Prior to calling this rate of change alarm use the timer command TIM,op5 to enter the
time since the last call in memory cell op5.
An input or a computed value op1 is monitored for change op3 per time interval op2. The
up-to-date value of op1 will be compared with the old value in op6 (op3 = op1 - op6)
when the time integral op7 > op2. If the change per time interval op3 is above 0 the
gradient is positive. If the change per time interval op3 is less 0 the gradient is negative.
Memory cells op6 to op9 must not be overwritten during the remaining user program.
Example
GRD,E01,K01,K02,K03,X01,X02,X03,X04,X05
Call
GRD,op1,op2,op3,op4,op5,op6,op7,op8,op9
GRD = (gradient) monitor rate of change
op1 = input value to be monitored
op2 = time interval in ms
op3 = max change per time interval
op4 = hysteresis
op5 = time since last call
op6 = input memory (start value)
op7 = time memory (integral of op5 in ms)
op8 = alarm memory
op9 = alarm -1, 0, 1
Formula
op9 = 1 for alarms or if op9 was 1 before
op9 = 0 while inside deadband or if op9 was 0 before
op9 = -1 when there is no alarm
Содержание 2/209
Страница 1: ...ISO9001 Trip Amplifier 2 209 PROCESS AUTOMATION MANUAL...
Страница 10: ...9 DOCT 1946C 2018 07 322903 Trip Amplifier 2 209 Technical data EN 2 10 Block diagram 2 11 Connection diagram...
Страница 11: ...DOCT 1946C 2018 07 322903 Trip Amplifier 2 209 Technical data 10 EN 2 12 Front control elements...
Страница 49: ...DOCT 1946C 2018 07 322903 Trip Amplifier 2 209 Notes 48 EN...
Страница 50: ...49 DOCT 1946C 2018 07 322903 Trip Amplifier 2 209 Notes EN...