration error) only the error message
configuration error is sent to the host, but AS-i is still running.