21
Installation and User’s Guide
5.
Relay Remote
–
In relay remote operation, the heat pump is started and stopped by remote relays which are
connected to the remote POOL, COMMON and SPA quick connect connectors on the back of the control
board. When conductivity is provided between the pool and common connections or the spa and common
connections, the heat pump will start as long as the water temperature is not over the local set point (under for
chiller operation). The local set points are active in relay remote operation.
a. To activate the relay Remote Mode, press the MENU SELECT button repeatedly until the Relay Remote
screen is displayed. Once displayed, press the UP or DOWN arrows to toggle between ON and OFF. The
last option shown on the display will become active.
6.
Serial Remote
–
In serial remote operation, the heat pump is made to start and stop via a serial RS-485
communications link with a Pentair automation controller. When operating in this mode, the heat pump's
local set point is disregarded. The heat pump will heat or cool as told by the automation controller without regard
to the local set point. However, the high and low temperature faults are still active so the heat pump will not
heat above 104° F. or cool below 45° F. To use the Serial Remote mode, the Serial Remote should be turned
ON (default setting) and, the Intell Address screen from the Operator Setup Menu Tree must be assigned to
the proper address. One (1) is the most commonly used address.
a. To activate the Serial Remote Mode, press the MENU SELECT button repeatedly until the Serial Remote
screen is displayed. Once displayed, press the UP or DOWN arrows to toggle between ON and OFF. The
last option shown on the display will become active.
b. The Address on the IntelliTouch
®
Address screen must match the address being used on the IntelliTouch
®
.
The IntelliTouch
®
address can be changed from the Operator Setup Menu as described below:
i.
Press the UP and DOWN arrows simultaneously. The Language Selection screen should be
displayed.
ii.
Then press the MENU SELECT button repeatedly until the Intell Address screen is displayed.
Once displayed, press the UP or DOWN arrows to select the address being used in the automation
controller. The last address shown on the display will become active.
7.
Temperature Scales
– The control board can display temperatures in either degrees Fahrenheit or Celsius.
The temperature scale in use can be changed from the Operator Setup Menu Tree as described below:
a. Press the UP and DOWN arrows simultaneously. The Language Selection screen should be displayed.
RELAY REMOTE
REMOTE IS ON/OFF
LANGUAGE / IDIOMA
SELECTED - ENGLISH
INTELL ADDRESS
ADDRESS = 1 - 16
LANGUAGE / IDIOMA
SELECTED - ENGLISH
SERIAL REMOTE
ON/OFF