![Pentair Raychem HWAT System Скачать руководство пользователя страница 2](http://html1.mh-extra.com/html/pentair/raychem-hwat-system/raychem-hwat-system_installation-and-operation-manual_1525813002.webp)
ii
Raychem-IM-H57548-HWATsystem-EN 16/08
Important Safeguards and Warnings
WARNING: FIRE AND SHOCK HAZARD
Raychem HWAT Systems must be installed
correctly to ensure proper operation and to prevent
shock and fire. Read these important warnings and
carefully follow all the installation instructions.
• To minimize the danger of fire from sustained
electrical arcing if the heating cable is damaged or
improperly installed, and to comply with Pentair
Thermal Management requirements, agency certifi-
cations, and national electrical codes, ground-fault
equipment protection must be used on each heating
cable branch circuit. Arcing may not be stopped by
conventional circuit breakers.
• Approvals and performance are based on the use of
Pentair Thermal Management parts only. Do not sub-
stitute parts or use vinyl electrical tape.
• Bus wires will short if they contact each other. Keep
bus wires separated.
• Connection kits and heating cable ends must be kept
dry before and during installation.
• The black heating cable core is conductive and can
short. They must be properly insulated and kept dry.
• Damaged bus wires can overheat or short. Do not
break bus wire strands when preparing the cable for
connection.
• Damaged heating cable can cause electrical arc-
ing or fire. Do not use metal attachments such as
pipe straps or tie wire. Use only Pentair Thermal
Management approved tapes and cable ties to secure
the cable to the pipe.
• Do not attempt to repair or energize damaged cable.
Remove damaged cable at once and replace with a
new length using the Raychem RayClic-S splice kit.
Replace damaged connection kits.
• Use only fire-resistant insulation which is
compatible with the application and the maximum
exposure temperature of the system to be traced.