background image

Note: 

You must set up Sn-1 and Sn-2 before you

can set up a RSP for your reset control system. Sn-1

is always the Master temperature sensor; typically

an outdoor air temperature sensor. Sn-2 is always

the control loop sensor; typically a boiler or chiller

water supply loop sensor. But Sn-2 can also be a

zone temperature or humidity sensor depending on

your application, and the RSP can be a temperature

or humidity value depending on the Sn-2 Sensor

Type you select in the Sensor Setup screens.
When you select the rES sensor in an output’s

Sensor Selection screen, the output references the

RSP, and System 450 displays the remaining output

setup screens for setting up reset control based on

a calculated (floating) setpoint (RSP) or proportional

band (RSP + Pb).

Note: 

If you select Sn-1, Sn-2 or Sn-3 in the 

Sensor

Selection

 screen, the output references a standard

temperature or humidity sensor; and System 450

displays the remaining output setup screens for

setting up standard control based on the fixed

setpoint or proportional band (SP and EP) you select

for the output.
You can also select a 

Shutdown High Temperature

(SdHI)

 and/or 

Shutdown Low Temperature (SdLO)

to shut down or limit the outputs that reference the

rES sensor.
You can also enable 

Load Balancing (bAL)

 to

balance the runtimes (relay ON times) of all relay

outputs (only) that reference the rES sensor.

1.

In the 

Reset Setpoint Setup Start

 screen, press

Next

 to go to the next screen and begin setting

up the Reset Setpoint. You can set up a floating

Reset Setpoint Sensor Type (rES) that can be

referenced by the outputs in your System 450 reset

control system. You can also select high and low

temperature shutdown values (SdHI and SdLO)

and an unoccupied Setback (SbK) for all Outputs

with reset; and enable Load Balancing for relay

(only) outputs with reset. See the Reset Setpoint

Setup Screens row in the setup screens flow chart in

System 450 menu flow example

.

Note: 

Sn-1 and Sn-2 must be set up in the UI

before the 

Reset Setpoint Setup Start

 screen

is available. All Setup Start screens are view-

only; selections cannot be made in Setup Start

screens.
The following figure shows the 

Reset Setpoint

Setup Start

 screen. The remaining figures

in this procedure show the setup parameter

values selected for the RSP, high and low

temperature shutdown, unoccupied setback,

and load balancing that are used by the outputs

setup to reference the rES sensor (Output 2

and Output 4) in the control system example in

Figure 3.

Figure 15: Reset Setpoint Setup Start screen

2.

In the 

Minimum Reset Setpoint Selection

 screen,

press 

Up

 or 

Down

 to select the Minimum Reset

Setpoint value for the controlled condition (sensed

at Sn-2). The selected Minimum Reset Setpoint

(MNSP) value establishes the lowest (temperature or

humidity sensed at Sn-2) setpoint value that outputs

with reset control can reference. The MNSP value

and the Maximum Reset Setpoint (MXSP) value

establish the total (temperature or humidity) range

for the floating RSP value. See Figure 14. Press 

Next

to save your selection and go to the next screen.

The following figure shows a Minimum Reset

Setpoint value of 110 (°F).

Figure 16: Minimum Reset Setpoint Selection screen

3.

In the 

Maximum Reset Setpoint Selection

 screen,

press 

Up

 or 

Down

 to select the Maximum Reset

Setpoint value for the controlled condition (sensed

at Sn-2). The selected Maximum Reset Setpoint

(MXSP) value establishes the highest (temperature

or humidity sensed at Sn-2) setpoint that outputs

with reset control can reference. The MXSP value

and the MNSP value establish the total (temperature

or humidity) range for the floating RSP value. See

Figure 14. Press 

Next

 to save your selection and go

to the next screen.

The following figure shows a Maximum Reset

Setpoint value of 180 (°F).

Figure 17: Maximum Reset Setpoint Selection screen

4.

In the 

Reset Range Start Temperature Selection

screen, press 

Up

 or 

Down

 to select the Reset Start

Temperature value (sensed at the Master sensor

Sn-1). The Reset Start Temperature (RSTR) value

and the Reset End Temperature (RENd) value

establish the temperature range over which the RSP

is calculated. RSTR and RENd are sensed at the Sn-1

Master sensor (typically outdoor air temperature).

RSTR defines the high limit of temperature range

and corresponds with MNSP. As the outdoor air

temperature decreases below the RSTR, the RSP is

driven from the MNSP towards MXSP. See Figure

14.Press 

Next

 to save your selection and go to the

next screen.

System 450 Series Reset Control Modules with Real-Time Clock and Relay Output Installation Guide

10

Содержание System 450 C450RBN-1

Страница 1: ...ith reset control and or real time setback control for temperature and humidity only control applications System 450 expansion modules allow you to control up to 10 outputs which can be relay and anal...

Страница 2: ...lies before mak ing electrical connections More than one disconnec tion or isolation may be required to completely de en ergize equipment Contact with components carrying hazardous voltage can cause e...

