12
E-03-577 (01-23-20)
3 PHASE
Notes:
1. Level Switches Must be Rated a Minimum of 2 Amps at 120 Volts
2. Torque all white field wiring terminals to 20 in. Lbs.
3. Field Wiring Must be 60˚C Copper Wire Minimum.
4. -------------- = Items Note Supplied In Control Panel.
5. Pump power, heat sensor, and seal probe cables must pass
through approved NEC 501.15 conduit seals.
1 PHASE
BLACK, WHITE, AND RED MOTOR LEADS CAN ONLY BE
CONNECTED TO PANEL TERMINAL BLOCKS AS SHOWN ON
SCHEMATIC. INCORRECT CONNECTION CAN CAUSE DAMAGE TO
PUMP AND/OR PANEL COMPONENTS THREE PHASE OVERLOAD
RELAY MUST BE CLASS 1O TRIP & AMBIENT COMPENSATED &
CONNECTED IN THE “DAISY CHAIN” CIRCUIT AS SHOWN.
Notes:
1. Level Switches Must be Rated a Minimum of 2 Amps at 120 Volts
2. Torque all white field wiring terminals to 20 in. Lbs.
3. Field Wiring Must be 60˚C Copper Wire Minimum.
4. -------------- = Items Note Supplied In Control Panel.
5. Pump power, heat sensor, and seal probe cables must pass
through approved NEC 501.15 conduit seals.
WIRING DIAGRAMS