Function "safety settings" (01)
4.1
Function "output on alarm" (010)
This f
u
nction is
u
sed to select the reaction of o
u
tp
u
t on an alarm.
Selection:
•
MI
N
(<= 3.6mA)
•
MAX (22mA)
•
Hold
•
User specific
MIN (<= 3.6mA)
If the instr
u
ment is in alarm state, the o
u
tp
u
t changes as follows:
•
HART:
MI
N
-Alarm 3.6 mA
•
PROFIBUS PA:
MI
N
-Alarm -99999
MAX 110% 22mA
If the instr
u
ment is in alarm state, the o
u
tp
u
t changes as follows:
•
HART:
MAX-Alarm 22 mA
•
PROFIBUS PA:
MAX-Alarm +99999
E
+
–
E
+
–
(110
%
)
(-10
%
)
3.6
t
[mA]
22
-99999
t
HART
PA
HART
PA
(110
%
)
(-10
%
)
3.6
t
[mA]
22
+99999
t