Страница 3: ...and input sensor terminals low voltage less than 30V Labels 5V 24V Sn 1 Sn 2 Sn 3 Note Common terminals C are internally connected 2 6 pin module connector 3 Second output relay and terminal block La...

Страница 4: ...ion Module 16 Analog Output 4 Table 1 System 450 terminal wiring information Label Terminal function Wire sizes 24V Accepts 24 VAC supply power when a C450YNN power module is not connected and provide...

Страница 5: ...nd Down for 5 seconds to access the Setup Start screens 7 Menu button Press M to move through the sensor and output setup start screens When moving through the status or setup screens press M to retur...

Страница 6: ...s of the assembly outputs which requires setting up the outputs again See Figure 4 for an explanation of the System 450 display screen and the 4 button touch pad features and functions See Table 3 for...

Страница 7: ...s that the Analog Output is set up with SP EP and OSP OEP and Relay Output 2 has 17 hours of total runtime relay ON Figure 7 System Status screens Accessing the System 450 Setup screens 1 Apply power...

Страница 8: ...screens are view only selections cannot be made in Setup Start screens 2 In the Sn 1 Sensor Type Selection screen press Up or Down to select a Sensor Type F C or Press Next to save your selection and...

Страница 9: ...Setup Start screen Setting up the System 450 Reset Setpoint The System 450 Reset Control Modules feature temperature and humidity setpoint reset capability based on a Master temperature sensor Sn 1 an...

Страница 10: ...screen The remaining figures in this procedure show the setup parameter values selected for the RSP high and low temperature shutdown unoccupied setback and load balancing that are used by the output...

Страница 11: ...en The following figure shows an Shutdown High Temperature value of 65 F selected Figure 20 Shutdown High Temperature Selection screen 7 In the Shutdown Low Temperature Selection screen press Up or Do...

Страница 12: ...e the following sections Setting up a Relay Output with Reset Setpoint Setting up an Analog Output with Reset Setpoint Setting up a Standard Relay Output A standard relay output provides On Off contro...

Страница 13: ...mains off after reaching the OFFT value Minimum Relay OFF Time range is 0 to 300 seconds Press Next to save your selection and go to the next screen The following figure shows 10 seconds selected for...

Страница 14: ...et up in Setting up the System 450 Reset Setpoint Figure 35 Relay Output Setup Start screen 2 In the Sensor Selection screen press Up or Down to select the Reset Setpoint Sensor rES for the output to...

Страница 15: ...nge is 0 to 300 seconds Press Next to save your selection and go to the next screen The following figure shows 0 seconds selected for the minimum OFF Time for Output 2 Figure 40 Minimum Relay OFF Time...

Страница 16: ...gth at End Point OEP The LCD displays different Control Ramp icons for the four control actions The following figure shows an example of the analog output setup values and the resulting output signal...

Страница 17: ...e To set up a Standard Analog Output you must select Sn 1 Sn 2 or Sn 3 in this screen and the selected sensor must already be set up in the System 450 UI See Setting up System 450 Sensors for informat...

Страница 18: ...re limits to set point excursion The following figure shows 0 selected for the Unoccupied Setback value for Output 3 Figure 51 Unoccupied Setback Selection screen 8 In the Integration Constant Selecti...

Страница 19: ...sensor is not selected the remaining output setup screens do not appear If a sensor is already selected for the output the Sensor Selection screen does not appear here the next screen in the setup se...

Страница 20: ...tput When properly set up P I control can drive the load closer to Setpoint than proportional only control Press Next to save your selection and go to the next screen Initially you should select the I...

Страница 21: ...wing figure shows 12 hour clock format selected Figure 67 12 or 24 Hour Clock Selection screen 3 In the Time of Day Setup screen press Up or Down to set the current time Set the clock to real time Pre...

Страница 22: ...e unoccupied times The load balancing feature is not effected in its function as a result of Occupied Unoccupied modes See Figure 3 1 In the Occupied Unoccupied Schedule Setup Start screen press Next...

Страница 23: ...eriods for that day and the entire day is occupied and all outputs operate at their occupied setpoint value Occupied and Unoccupied time periods are available at 15 minute intervals only For example 1...

Страница 24: ...nd menu flow example System screens Description 1 Main screens Note The Main menu screens auto scroll during normal operation After two minutes of inactivity in any screen the display returns to the m...

Страница 25: ...eed 8 Standard analog output setup start screens Mixing valve output 9 Time and day clock setup start screens Note You can set Time and day and occupied or unoccupied schedule for any control system T...

Страница 26: ...VAC AC Full load Amperes 4 9 A AC Locked Rotor Amperes 29 4 A _____________________________________ 10 Amperes AC noninductive at 24 240 VAC Pilot Duty 125 VA at 24 240 VAC Clock accuracy 4 minutes pe...

Страница 27: ...or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different fro...

Страница 28: ...2020 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice www penncontrols com...

Отзывы: