4

always be submerged during the
pumping cycle. The second 
or turn-on control is set about 
24 inches above the lower 
turn-off control. 

More distance between turn-on
and turn-off controls can be used,
but sewage may become septic
and excessive solids may collect
for the pump to handle. A 
frequent pumping cycle is 
recommended for best operation.

If an alarm system is used, this
control is usually set about 6
inches above the override control.

Some engineers as described 
previously prefer to have the
alarm control set below the 
override control.

amps on the motor housing. The
amp draw on these submersible
motors is slightly higher than 
a corresponding horsepower 
surface motor so heaters must be
sized by the nameplate rating.

Single phase pumps with 
capacitor start have a run and a
start winding each drawing a 
different current. To adequately
protect these windings with 
the appropriate heaters, consult 
the factory.

IMPORTANT: If other than
Hydromatic starters are used,
be sure the heat sensor wires are
connected in series with the
starter coil circuit. Typical
wiring diagrams are included.

Hydr-O-Rail:

If the pump or pumps are to be
used with Hydr-O-Rail system,
the pumps will be equipped with
guide brackets and hydraulic 
sealing flange.

check valve the line pressure can
be cut off. Single pump systems
are sometimes installed without a
check valve where it is desirable
to self-drain the discharge line to
prevent freezing. This can be
done only with short discharge
lines, otherwise water will return
to the sump and cause short
cycling of the pump.

NEMA 4 Junction Box
(Optional):

If electrical control panel is to be
set remote from the pump sump, a
NEMA 4 junction box should be
used to make power and control
connections. The Hydromatic
NEMA 4 junction box is provid-
ed with compression connectors
for sealing all wires. No sealing 
compound is needed to make 
connections waterproof. 

Wiring diagrams are provided
with the panel for making 
connections. An extra set of 
diagrams is included so that one
set can be used in the sump when
making connections. The size
wire to use from panel to sump
depends on motor size and 
distance in feet. 

Be sure each wire is checked out
so that a wrong connection will
not be made. 

Installing 3900 Mercury
Switch Controls:

The controls are supported by a
mounting bracket that is attached
to sump wall or cover or to the
NEMA 4 junction box.

Cord snubbers are used to hold
the cord in place. Control level
can be changed at any time 
by loosening the snubber and
readjusting cord length.

In either simplex or duplex 
system the lower or turn-off 
control is set just above the top of
volute so that the volute will

Installation
Instructions

Installing Pump in Sump:

Before installing pump in sump
lay it on side and turn impeller
manually. Impeller may be 
slightly stuck due to factory test
water so it must be broken loose
with small bar or screwdriver in
edge of vanes. The impeller
should turn freely.

Clean all trash and sticks from
sump and connect pump to piping.
A check valve must be installed
on each pump. A gate or plug
valve in each pump discharge line
is also recommended. This valve
should be installed on the 
discharge side of the check valve
so if necessary to service the

Содержание Hydromatic S4HRC

Страница 1: ...For use with product built with USEM motor S4HRC NOTE To the installer Please make sure you provide this manual to the owner of the pumping equipment or to the responsible party who maintains the sys...

Страница 2: ...the seal failure unit indicates only that there is some water in the seal chamber The pump will continue to operate without damage but the seal should be checked immediately after failure is indicate...

Страница 3: ...ludes a maincircuit breaker for each pump a magnetic starter with overload protection for each pump an H O A switch and run light for each pump an electric alternator and a transformer to provide appr...

Страница 4: ...o the sump and cause short cycling of the pump NEMA 4 Junction Box Optional If electrical control panel is to be set remote from the pump sump a NEMA 4 junction box should be used to make power and co...

Страница 5: ...CORD See Wiring Diagram of seal failure unit 4673 or 4674 for connecting dark green and red wires If seal fail ure unit 4673 or 4674 is not used leave dark green and red wires open CONNECTION DIAGRAM...

Страница 6: ...ration 6 Turn both H O A switches to OFF position and allow sump to fill to the override control level 7 Turn both switches to Auto position and both pumps should start and operate together until leve...

Страница 7: ...r is present seals can be considered satisfactory to reuse 9 Check top bearing If clean and does not turn rough bearings can be reused and it is not necessary to completely dismantle pump to change be...

Страница 8: ...ut seal with screwdriver 8 To remove seal housing take out socket head bolts and using bolts in back of holes pry plates loose This will force out the lower seal if not already removed 9 Remove snap r...

Страница 9: ...the closed position Check in sump to be sure control is free 3 Selector switch may be in the Hand position Pump does not deliver proper capacity 1 Discharge gate valve may be partially closed or part...

Страница 10: ...ng Plate 1 15 001780041 SHCS 5 16 18 UNC x 1 4 16 000650311 Lower Ball Bearing R 1 17 009200011 Upper Mechanical Seal 1 18 19103A062 HHCS 1 2 13 UNC x 3 4 19 001500241 O Ring SC 2 20 009240101 Pipe Pl...

Страница 11: ...11 S4HRC...

Страница 12: ...isposition Any transportation charges involved in such disposition shall be for the Buyer s account The Buyer s exclusive and sole remedy on account or in respect of the furnishing of material that do...

Отзывы: