Software description
EN
4.2.8
Live zero conversion
This command serves to convert live zero input signals into engineering units. That way
measured values and trip points can be displayed as °C, m
3
/h, % or other engineering
units. The user does not have to establish conversion formula for himself.
Example
•
Begin = 180 at 4 mA
•
Full scale = 380 at 20 mA
•
Display = 280 at 12 mA
The device front offers space for entering TAG numbers and engineering units. Enter
•
0 = beginning
•
100 = full scale
in order to display percentage values.
Live zero signals: 4 mA ... 20 mA, 1 V ... 5 V, 2 V ... 10 V
4.2.9
Dead zero conversion
Convert dead zero input signals into engineering units.
The function is equivalent to the live zero conversion.
Dead zero signals: 0 mA ... 20 mA, 0 V ... 5V, 0 V ... 10 V
Call
CLI, op1, op2, op3, op4 (convert live input)
CLI = live zero - measuring range
op1 = input (AE1 ... AE4)
op2 = beginning of range
op3 = full scale
op4 = result
Formula
op4 = (op1-0.2) / 0.8 x (op3-op2) + op2
Call
CDI, op1, op2, op3, op4 (convert dead input)
CDI = dead zero - measuring range
op1 = input (AE1 ... AE4)
op2 = beginning of range
op3 = full scale
op4 = result
Formula
op4 = op1 x (op3-op2) + op2
Содержание 2/209
Страница 1: ...ISO9001 Trip Amplifier 2 209 PROCESS AUTOMATION MANUAL...
Страница 10: ...9 DOCT 1946C 2018 07 322903 Trip Amplifier 2 209 Technical data EN 2 10 Block diagram 2 11 Connection diagram...
Страница 11: ...DOCT 1946C 2018 07 322903 Trip Amplifier 2 209 Technical data 10 EN 2 12 Front control elements...
Страница 49: ...DOCT 1946C 2018 07 322903 Trip Amplifier 2 209 Notes 48 EN...
Страница 50: ...49 DOCT 1946C 2018 07 322903 Trip Amplifier 2 209 Notes EN...