Commissioning and Preventive
Maintenance
Raychem-IM-H57548-HWATsystem-EN 16/08
put in Section 9 for an indication of heating cable
performance:
Ground-fault test
Test all ground-fault breakers per manufacturer’s
instructions.
Cable and Connection Continuity
Cable and connection continuity test verifies all the
electrical connections are made properly. Pentair
recommends conducing this test as the cable is
installed to identify any potential problems imme-
diately. This test can also be conducted after the
entire cable run is installed but before end seals are
applied.
8.2
Preventative Maintenance
Recommended maintenance for HWAT Systems
consists of performing the system tests for commis-
sioning, and on a regular basis. Procedures for these
tests are described in Section 9. Systems should be
checked each year. If the HWAT System fails any of
the tests, refer to Section 10 for trouble shooting
assistance. Make the necessary repairs and replace
any damaged cable immediately. De-energize all cir-
cuits that may be affected by maintenance. Protect
the heating cable from mechanical or thermal dam-
age during maintenance work.
Maintenance records
The “Installation and Inspection Record,” (refer to
Section 11) should be filled out during all mainte-
nance and repairwork and kept for future reference.
Repairs
Use only HWAT heating cable, HWAT-ECO or ACS-30
controller, and RayClic connection kits when replac-
ing any damaged heating cable system. Repair the
thermal insulation to original condition or replace
with new insulation, if damaged. Retest the system
after all repairs or replacements.
WARNING: Damage to cables or components can
cause sustained electrical arcing or fire. Do not
attempt to repair damaged heating cable. Do not
energize cables that have been damaged by fire.
Replace damaged cable at once by removing the
entire damaged section and splicing in a new length
using the appropriate RayClic splice kits.