background image

1) SETTINGS:  (Has 5 submenus) 

Time

(2 parameters):

Hour:

Allows you to change the time of day.

Date:

Allows you to change the calendar day.

PID Control:

Changing these parameters is NOT

recommended. These parameters control the drive’s
reaction to pressure changes in the system. They should
be considered as a group. If it seems necessary to alter
anything in this group, please call Pentek Customer
Service at 1-300-137-344 BEFORE YOU START. Also,
note that the last item on the main menu resets ALL
parameters to the default values.

Sleep

(6 parameters plus Reset):

Boost Differential:

Raises the system pressure

slightly before going into sleep mode. Units are in
PSI. The default boost value is 20 kPa.  (i.e., with
Boost Differential set to 20 kPa and Pressure
Setpoint set to 400 kPa, the system pressure will
rise to 420 kPa before the drive goes to sleep).
Maximum is 70 kPa, minimum is 20 kPa.

Boost Delay:

The length of time (in seconds) that

the drive monitors the system before boosting the
pressure. Default is 60 seconds, maximum is 
300 seconds, minimum is 30 seconds.

Wakeup Differential: 

The total pressure drop from

the setpoint that the drive must see to come out of
Sleep mode. The default setting is 35 kPa (i.e., with
the Wakeup Differential set to 35 kPa, the drive
will wake up when the pressure in the system has
dropped 35 kPa below the system Pressure
Setpoint.) Maximum is 100 kPa, minimum is 
35 kPa.

Wake Delay:

The time it takes to ramp down to the

Wake Up pressure. Default is 15 seconds,
maximum is 120 seconds, minimum is 3 seconds.

Sleep 2 PRESSURE:

A setting to prevent Over-

Pressure. If the system pressure rises enough that
the drive reaches the Sleep 2 PRESSURE setpoint,
the drive will go to sleep for one minute. Default
pressure is 550 kPa, maximum is ‘Max Sensor’
value minus 20 kPa, minimum is 100 kPa. 
• 

NOTE:

If the Internal or External Setpoint is set to

a value that is near, at, or above the 
Sleep 2 PRESSURE setpoint,  you may experience
nuisance tripping. In this case, raise the 
Sleep 2 PRESSURE setpoint until the nuisance
tripping stops.

Boost Trigger: 

Sets the frequency range that defines

system stability. When the frequency stabilizes
within this range, the drive starts the boost process.
Increasing this value allows the drive to sleep
under less stable conditions. The default is 3 Hz.
The range is 3 to 30 Hz.

Reset to defaults: 

Default value is NO. Change to

YES to reset all Sleep parameters to their default
values.

Password 

(2 parameters):

Password Timeout:

Sets the time (in minutes) that

the drive takes to lock out the password-protected
(blue) buttons on the keypad. The range is 
1 – 360 minutes; the default is 60 minutes. When
drive programming is complete, a timer starts.
Once it reaches the time set in this parameter the
buttons automatically lockout.

Password:

The Password locks or unlocks the blue

buttons on the keypad. The password is a number
(default is 7777) and can be changed to any 1- to
4-digit number.

Setpoints

(2 Parameters): 

Internal Setpoint:

The main pressure setting used by

the drive. The default value is 400 kPa. Maximum
is the ‘Max Sensor’ value minus 20 kPa, minimum
is 100 kPa.

External Setpoint:

The Drive’s pressure reference

when the External Input is set to External Setpoint
and the proper drive is connected to it (see I/O
section, Pages 11 and 12). Default is 300 kPa,
Maximum is ‘Max Sensor’ minus 20 kPa, minimum
is 100 kPa.

2) MOTOR (4 parameters plus Reset):

Service Factor Amps:

The service factor amps of the

motor. This value is entered during the setup
process and can be changed if necessary. For your
Global motor, use the value listed in Table 5, 
Page 8. This value may differ slightly from the
motor’s nameplate amps. For other manufacturer’s
3-wire, 1-Phase motors, use the Cap Start/Cap Run
values supplied by the motor manufacturer. 

Min Frequency:

The minimum frequency that the drive

will send to the motor (this translates to the slowest
speed at which the motor will run).  The default is 
30 Hz.  If necessary this value can be increased, but
cannot exceed the Max Frequency value.

Max Frequency:

This is the maximum frequency

the drive will send to the motor (this translates to
the highest speed at which the motor will run).
The default is 50 Hz.  

Reset to defaults:

Default value is NO. Change to

YES to reset all Motor parameters to their default
values.

Operation / Programming

10

Содержание PENTEK INTELLIDRIVE PID2000-1123

Страница 1: ...INSTALLATION MANUAL PENTEK INTELLIDRIVE PID2000 1123 www onga com au 2010 PNX900 Rev 9 14 10 Installation Operation Parts For further operating installation or maintenance assistance Call 1 300 137 344 ...

Страница 2: ... Pressure Tank Serial No ______________________________________________ Dealer Installer _____________________________________________________ __________________________________________________________________ Installer Phone No ___________________________________________________ Date of Installation ___________________________________________________ Wire Lengths in Feet Metres Circuit Breaker to...

