4.
4.201
4
18
AS-i Safety Output Module with Diagnostic Slave
Safety Requirements
8.
Safety Requirements
•
Two semiconductor switches in series are used which issue the safety
release.
•
These switches are tested in the unit so that any error which prevents one of
the two semiconductor switches from turning off is detected.
•
The two outputs
1.14 ext.out
and
2.14 ext.out
are fed by the same release
signal. They are not safely isolated from each other.
•
If there is no release, both outputs are safety turned off.
•
If there is a release, both outputs can be controlled by non-safety signals.
•
The return line from the consumers must be connected to the
0 V ext.out
ter-
minal on the module and may not be taken directly to the
0 V ext.out
of the
power supply.
•
There is no cross-connection monitoring between
1.14 ext.out
and
2.14 ext.out
.
•
If two independent, series wired contactors need to by controlled by the
device, you must ensure that the line between the contactors and the device
cannot make a connection to a different potential, so as to prevent undesired
turning on of the contactors.
•
Input 1.Y1, just like inputs I1... I3, is a standard AS-i input.
•
The external 24 V supply must be provided by a PELV power supply.