37
Radar Motion Sensor RMS-FRW
Safety
3.3
Standard-relevant safety settings
Some functions permit settings that are not in accordance with AutSchR: 1997 (Directive for automatic sliding doors
in escape and rescue routes):
3.3.1 Settings for doors in escape and rescue routes:
Connecting the sensor:
The two relay contacts are galvanically separated. For safety reasons, series or parallel connection is not permissi-
ble. Both contacts must be evaluated separately on the door control system. The output signal is only valid if the two
relay contacts of the movement output are in the same state.
Sensitivity of the movement detection:
The field depth must be at least 1.5 m!
Output hold time movement detector:
The setting "Off" is not permissible!
Polarity output movement detector:
The setting "Active" is not permissible!