background image

The transducer terminals, marked AI+ and AI-, are located
to the left of the output terminals. Connect the red wire of
the transducer cable to AI+, connect the black wire to AI–,
and connect the cable shield to the metal lug to the right.

NOTE: 

Do not use the clear wire on the transducer cable

for any connections; tape the end and tie it back to the
cable with electrical tape so that it does not touch any
other components or connections. 

Note: To connect the wires;
1. If the wire ends are not pre-stripped, strip them  back

about 12mm.

2. Push the spring terminals up (back).
3. Insert the wires. 
4. Release the spring terminals.

Input Connections (See Figure 5):

The input power terminals are located on the lower left
side and marked L1 and L2 (see Figure 5); there is a
ground lug for the input ground wire to the left of the
connector.  Feed the wire through the 20mm conduit hole
on the bottom left side and into the appropriate terminals.
If the wire is large enough to require a larger conduit hole,
remove the 32mm knockout and use the appropriate
conduit connections.

To determine the correct wire sizes for your installation,
see Table 2, Page 6.

NOTE:

The drive only accepts 190-265V single phase input

power. If your incoming power does not match this, have a
competent electrician alter it to 220V or 240V nominal
1Ph before connecting the drive.

Lightning/Surge Protection

Lightning arrestors or other surge suppressing devices can
be used with this product. MOV (Metal Oxide Varistor),
SOV (Silicon Oxide Varistor), or a flashover type can be
used when wired between the drive and the circuit breaker.
If a lightning arrestor is to be used between the drive and
the motor, a flashover type arrestor is recommended.

INITIAL STARTUP

PROGRAMMING

PROCEDURE

Be Sure

that the cover is installed before operating the drive.

Most installations will only require the initial startup
settings. However, the installer may need to set additional
parameters occasionally. See “Advanced Programming”,
Page 9, for information about accessing all parameters,
explanations of their functions, and procedures for
changing parameter values, if necessary.

1.

Program the Drive:

Apply power to the PENTEK 

INTELLIDRIVE. “Setup Guide” will appear.

A. Service Factor Amps (See Sidebar, “Service Factor

Amps”)

1. Use 

DIRECTIONAL Arrows

to enter the correct

service factor amps (see Table 4)

2. Press 

ENTER

to save the entry.

B. Application Type:

1. Use 

DIRECTIONAL Arrows

to scroll between

‘Above Ground’ and ‘Submersible’.

2. Press 

ENTER

to save.

C. Current Time:

1. Use 

DIRECTIONAL Arrows

to scroll to correct

time

2. Press 

ENTER

to save the time.

D. Current Date:

1. Use 

DIRECTIONAL Arrows

to scroll to 

correct date

2. Press 

ENTER

to save the date.

To change any values, press Back to return to the
previous screen. 

To change any values after startup, go to Main Menu
and edit the parameters as needed.

Connections / Operation

8

Service Factor Amps (See Table 5)

To get the best performance out of your pump, be
sure you enter the correct Service Factor Amps 
(SF Amps) in the PENTEK INTELLIDRIVE.

• Entering SF Amps 

higher than the motor rating

lets the drive supply more amps to the motor than
the motor is designed for and may allow the motor
to overheat;

Entering SF Amps 

lower than the motor rating

limits the output amps to less than the motor is
designed for and will reduce the performance of
the pump.

For any 1-Phase 3-Wire motor, the correct Service
Factor Amp rating for the PENTEK INTELLIDRIVE
is Cap Start/Cap Run amps. This may not match
the motor nameplate, which (for a 3-Wire, Single
Phase motor) will generally be Cap Start/
Induction Run Amps.

NOTE:

Global submersible motors may differ from

motors of the same horsepower from other
manufacturers.

For 3-Wire, 1-Phase motors from

all other submersible motor manufacturers, enter
the motor manufacturer’s CS/CR service factor
amps for your motor.

Part Number

Volts/Hz/Ph

HP

kW

S.F. Amps

3-Wire Single Phase Motors

G43A0010B2

220/50/1

1.0

0.75

6.4

G43A0015B2

220/50/1

1.5

1.1

9.4

G43A0020B2

220/50/1

2.0

1.5

11.6

Table 5: Global Motor Service Factor Amps

Содержание PENTEK INTELLIDRIVE PID2000-1123

Страница 1: ...INSTALLATION MANUAL PENTEK INTELLIDRIVE PID2000 1123 www onga com au 2010 PNX900 Rev 9 14 10 Installation Operation Parts For further operating installation or maintenance assistance Call 1 300 137 344 ...

Страница 2: ... Pressure Tank Serial No ______________________________________________ Dealer Installer _____________________________________________________ __________________________________________________________________ Installer Phone No ___________________________________________________ Date of Installation ___________________________________________________ Wire Lengths in Feet Metres Circuit Breaker to...

Страница 3: ... on an independent branch circuit protected by a circuit breaker see Table 2 Page 6 for circuit breaker sizing with no other appliances on the circuit Risk of burns The drive can become hot during normal operation Allow it to cool for 10 minutes after shut down before handling it to avoid burns Risk of electric shock A means for disconnection from the supply mains having a contact separation in al...

Страница 4: ... to operate 4 submersible pumps Each drive is rated for maximum output amp rating Any use of the drive outside of its intended use and design parameters will void the warranty Transducer The drive uses a 4 20mA 0 690 kPa pressure transducer to control the speed of the motor The transducer senses pressure in the pipe and converts it to an electrical signal which it sends to the drive The drive proc...

Страница 5: ...staller to pump out the well Toggles the pressure setpoint between 300 400 and 500 kPa default is 400 Views and changes parameters Shows the last 15 faults Changes the display to the previous screen With code locks and unlocks the password protected keys default password is 7777 Selects menu items and confirms numeric value changes The up and down arrows scroll through the menus and change numeric...

Страница 6: ...g area is free of electronics other than the terminals Conduit holes and knockouts are located so that the wire can be fed straight through to the connectors with minimal bending The terminals accept 1 5 to 4 0mm2 wire NOTE For convenience in wiring the input and motor terminals unplug from the box Pull them down to remove them for ease of access See Figure 4 BE SURE that when you replace them the...

Страница 7: ...ycling of the pump Table 4 Control Pressure Set Point and Tank Pre Charge Pressure Values NOTE Set the pressure tank s pre charge to 70 of the system operating pressure When using an external set point as well as an internal set point pre charge the tank to 70 of the lower set point of the two Some applications may require a different percentage when figuring the set point Transducer Connections S...

Страница 8: ...onal parameters occasionally See Advanced Programming Page 9 for information about accessing all parameters explanations of their functions and procedures for changing parameter values if necessary 1 Program the Drive Apply power to the PENTEK INTELLIDRIVE Setup Guide will appear A Service Factor Amps See Sidebar Service Factor Amps 1 Use DIRECTIONAL Arrows to enter the correct service factor amps...

Страница 9: ...information on Keypad functions see the Parameters section Changing a Parameter Value NOTE This procedure works for ANY parameter 1 Find the parameter and display the current parameter value on the screen 2 Press ENTER to enable editing of the parameter 3 Use the UP DOWN LEFT and RIGHT arrows to change the parameter values 4 Press ENTER again to save the new parameter value NOTE A shorthand way to...

Страница 10: ...gger Sets the frequency range that defines system stability When the frequency stabilizes within this range the drive starts the boost process Increasing this value allows the drive to sleep under less stable conditions The default is 3 Hz The range is 3 to 30 Hz Reset to defaults Default value is NO Change to YES to reset all Sleep parameters to their default values Password 2 parameters Password...

Страница 11: ...he event of nuisance dry run faults Fill Time The amount of time the drive will operate in line fill mode For self primers increase value to allow for priming Default is 60 seconds Range is 15 to 600 seconds Reset Window Read Only The time window allowed for resets after a Dry Run Fault This is calculated based on the values in the two parameters above Auto Reset Relay and Number of Resets 6 I O T...

Страница 12: ... V to the right of I O terminal I1 See Figures 6 and 7 Output Relay Rating The unique design of the PENTEK INTELLIDRIVE allows this output to be 24V DC or 24 240V AC Power can be supplied 24VDC from terminals V and V to the right of I O terminal I1 See Figures 8 and 9 The Output Relay is rated at 5A 30VDC or 8A 240VAC Note To connect the wires to either terminal 1 Strip the wires back about 1 2 2 ...

Страница 13: ...re correct Make sure pump and motor are correct Locked rotor Pull pump check for debris in pump Dry Run Well draws down too far pump runs dry Check water depth Under sized pump or motor Make sure pump and motor are sized correctly Leak in the pipe system Check system for leaks Intermittent transducer connection Check transducer cable for loose connections or damaged insulation Cannot reach pressur...

Страница 14: ...ake sure that all vents are clear Drive goes into TPM and limits the motor current until it is within the operating temperature Pipe Break Leak detected Check for any leaks in the pipe system Application calls for long run times Extend run time limitation Go to Main Menu Pipe Break No of Days without Sleep to verify preset value and change if needed Disable Pipe Break Fault Go to Main Menu Pipe Br...

Страница 15: ...or pulses motor to try to free it NOTE No user action is required when a Warning is displayed Table 6 AWG Wire Sizing VFD to 3 Wire 1 Phase Motor NOTE Information in this Table applies ONLY to Global Series motors For other motors refer to motor manufacturer s specifications for wire sizing VFD Global Volts Maximum Cable Length in Metres Model Motor HP Hz Ph kW Amps 1 5 mm2 2 0 mm2 2 5 mm2 3 5 mm2...

Страница 16: ...pplication improper installation or improper maintenance Without limiting the foregoing operating a three phase motor with single phase power through a phase converter will void the warranty Your only remedy and PENTAIR WATER s only duty is that PENTAIR WATER repair or replace defective products at PENTAIR WATER s choice You must pay all labor and shipping charges associated with this warranty and...

Отзывы: