background image

 2

0

1

8

-1

2

44

FB Remote I/O

Installation

Installing field wiring for non-intrinsically safe circuits

Non-intrinsically safe circuits must be covered with protective covers for Ex e modules.

1. The I/O modules are wired differently depending on the type. Wire the terminal blocks to the 

field devices in accordance with the information in the datasheets for the I/O modules used.

2. Note the permissible core cross section of the conductor. We recommend that you do not 

exceed a conductor cross section of 0.75 mm

2

.

3. If you are using stranded conductors, crimp the stranded conductors with wire end ferrules.

4. Make sure that the insulation on the conductors extends all the way to the terminal.

5. Use only black type LB9109.E.6.1, LB9109.E.8.1, and LB9109.E.8.2 terminal blocks and 

protective covers for type LB9107.E.6 and LB9107.E.8 Ex e modules.

Figure 3.18

Spring terminal with protective cover for Ex e modules

6. Make sure that the separation distances to intrinsically safe circuits are observed.

7. Unused cables and connection lines must be either connected to terminals, securely fixed 

and isolated, or grounded.

8. If necessary, code the front sockets of the I/O modules and terminals so that the terminals 

and the associated field devices can be assigned to exactly one front socket.

9. Plug the terminals into the front sockets of the corresponding I/O modules and screw the 

terminals into place using the side screws.

10.Break off the lugs of a protective cover for Ex e modules at the points where the field lines 

lead into the terminal openings. Unused terminal openings must remain covered by the lugs 
of the protective cover so that no bare, conductive parts are exposed.

Danger!

Explosion hazard when removing the protective caps

If intrinsically safe and non-intrinsically safe circuits are present, removing the protective cap in 
a potentially explosive atmosphere can create sparks that can ignite the surrounding 
atmosphere.

n

Only remove the cover when not located in a potentially explosive atmosphere.

n

Only remove the cover if the non-intrinsically safe circuits are de-energized (no voltage or 
current). Remove the I/O module or switch off the circuit using the multifunction terminal.

n

Cover all the unused terminal ports.

n

If the field wiring is changed and lines for which lugs have already been broken off from 
the protective cover are removed, you must replace the protective cover with a new one.

Содержание FB Remote I/O

Страница 1: ...FB Remote I O Hardware PROCESS AUTOMATION MANUAL...

Страница 2: ...erms of Delivery for Products and Services of the Electrical Indus try published by the Central Association of the Electrical Industry Zentralverband Elektrotechnik und Elektroindustrie ZVEI e V in it...

Страница 3: ...ane and Module Compatibility 15 2 6 I O Modules Com Units Bus Termination Modules Power Supplies 16 2 6 1 Layout 16 2 6 2 Function 17 2 6 3 Design and Dimensions of the Modules 20 2 7 Accessories 21 2...

Страница 4: ...3 2 Media Redundancy 53 3 13 3 Application Redundancy 53 3 14 Fieldbus Connection 54 3 14 1 RS 485 Based Fieldbuses 54 3 14 2 Ethernet Based Fieldbuses 56 3 14 3 Cable Gland for Prefabricated Cables t...

Страница 5: ...tes Control drawings Other documents 1 2 Target Group Personnel Responsibility for planning assembly commissioning operation maintenance and dismounting lies with the plant operator Only appropriately...

Страница 6: ...d in descending order as follows Informative Symbols Action This symbol indicates a paragraph with instructions You are prompted to perform an action or a sequence of actions Danger This symbol indica...

Страница 7: ...ules on the backplane and the process control system Power supplies are used to power the I O modules and com unit gateway All components of the FB remote I O with Ex q protection meet the FB concept...

Страница 8: ...ew Figure 2 1 FB remote I O system components 1 Field Unit Surrounding Enclosure 2 Power supply 3 Bus termination module 4 Com unit 5 I O module 6 Backplane 7 Cable gland for field lines 8 Cable gland...

Страница 9: ...tains Ex e terminals for power and communication lines For safety these are individually equipped with protective covers IP30 and touch protection The surrounding enclosures are equipped with a rating...

Страница 10: ...t you with designing your ideal FB remote I O More information can be found at www pepperl fuchs com Order designation Type Max number of slots Material Field unit Redundant field unit Stainless steel...

Страница 11: ...kplanes in the following combinations Warning Risk of death as a result of using a damaged or tampered backplane Using a defective or tampered backplane means that explosion protection can no longer b...

Страница 12: ...DP MODBUS RTU MODBUS TCP Ethernet Figure 2 4 FB9262BP10220 1 dimensions 1 Power supply 2 Bus termination module when used as a base backplane Empty slot when used as an extension backplane 3 Gateway w...

Страница 13: ...n used as a base backplane Empty slot when used as an extension backplane 3 Com unit when used as a base backplane Empty slot when used as an extension backplane 4 Slots for 20 narrow or 10 wide I O m...

Страница 14: ...P24110 1 n Base backplane n Non redundant configuration with slots for 1 com unit bus termination modules see chapter 2 6 and 1 power supply n Slots for max 24 narrow or 12 wide I O modules n For PROF...

Страница 15: ...00 1 dimensions 2 5 3 Backplane and Module Compatibility In principle FB backplanes are compatible with all FB modules Narrow I O modules occupy one slot while wide I O modules occupy two slots Howeve...

Страница 16: ...the module offer 1 2 4 and 8 channels to connect Ex field devices Using the single channel modules for controlling valves including feedback two additional binary input signals can be transmitted from...

Страница 17: ...odules on the backplane are equal so you can use I O modules with different functions next to each other The various I O modules can be plugged in Com unit Com units form the interface between the I O...

Страница 18: ...nites an explosive mixture n Do not pull out M12 connectors in potentially explosive atmospheres n Use only original Pepperl Fuchs cables Warning Property damage due to incorrect terminal assignment I...

Страница 19: ...of the bus line A bus termination module is required in each final unit of a bus line Power supplies The power supplies provide power to all components of the FB remote I O The slots for com units are...

Страница 20: ...ways wide modules Bus termination modules are narrow modules Both the I O modules and the com units and power supplies are equipped with LEDs on the front that display the device status The I O module...

Страница 21: ...e LB9107P LB9115A LB9116A LB9126A LB9130A Black LB9109 E 6 1 LB9109 E 8 1 LB9109 E 8 2 Figure 2 11 Screw terminal dimensions L 33 3 mm for 6 pin terminals and 40 9 mm for 8 pin terminals Figure 2 12 F...

Страница 22: ...ve parts are exposed Use black protective covers for non intrinsically safe circuits that comply with type of protection Ex e n Protective covers Black LB9107 E 6 LB9107 E 8 Figure 2 15 Dimensions of...

Страница 23: ...protective cover L 33 3 mm for 6 pin terminals Coding pins Coding pins provide a unique assignment between I O modules and terminal blocks or the associated field devices To do this the coding pins a...

Страница 24: ...feedback input FB2201B FB2213E The watchdog plug sends the output signal from the I O module back to its input channel making it possible to check the function of the I O module as well as the communi...

Страница 25: ...network must be installed to ensure that the line fault detection function can work correctly Using the additional resistor network the electronics can distinguish between a closed switch and a short...

Страница 26: ...ne and the I O modules on the extension backplane The length of the backplane cordset is up to 3 m Overview of cordsets Cordset for gateways There are two types of cordsets for gateways One with a wir...

Страница 27: ...way the module can be replaced without a hot work permit via the two stage removal process Use the removal tool with item number 536627 for wide modules and the removal tool with item number 536628 f...

Страница 28: ...sonnel have relevant experience in this area They know and understand the rules and standards for the components and systems n Before you begin installation make sure that the atmosphere is not potent...

Страница 29: ...rning Explosion hazard due to thermal ignition and violation of protection type Make sure that the maximum ambient temperature for the components used is not exceeded Details of ambient temperature ca...

Страница 30: ...n The separate shutdown input deactivates the outputs with a single action In order to avoid unnecessary diagnostic messages the output circuit is interrupted rather than simply switching off the modu...

Страница 31: ...n the supply lines to a minimum Danger Explosion hazard due to the use of non suitable devices Devices that do not meet the requirements for use in explosion hazardous areas can cause explosive mixtur...

Страница 32: ...cause the maximum permissible temperature within the enclosure and the maximum permissible surface temperature of the surrounding enclosure to be exceeded Perform a heat calculation to determine the m...

Страница 33: ...measures to be disconnected during operation Do not connect or disconnect the module while the circuit is live and while it cannot be guaranteed that the surroundings do not present an explosion hazar...

Страница 34: ...hese modules from being accidentally plugged into the slot of an I O module Slots for I O modules have equal status meaning functions can be arranged side by side as required I O modules with intrinsi...

Страница 35: ...al paper so that the I O modules engage properly at all times Figure 3 6 An example of backplane labeling 2 Arrange the modules on the backplane from left to right 3 Push the I O module into the slot...

Страница 36: ...x d modules and right column with Ex q modules The I O module is now mounted to the backplane Rasthaken 1 Rasthaken 2 Backplane Rasthaken 1 Rasthaken 2 Backplane Note All modules with Ex e front conne...

Страница 37: ...osion protection can no longer be guaranteed Only remove modules using the built in removal device The built in removal device forces a two stage removal process that contains any potential ignition s...

Страница 38: ...together with the FB removal tool out of the backplane Figure 3 11 Pull out the module together with the front socket removal tool The second rear catch is released and the module is removed from the...

Страница 39: ...illimeters until you feel resistance from the second rear catch Warning Explosion hazard due to damaged modules Forcibly removing modules or using unsuitable tools can damage the module or the backpla...

Страница 40: ...3 14 Integrated removal device 5 Loosen the second rear catch on the backplane To do this press the integrated removal levers on the top and bottom of the module using your thumb and index finger Pul...

Страница 41: ...designed for Ex e type of protection 3 Ex d Modules with non intrinsically safe circuits and cable tails I O modules with a cable tail must be connected to separately approved terminals that comply wi...

Страница 42: ...5 and 6 Figure 3 17 Stranded conductor with wire end ferrule Warning Explosion hazard due to unapproved measuring devices Ensure that measuring devices also satisfy the requirements of their respecti...

Страница 43: ...cross section of 0 75 mm2 3 If you are using stranded conductors crimp the stranded conductors with wire end ferrules 4 Make sure that the insulation on the conductors extends all the way to the term...

Страница 44: ...nded 8 If necessary code the front sockets of the I O modules and terminals so that the terminals and the associated field devices can be assigned to exactly one front socket 9 Plug the terminals into...

Страница 45: ...rotective cover into place using the side screws Figure 3 19 Terminal with adapted protective cover for Ex e modules 12 Apply the warning marking Warning non intrinsically safe circuits protected by i...

Страница 46: ...conductors extends all the way to the terminal 5 Follow the manufacturer s mounting instructions to install the terminals and the cover 6 Unused cables and connection lines must be either connected to...

Страница 47: ...r single width I O modules Color coding for dual width I O modules Connection Color 6 pink 5 gray 4 yellow 3 green 2 brown 1 white Left connection Right connection Color 8 16 red 7 15 blue 6 14 pink 5...

Страница 48: ...to match the front socket cut off the plastic lugs from the terminal from those points where coding pins are located in the front socket Note that the coding in example 1 and example 2 is not unique...

Страница 49: ...etection 3 9 Cold Junctions in Thermocouples The I O modules FB5202 and LB5205 are equipped with an internal cold junction However they can also be used with an external cold junction The temperature...

Страница 50: ...make a note of the measured value 4 In the configuration software set the measuring input of the I O module to 2 wire measurement with Pt100 sensor 5 Enter the measured resistance in the Line resista...

Страница 51: ...bridge voltage of 7 V is produced With a bridge sensitivity of 2 mV V a voltage of 14 mV results at full load Configuring I O Modules for Strain Gage Measurement 1 Either set the FB4 01 analog output...

Страница 52: ...ot lit the com unit is passive For more information about the status LEDs refer to the datasheet for the relevant com unit in use As a general rule a distinction is made between media redundancy and a...

Страница 53: ...ended media redundancy Figure 3 24 Extended media redundancy 3 13 3 Application Redundancy In application redundancy the master has two redundant interfaces to allow it to access both the fieldbus and...

Страница 54: ...oper installation Improperly installed fieldbuses can cause explosive mixtures to ignite Observe the wiring specifications set out in IEC EN 60079 14 for laying lines in an explosion hazardous area Da...

Страница 55: ...data at high speeds over long distances 1000 m at 1 5 Mbit s Terminators The RS 485 fieldbus must have exactly two terminators per segment one at the start and one at the end A segment usually starts...

Страница 56: ...ough an M12 plug connection according to IEC 61076 2 101 2012 Three basic connection scenarios are shown below Figure 3 26 Connection scenarios Zone 1 Gateway I O modules Enclosure Gateway GW IOM GW I...

Страница 57: ...sion hazardous areas A cable with an M12 plug must be connected either directly to another M12 connection in the explosion hazardous area or directly to an RJ45 port in the safe area n Plugging and un...

Страница 58: ...ectly attached to the screw sleeve Insert the screw sleeve through the thru hole 3 Feed the union nut onto the screw sleeve from inside the enclosure and tighten the union nut to the specified torque...

Страница 59: ...torque specified in the table The seal is compressed and seals the cable gland Tightening torque for screws Removing seal for pre assembled cable Figure 3 28 Removing the seal 1 Unscrew the bolts cros...

Страница 60: ...oise is active across the entire area Figure 3 30 Reduced admission of interfering signals in twisted pair cable A shielding keeps interfering noise away from the communication path Figure 3 31 Shield...

Страница 61: ...uts are normally controlled by NAMUR proximity switches with a low impedance signal In this case noise has a far lower impact than in circuits containing open switches that do not have an additional r...

Страница 62: ...com unit the new configuration in the com unit is activated and the old configuration is deleted For more information refer to the software manual for the com unit used Extending the fieldbus In orde...

Страница 63: ...B remote I O unit 4 Measure the current at the bus connector between A and B It must be possible to measure a current of I 5 V 2 390 6 4 mA between A and B If the current is significantly higher by a...

Страница 64: ...om unit can be set up via either the fieldbus or the service bus For more information refer to the software manual for the com unit used 4 3 Startup Phase For the purposes of fault analysis we recomme...

Страница 65: ...for the I O modules via the com unit For more information refer to the software manual for the com unit used In addition you can read off basic information about supply and communication from the LEDs...

Страница 66: ...ith one another Communication error on the service bus Check that the cables are connected Check that the nodes are positioned in linear form and without branches A star shaped layout is not permitted...

Страница 67: ...ront sockets using com unit cordset LB9140A I O modules are continuously changing the data Check whether one of the com units has not been configured for redundancy mode If this is the case both com u...

Страница 68: ...er the measured value is being distorted by external influences Check that the shielding is intact I O module reported to be faulty Check that the correct I O module is plugged in Check that the green...

Страница 69: ...rl fuchs com Worldwide Headquarters Pepperl Fuchs GmbH 68307 Mannheim Germany Tel 49 621 776 0 E mail info de pepperl fuchs com For the Pepperl Fuchs representative closest to you check www pepperl fu...

Отзывы: