Installation
Any cable used has to fullfil the following specifications:
■
The cable needs to be rated for at least 60
°
C.
■
The cable has to be double insulated.
■
The cable has to have an individual wire size of at least 18 AWG (0.75 mm
²
).
■
The cable has to have a ground conductor with the same size as the other 2 conductors.
■
The cable must be rated for 10 A for the AC version.
■
The cable has to be connected to a type TN power system, protected by a maximum 20 A
breaker or fuse.
■
The socket outlet should be close to the equipment and easily accessible.
Figure 3.5
C14 receptacle
1 & 3 = AC power
2 = ground
DC 12 V
For 12 V
DC
power, you insert a power jack into the back of the unit. The connector on the back
of the unit is a 5.5 mm barrel jack. The polarity of the plug is center positive. For this option, an
AC power adapter with 5.5 mm barrel jack is supplied.
Figure 3.6
12 V
DC
barrel jack
Warning!
The connector on the back of the unit is an IEC320-C14 receptacle and requires a mating of an
IEC320-C13.
The intended installation location is an overvoltage category II. The Industrial Box Thin Client
BTC01 comes with an AC power cable that is intended for US type outlet. Other power cables
for other global regions are available as accessories. See chapter 2.5.
1
2
3
Warning!
The 12 V
DC
power has to be provided from a rated supply of -20
°
C to 60
°
C, and has to
provide a SELV output according to IEC60950-1. This supply has to be powered from an OVC II
source.
12 VDC