Pump
Operation

As the motors are oil filled no 
lubrication or other maintenance
is required. 

If a seal failure unit is used, no 
attention is necessary as long 
as the seal shows satisfactory
operation.

If seal failure is not used, the
pump should be lifted once every 
two years and the oil be drained
from the seal chamber to check
for water.

If the pump is used on a 
Hydr-O-Rail system, it should be
lifted once every six months and
checked for corrosion and wear.

Generally these pumps give 
very reliable service and can be
expected to operate for years 
on normal sewage pumping
without failure.

Lightning:

In some areas where considerable
lightning occurs,

it is 

recommended that a lightning
arrestor be installed at the 
control panel.

Complete data on lightning
arrestors and cost is available
from the factory. Lightning 
arrestors are good insurance
against damage to an expensive
motor.

Servicing Instructions:

IMPORTANT: Read all the 
instructions before replacing
any parts.

Starting System:

1. Turn H-O-A switch to Off 

position, then turn on main 
circuit breakers.

2. Open all discharge valves and

allow water to rise in sump.

3. Turn H-O-A switch to Hand

position on one pump and
notice operation. If pump is
noisy and vibrates, rotation is
wrong. To change rotation on
3ø motors, interchange any 
two line leads to motor. DO
NOT INTERCHANGE MAIN 
INCOMING LINES. If duplex
system, check second pump in
the same manner. 

4. Now set both H-O-A switches

to Auto position and allow
water to rise in sump until one
pump starts. Allow pump to
operate until level drops to
turn-off point.

5. Allow sump level to rise to

start other pump. Notice run
lights on panel; pumps should
alternate on each successive
cycle of operation. 

6. Turn both H-O-A switches

to OFF position and allow
sump to fill to the override 
control level.

7. Turn both switches to Auto 

position and both pumps should
start and operate together until
level drops to turn-off point.

8. Repeat this operation cycle

several times before leaving
the job.

9. Check voltage when pumps 

are operating and check the
amp draw of each pump.
Check amps on each wire 
as sometimes a high leg 
will exist. One leg can be 

somewhat higher, 5 to 10%,
without causing trouble. For
excessive amp draw on one
leg, the power company should
be consulted.

Pump
Maintenance

WARNING: Before handling
these pumps and controls,
always disconnect the power
first.

Do not smoke or use sparkable
electrical devices or flames in a
septic (gaseous) or possible 
septic sump.

Field Service on Motor:

All submersible motors can 
be serviced (out of warranty) in
the field by any reliable motor
service shop. Any pump (in 
warranty) must be returned to the
factory for service or repaired in
an authorized Hydromatic service
center. Charges will not be
allowed if (in warranty) pump is
taken to a motor repair shop that is
not an authorized Hydromatic
service center.

When field service is performed
on a pump, these instructions
should be carefully followed.

Replacing Stator:

If motor winding is burned or
shortened, it can be rewound or
replaced with new factory wound
stator. Refer to sectional drawing
of pump and motor and use the 
following steps to remove and
replace stator.

1. If stator only is damaged it

may not be necessary to 
completely dismantle pump as
stator and housing can be lifted
from pump without disturbing
seals or bearings.

2. Drain all oil from upper 

housing, remove from upper
housing, remove drain plug in
bottom of stator housing and
remove plug in top of housing
to allow air to enter.

3. After chamber is drained,

remove hold-down bolts 
and lift off. Use care in 
lifting as the seal failure 

Содержание Hydromatic S4HRC

Страница 1: ...For use with product built with USEM motor S4HRC NOTE To the installer Please make sure you provide this manual to the owner of the pumping equipment or to the responsible party who maintains the sys...

Страница 2: ...the seal failure unit indicates only that there is some water in the seal chamber The pump will continue to operate without damage but the seal should be checked immediately after failure is indicate...

Страница 3: ...ludes a maincircuit breaker for each pump a magnetic starter with overload protection for each pump an H O A switch and run light for each pump an electric alternator and a transformer to provide appr...

Страница 4: ...o the sump and cause short cycling of the pump NEMA 4 Junction Box Optional If electrical control panel is to be set remote from the pump sump a NEMA 4 junction box should be used to make power and co...

Страница 5: ...CORD See Wiring Diagram of seal failure unit 4673 or 4674 for connecting dark green and red wires If seal fail ure unit 4673 or 4674 is not used leave dark green and red wires open CONNECTION DIAGRAM...

Страница 6: ...ration 6 Turn both H O A switches to OFF position and allow sump to fill to the override control level 7 Turn both switches to Auto position and both pumps should start and operate together until leve...

Страница 7: ...r is present seals can be considered satisfactory to reuse 9 Check top bearing If clean and does not turn rough bearings can be reused and it is not necessary to completely dismantle pump to change be...

Страница 8: ...ut seal with screwdriver 8 To remove seal housing take out socket head bolts and using bolts in back of holes pry plates loose This will force out the lower seal if not already removed 9 Remove snap r...

Страница 9: ...the closed position Check in sump to be sure control is free 3 Selector switch may be in the Hand position Pump does not deliver proper capacity 1 Discharge gate valve may be partially closed or part...

Страница 10: ...ng Plate 1 15 001780041 SHCS 5 16 18 UNC x 1 4 16 000650311 Lower Ball Bearing R 1 17 009200011 Upper Mechanical Seal 1 18 19103A062 HHCS 1 2 13 UNC x 3 4 19 001500241 O Ring SC 2 20 009240101 Pipe Pl...

Страница 11: ...11 S4HRC...

Страница 12: ...isposition Any transportation charges involved in such disposition shall be for the Buyer s account The Buyer s exclusive and sole remedy on account or in respect of the furnishing of material that do...

Отзывы: