31
DO
CT
-1946C
2018-
07
322
903
Trip Amplifier 2/209
Software description
EN
4.3.6
Device Programming P707 (PC menu only)
Entering parameter P707 = 1 will delete all data in EEPROM. The device will then expect
to receive a new identification ID, 20 constants, 200 programming steps and a CRC
(checksum) following data transmission.
Once data transmission has been completed successfully data are copied to EEPROM
followed by an echo of 0. Otherwise 1 is echoed. The PC program will control data
transmission and the generation of the CRC.
4.3.7
Test parameters
Test parameters are used for electrical device checks.
Check analog inputs and push buttons (ONLINE)
Check calibration data (ONLINE). Both microprocessors contain calibration data about
the redundant analog inputs assigned to them.
4.3.8
Calibration
Devices are calibrated ex works. Therefore recalibration is not normally required after
commissioning. An annual check is regarded as being sufficient. Range changes or live/
dead zero changes do not involve recalibration.
Recalibration is also not required after changing from current to voltage inputs or vice
versa (also 5V ... 10V) because precision resistors have been used.
Set the MODE jumper to PROG (4–5) and the TEST jumper to X2. Connect the device
to the PC using the TERMINAL EMULATOR <ALT><E> (see section "Numerical
parameter list").
1. Set all analog inputs to 100 %
2. Enter P790=1 (calibrate analog inputs)
3. Display P790 = n
n = 0 o.k.
n = 1...8 error in channel
n
n = 9 jumper TEST disabled
P711
analog input 1 corresponding to 0 ... 1 (read)
P712
analog input 2 corresponding to 0 ... 1 (read)
P713
analog input 3 corresponding to 0 ... 1 (read)
P714
analog input 4 corresponding to 0 ... 1 (read)
CPU A
P781
read calibrate analog input 1A
P782
read calibrate analog input 2A
P783
read calibrate analog input 3A
P784
read calibrate analog input 4A
CPU B
P785
read calibrate analog input 1B
P786
read calibrate analog input 2B
P787
read calibrate analog input 3B
P788
read calibrate analog input 4B
Содержание 2/209
Страница 1: ...ISO9001 Trip Amplifier 2 209 PROCESS AUTOMATION MANUAL...
Страница 10: ...9 DOCT 1946C 2018 07 322903 Trip Amplifier 2 209 Technical data EN 2 10 Block diagram 2 11 Connection diagram...
Страница 11: ...DOCT 1946C 2018 07 322903 Trip Amplifier 2 209 Technical data 10 EN 2 12 Front control elements...
Страница 49: ...DOCT 1946C 2018 07 322903 Trip Amplifier 2 209 Notes 48 EN...
Страница 50: ...49 DOCT 1946C 2018 07 322903 Trip Amplifier 2 209 Notes EN...