Installer Manual Riversoft - Description
18 / 90
Ref. MKT-IM-045 / A - 13.03.2020
Valve configuration
Injector.................................................... E .......................G .......................F ....................... H
DLFC ....................................................... 6 gpm................8 gpm ...............7 gpm ............... 9 gpm
BLFC ....................................................... 0.14 gpm...........0.14 gpm ..........0.14 gpm .......... 0.14 gpm
Cycles duration [min]
Estimated water consumption per regeneration [L]
Softener connections
Inlet/Outlet.............................................. ¾" BSPT, male
Drain line ................................................ ½"
Overflow drain line ................................. ½"
Electrical
Controller Operating Voltage ................. 12 VAC (requires use of Pentair Water supplied transformer)
Input Supply Frequency.......................... 50 or 60 Hz
Motor Input Voltage ................................ 12 VAC
Controller Power Consumption ............. 6 W average
Protection rating..................................... IP23
Transient overvoltages ........................... within the limits of category II
Pollution Degree..................................... 3
Temporary overvoltages must be limited in duration and in frequency.
Riversoft 4
Riversoft 8
Riversoft 15
Riversoft 30
C1
1
1
1
1
1
1
3
3
3
3
3
3
C2
27
28
30
29
31
34
52
56
63
59
66
81
C3
3
3
3
3
3
3
3
3
3
3
3
3
C4
1
1
1
1
1
1
3
3
3
3
3
3
C5
1
1
1
1
1
1
1
1
1
1
1
1
C6
1
1
1
1
1
1
1
1
1
1
1
1
C7
1.7
2.5
4.1
3.4
5
8.3
54.8
58.5
65.6
12.5
18.8
31.2
Riversoft 4
Riversoft 8
Riversoft 15
Riversoft 30
24.6
25.5
27.4
36.1
38.0
41.3
54.8
58.5
65.6
104.5
113.1
131.0
Содержание Riversoft
Страница 1: ...Riversoft Water Softener INSTALLER MANUAL WATER PURIFICATION...
Страница 61: ...Installer Manual Riversoft Maintenance Ref MKT IM 045 A 13 03 2020 61 90...
Страница 65: ...Installer Manual Riversoft Maintenance Ref MKT IM 045 A 13 03 2020 65 90...
Страница 73: ...Installer Manual Riversoft Maintenance Ref MKT IM 045 A 13 03 2020 73 90 PAGE INTENTIONALLY LEFT BLANK...
Страница 75: ...Installer Manual Riversoft Maintenance Ref MKT IM 045 A 13 03 2020 75 90...
Страница 77: ...Installer Manual Riversoft Maintenance Ref MKT IM 045 A 13 03 2020 77 90 turn turn Point 0 Point 0...
Страница 89: ...Installer Manual Riversoft Disposal Ref MKT IM 045 A 13 03 2020 89 90 PAGE INTENTIONALLY LEFT BLANK...
Страница 90: ...www pentairaquaeurope com...