17
P/N S794 Rev. H 8-11-14
MAX-E-THERM
®
Pool and Spa Heater Installation and User’s Guide
Section 2. Installation
Figure 10.
VENTING GUIDELINES
OUTDOOR INSTALLATION
Chec
k local b
uilding codes
for setbac
k requirements
.
Force
Air Inlet
Property Line
4'
4'
3'
SIDE VIEW
Building
From building wall
Exhaust
Grill
(Vent)
Exhaust
Grill
(Vent)
6 in.
From window or door
4'
Must be at least 3 ft. above any forced
air inlet located within a 10 ft. radius.
Vent Termination:
Must be located 6 in. away from the building
wall and the following distances away from any building
wall openings, included but not limited to vented eaves,
doors, windows, gravity air inlet:
4 ft. below,
4 ft. horizontally
Figure 11.
Must be at least 3 ft. (.9M) above any forced
air inlet located within a 10 ft. (3M) radius.
Vent Termination:
Must be located 6 in. (15.24cm) away from the building
wall and the following distances away from any building
wall openings, included but not limited to vented eaves,
doors, windows, gravity air inlet:
10 ft. (3M) below,
10 ft. (3M) horizontally
Chec
k local b
uilding codes
for setbac
k requirements
.
Force
Air Inlet
Property Line
10'
(3M)
3'
(.9M)
SIDE VIEW
Building
Exhaust
Grill
(Vent)
Exhaust
Grill
(Vent)
6 in.
(15.24cm)
OUTDOOR INSTALLATION
VENTING GUIDELINES
FOR CANADA
10'
(3M)
From building wall
From window or door
10'
(3M)