Страница 3: ... on an independent branch circuit protected by a circuit breaker see Table 2 Page 6 for circuit breaker sizing with no other appliances on the circuit Risk of burns The drive can become hot during normal operation Allow it to cool for 10 minutes after shut down before handling it to avoid burns Risk of electric shock A means for disconnection from the supply mains having a contact separation in al...

Страница 4: ... to operate 4 submersible pumps Each drive is rated for maximum output amp rating Any use of the drive outside of its intended use and design parameters will void the warranty Transducer The drive uses a 4 20mA 0 690 kPa pressure transducer to control the speed of the motor The transducer senses pressure in the pipe and converts it to an electrical signal which it sends to the drive The drive proc...

Страница 5: ...staller to pump out the well Toggles the pressure setpoint between 300 400 and 500 kPa default is 400 Views and changes parameters Shows the last 15 faults Changes the display to the previous screen With code locks and unlocks the password protected keys default password is 7777 Selects menu items and confirms numeric value changes The up and down arrows scroll through the menus and change numeric...

Страница 6: ...g area is free of electronics other than the terminals Conduit holes and knockouts are located so that the wire can be fed straight through to the connectors with minimal bending The terminals accept 1 5 to 4 0mm2 wire NOTE For convenience in wiring the input and motor terminals unplug from the box Pull them down to remove them for ease of access See Figure 4 BE SURE that when you replace them the...

Страница 7: ...ycling of the pump Table 4 Control Pressure Set Point and Tank Pre Charge Pressure Values NOTE Set the pressure tank s pre charge to 70 of the system operating pressure When using an external set point as well as an internal set point pre charge the tank to 70 of the lower set point of the two Some applications may require a different percentage when figuring the set point Transducer Connections S...

Страница 8: ...onal parameters occasionally See Advanced Programming Page 9 for information about accessing all parameters explanations of their functions and procedures for changing parameter values if necessary 1 Program the Drive Apply power to the PENTEK INTELLIDRIVE Setup Guide will appear A Service Factor Amps See Sidebar Service Factor Amps 1 Use DIRECTIONAL Arrows to enter the correct service factor amps...

Страница 9: ...information on Keypad functions see the Parameters section Changing a Parameter Value NOTE This procedure works for ANY parameter 1 Find the parameter and display the current parameter value on the screen 2 Press ENTER to enable editing of the parameter 3 Use the UP DOWN LEFT and RIGHT arrows to change the parameter values 4 Press ENTER again to save the new parameter value NOTE A shorthand way to...

Страница 10: ...gger Sets the frequency range that defines system stability When the frequency stabilizes within this range the drive starts the boost process Increasing this value allows the drive to sleep under less stable conditions The default is 3 Hz The range is 3 to 30 Hz Reset to defaults Default value is NO Change to YES to reset all Sleep parameters to their default values Password 2 parameters Password...

Страница 11: ...he event of nuisance dry run faults Fill Time The amount of time the drive will operate in line fill mode For self primers increase value to allow for priming Default is 60 seconds Range is 15 to 600 seconds Reset Window Read Only The time window allowed for resets after a Dry Run Fault This is calculated based on the values in the two parameters above Auto Reset Relay and Number of Resets 6 I O T...

Страница 12: ... V to the right of I O terminal I1 See Figures 6 and 7 Output Relay Rating The unique design of the PENTEK INTELLIDRIVE allows this output to be 24V DC or 24 240V AC Power can be supplied 24VDC from terminals V and V to the right of I O terminal I1 See Figures 8 and 9 The Output Relay is rated at 5A 30VDC or 8A 240VAC Note To connect the wires to either terminal 1 Strip the wires back about 1 2 2 ...

Страница 13: ...re correct Make sure pump and motor are correct Locked rotor Pull pump check for debris in pump Dry Run Well draws down too far pump runs dry Check water depth Under sized pump or motor Make sure pump and motor are sized correctly Leak in the pipe system Check system for leaks Intermittent transducer connection Check transducer cable for loose connections or damaged insulation Cannot reach pressur...

Страница 14: ...ake sure that all vents are clear Drive goes into TPM and limits the motor current until it is within the operating temperature Pipe Break Leak detected Check for any leaks in the pipe system Application calls for long run times Extend run time limitation Go to Main Menu Pipe Break No of Days without Sleep to verify preset value and change if needed Disable Pipe Break Fault Go to Main Menu Pipe Br...

Страница 15: ...or pulses motor to try to free it NOTE No user action is required when a Warning is displayed Table 6 AWG Wire Sizing VFD to 3 Wire 1 Phase Motor NOTE Information in this Table applies ONLY to Global Series motors For other motors refer to motor manufacturer s specifications for wire sizing VFD Global Volts Maximum Cable Length in Metres Model Motor HP Hz Ph kW Amps 1 5 mm2 2 0 mm2 2 5 mm2 3 5 mm2...

Страница 16: ...pplication improper installation or improper maintenance Without limiting the foregoing operating a three phase motor with single phase power through a phase converter will void the warranty Your only remedy and PENTAIR WATER s only duty is that PENTAIR WATER repair or replace defective products at PENTAIR WATER s choice You must pay all labor and shipping charges associated with this warranty and...

Отзывы: