background image

Figure 64: Edit Sensor screen

10. The Analog Output with Reset Setpoint is now set up

in UI. Press 

M

 to scroll through the remaining Setup

Start screens and continue setting up your control

system, or press 

Up

 and 

Down

 simultaneously to

return to the System 450 Main screens.

Figure 65: Analog Output Setup Start screen

Setting up time and day of week

To use the System 450 Setback feature, you must set up

the (real) time and day of the week. You can also set up

time and day of week for any control system. However,

time and day setup is not required for control systems

that do not use the setback feature. You must also set

up a weekly occupied/unoccupied schedule and select

setback values for outputs. See 

Setting up an occupied/

unoccupied schedule

 for setting up a weekly occupied/

unoccupied schedule and 

Setting up the System 450 Reset

Setpoint

 for selecting setback values.

1.

In the 

Time and Day Setup Start

 screen, press 

Next

to go to the 12 or 24 Hour Clock Selection screen. The

Time Setup Start screen is displayed when you access

the System 450 setup screens and scroll through the

Setup Start screens by pressing 

M

 repeatedly. See

the Time and Day Setup Screens row in the setup

screens flow chart in 

System 450 menu flow example

.

Note: 

All Setup Start screens are view-only;

selections cannot be made in Setup Start

screens.
The following figure shows the Time and Day

Setup Start screen with four flashing dashes.

Figure 66: Time and Day Setup Start screen

2.

In the 

12 or 24 Hour Clock Selection

 screen, press

Up

 or 

Down

 to select either the 12 hour or 24 hour

format digital clock display. Press 

Next

 to save your

selection and go to the next screen.

The following figure shows 12 hour clock format

selected.

Figure 67: 12 or 24 Hour Clock Selection screen

3.

In the 

Time of Day Setup

 screen, press 

Up

 or 

Down

to set the current time. Set the clock to real-time.

Press 

Next

 to save the time setting and go to the

next screen.

The following figure shows (real) time selected

is 11:32 A.M.

Figure 68: Time of Day Setup screen

4.

In the 

Day of Week Setup

 screen, press 

Up

 or 

Down

to select the current day of the week. Set the day to

real-time. Press 

Next

 to save the time setting and

return to the Time and Day Setup Start screen.

Note: 

1 = MON, 2 = TUE, 3 = WED, 4 = THU, 5 =

FRI, 6 = SA, and 7 = SUN.
The following figure shows day of week set to 2

(TUE, Tuesday).

Figure 69: Day of Week Setup screen

5.

The time of day and day of week are now set up in

the System 450 UI and you have returned to the

Setup Start screen. Press 

M

 to scroll through the

remaining Setup Start screens and continue setting

up your control system, or press 

Up

 and 

Down

simultaneously to return to the System 450 Main

screens.

Figure 70: Time and Day Setup Start screen

Setting up an occupied/unoccupied schedule

To use the System 450 Setback feature, you must set up a weekly occupied/unoccupied schedule. However, a weekly

occupied/unoccupied schedule is not required for control systems that do not use the setback feature. 

Relay Output and

Analog Output that reference the Reset function

 provides occupied/unoccupied schedule setup information, procedures,

and screen examples.
To use the System 450 Setback feature to provide setback control for a relay output, you must also select a Setback (SbK)

value and set up the (real) time and day of the week. See 

Setting up the System 450 Reset Setpoint

 for selecting setback

values and 

Setting up time and day of week

 for setting up time and day.

System 450 Series Reset Control Modules with Real-Time Clock and Relay Output Installation Guide

21

Содержание System 450 C450RBN-1

Страница 1: ...ith reset control and or real time setback control for temperature and humidity only control applications System 450 expansion modules allow you to control up to 10 outputs which can be relay and anal...

Страница 2: ...lies before mak ing electrical connections More than one disconnec tion or isolation may be required to completely de en ergize equipment Contact with components carrying hazardous voltage can cause e...

Страница 3: ...and input sensor terminals low voltage less than 30V Labels 5V 24V Sn 1 Sn 2 Sn 3 Note Common terminals C are internally connected 2 6 pin module connector 3 Second output relay and terminal block La...

Страница 4: ...ion Module 16 Analog Output 4 Table 1 System 450 terminal wiring information Label Terminal function Wire sizes 24V Accepts 24 VAC supply power when a C450YNN power module is not connected and provide...

Страница 5: ...nd Down for 5 seconds to access the Setup Start screens 7 Menu button Press M to move through the sensor and output setup start screens When moving through the status or setup screens press M to retur...

Страница 6: ...s of the assembly outputs which requires setting up the outputs again See Figure 4 for an explanation of the System 450 display screen and the 4 button touch pad features and functions See Table 3 for...

Страница 7: ...s that the Analog Output is set up with SP EP and OSP OEP and Relay Output 2 has 17 hours of total runtime relay ON Figure 7 System Status screens Accessing the System 450 Setup screens 1 Apply power...

Страница 8: ...screens are view only selections cannot be made in Setup Start screens 2 In the Sn 1 Sensor Type Selection screen press Up or Down to select a Sensor Type F C or Press Next to save your selection and...

Страница 9: ...Setup Start screen Setting up the System 450 Reset Setpoint The System 450 Reset Control Modules feature temperature and humidity setpoint reset capability based on a Master temperature sensor Sn 1 an...

Страница 10: ...screen The remaining figures in this procedure show the setup parameter values selected for the RSP high and low temperature shutdown unoccupied setback and load balancing that are used by the output...

Страница 11: ...en The following figure shows an Shutdown High Temperature value of 65 F selected Figure 20 Shutdown High Temperature Selection screen 7 In the Shutdown Low Temperature Selection screen press Up or Do...

Страница 12: ...e the following sections Setting up a Relay Output with Reset Setpoint Setting up an Analog Output with Reset Setpoint Setting up a Standard Relay Output A standard relay output provides On Off contro...

Страница 13: ...mains off after reaching the OFFT value Minimum Relay OFF Time range is 0 to 300 seconds Press Next to save your selection and go to the next screen The following figure shows 10 seconds selected for...

Страница 14: ...et up in Setting up the System 450 Reset Setpoint Figure 35 Relay Output Setup Start screen 2 In the Sensor Selection screen press Up or Down to select the Reset Setpoint Sensor rES for the output to...

Страница 15: ...nge is 0 to 300 seconds Press Next to save your selection and go to the next screen The following figure shows 0 seconds selected for the minimum OFF Time for Output 2 Figure 40 Minimum Relay OFF Time...

Страница 16: ...gth at End Point OEP The LCD displays different Control Ramp icons for the four control actions The following figure shows an example of the analog output setup values and the resulting output signal...

Страница 17: ...e To set up a Standard Analog Output you must select Sn 1 Sn 2 or Sn 3 in this screen and the selected sensor must already be set up in the System 450 UI See Setting up System 450 Sensors for informat...

Страница 18: ...re limits to set point excursion The following figure shows 0 selected for the Unoccupied Setback value for Output 3 Figure 51 Unoccupied Setback Selection screen 8 In the Integration Constant Selecti...

Страница 19: ...sensor is not selected the remaining output setup screens do not appear If a sensor is already selected for the output the Sensor Selection screen does not appear here the next screen in the setup se...

Страница 20: ...tput When properly set up P I control can drive the load closer to Setpoint than proportional only control Press Next to save your selection and go to the next screen Initially you should select the I...

Страница 21: ...wing figure shows 12 hour clock format selected Figure 67 12 or 24 Hour Clock Selection screen 3 In the Time of Day Setup screen press Up or Down to set the current time Set the clock to real time Pre...

Страница 22: ...e unoccupied times The load balancing feature is not effected in its function as a result of Occupied Unoccupied modes See Figure 3 1 In the Occupied Unoccupied Schedule Setup Start screen press Next...

Страница 23: ...eriods for that day and the entire day is occupied and all outputs operate at their occupied setpoint value Occupied and Unoccupied time periods are available at 15 minute intervals only For example 1...

Страница 24: ...nd menu flow example System screens Description 1 Main screens Note The Main menu screens auto scroll during normal operation After two minutes of inactivity in any screen the display returns to the m...

Страница 25: ...eed 8 Standard analog output setup start screens Mixing valve output 9 Time and day clock setup start screens Note You can set Time and day and occupied or unoccupied schedule for any control system T...

Страница 26: ...VAC AC Full load Amperes 4 9 A AC Locked Rotor Amperes 29 4 A _____________________________________ 10 Amperes AC noninductive at 24 240 VAC Pilot Duty 125 VA at 24 240 VAC Clock accuracy 4 minutes pe...

Страница 27: ...or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different fro...

Страница 28: ...2020 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice www penncontrols com...

Отзывы: