During this process the valves will need to be quickly advanced
to the next cycle. To quick cycle, press
and
after the
regeneration cycle has started.
Alternating tank systems have one Logix 764 control that is
mounted on Tank 1. Tank 2 has a blank faceplate and the Tank
2 valve is controlled by the Logix 764 control on Tank 1.
Placing the Alternating System into Operation
1. Press and hold the
button for five seconds. This will
start the first regeneration.
NOTE:
Once the valve has reached the cycle (visible on
the display and camshaft has stopped turning),
quick cycle to the next cycle. This is especially
recommended for the C8 cycle. Overfilling the
regenerant tank will affect the brine and future regen
cycles.
NOTE:
It is recommended that you do not put regenerant
into the tank until after the control valve has been
put into operation. With not regenerant in the tank, it
is much easier to view water flow and motion in the
tank.
Tank 1 moves through cycles:
C5 - Fast Rinse: as the water enters the tank, air will
be forced out the drain line. Once water fills the tank,
it will then discharge out the drain line. Quick cycling
the control can now be used to advance through the
remaining cycles.
C8 - Regenerant Refill: the aircheck is filled and flow to
the regenerant tank is visible.
Quick cycle Tank 1 to service
then--
Tank 2 moves through cycles:
C1 - Backwash: as water enters the tank, air will be
forced out the drain line. Once water fills the tank, it
will then discharge out the drain line. Quick cycling
the control can now be used to advance through the
remaining cycles.
C2 - Regenerant Draw: the regenerant tank should
have water in it. As the draw occurs the level will go
down.
C3 - Slow Rinse
C4 - Standby
Both tanks have now been purged of air. The water supply
valve can be fully opened.
2. Press and hold the
button for five seconds. This will
start the second regeneration.
Quick cycle as Tank 2 moves through cycles:
C5 - Fast Rinse
C8 - Regenerant Refill: the aircheck is filled and flow to
the regenerant tank is visible.
then--
Quick cycle as Tank 1 moves through cycles:
C1 - Backwash
C2 - Regenerant Draw: the regenerant tank should
have water in it. As the draw occurs the level will go
down.
C3 - Slow Rinse
C4 - Standby
At this point Tank 1 is fully operational.
3. Press and hold the
button for five seconds. This will
start the third regeneration. After this step both tanks will
be ready.
Quick cycle as Tank 1 moves through cycles:
C5 - Fast Rinse
C8 - Regenerant Refill
Quick cycle to service
then--
Quick cycle as Tank 2 moves through cycles:
C1 - Backwash
C2 - Regenerant Draw: the regenerant tank should
have water in it. As the draw occurs the level will go
down.
C3 - Slow Rinse
C4 - Standby
Both tanks are now ready.
4. Turn on a faucet plumbed after the water conditioner. Run
the faucet until the water runs clear.
5. Add water to the regenerant tanks.
A. With a bucket or hose, add water until approximately
four gallons (15 liters) of water in each regenerant tank.
B. If the tank has a salt platform in the bottom of the tank,
add water until the water level is approximately 1"(25
mm) above the platform.
The Alternating Water Conditioning System is
Now Fully Operational
NOTE:
After any control reset (valve type or system
change, etc.), it is necessary to initiate a manual
regeneration and quick cycle through it. This will
ensure the control and cam are synchronized. If not
synchronized, Err3 will display and the control will
drive cams to the correct position for the valve and
system type programmed.
PROGRAMMING
CONTINUED
AUTOTROL
®
Logix 764 Control Performa Cv Series Valves (273, 278) Service Manual
•
15