Figure 71: Example System 450 Reset Control weekly occupied/unoccupied setback schedule

Relay Output that references an

Input Sensor

See 

System 450 menu flow example

. During the occupied

time, OUTR4 relay turns ON at 55°F (13°C) and turns OFF

at 65°F (18.5°C). During the unoccupied times with SbK =

0F° (0C°), there is no change to the On and OFF points.

Analog Output that references an

Input Sensor

An analog output can be added to a Reset control system

and controlled by Sn-1, Sn-2, or Sn-3. This analog output

can also be Setback according to the Time Clock Schedule.

For example, if SbK = -5F° (-3C°) is selected in the OUTA

setup screens, then during the unoccupied times, the SP

becomes 5F° (3C°) lower and the EP becomes 5F° (3C°)

lower.

Note: 

Setback set point temperature does not

exceed MXSP or go lower than MNSP. In reset, MNSP

and MXSP are the limits to set point excursion.

Relay Output and Analog Output

that reference the Reset function

During the occupied time, the RSP is calculated using the

Reset Applications from Figure 14. During the unoccupied

time with the SbK = -10F° (-5.5C°), the RSP is calculated

and 10F° (5.5C°) is subtracted. Using the example in this

procedure, the RSP would change from 153°F (67°C) to

143°F (61.5°C) during the unoccupied times.

The load balancing feature is not effected in its function

as a result of Occupied/Unoccupied modes.

See Figure 3.

1.

In the 

Occupied/Unoccupied Schedule Setup

Start

 screen, press 

Next

 to go to the Day 1 (SUN)

Occupied Time Selection screen. The Occupied/

Unoccupied Schedule Setup Start screen is displayed

when you access the System 450 setup screens and

scroll through the Setup Start screens by pressing 

M

repeatedly. See the Occupied/Unoccupied Schedule

Setup Screens row in the setup screens flow chart in

System 450 menu flow example

.

Note:

- To use the System 450 Setback feature,

you also must select a Setback (SbK)

value for the outputs you want to set

back and you must set up the (real) time

and day of week. See 

Setting up the

System 450 Reset Setpoint

 and 

Setting

up System 450 Outputs

 for selecting

output Setback (SbK) values. See 

Setting

up time and day of week

 for setting up

time and day of week.

- You must set up the time and day of

week before the schedule takes effect.

You can select the output setback (SbK)

values at any time.

The following figure shows the 

Occupied/

Unoccupied Schedule Setup Start

 screen

with flashing dashes. The remaining screens in

this procedure show how to set up the weekly

schedule shown in Figure 71.

Figure 72: Occupied/Unoccupied Schedule Setup Start

screen

System 450 Series Reset Control Modules with Real-Time Clock and Relay Output Installation Guide

22

Содержание System 450 C450RBN-1

Страница 1: ...ith reset control and or real time setback control for temperature and humidity only control applications System 450 expansion modules allow you to control up to 10 outputs which can be relay and anal...

Страница 2: ...lies before mak ing electrical connections More than one disconnec tion or isolation may be required to completely de en ergize equipment Contact with components carrying hazardous voltage can cause e...

Страница 3: ...and input sensor terminals low voltage less than 30V Labels 5V 24V Sn 1 Sn 2 Sn 3 Note Common terminals C are internally connected 2 6 pin module connector 3 Second output relay and terminal block La...

Страница 4: ...ion Module 16 Analog Output 4 Table 1 System 450 terminal wiring information Label Terminal function Wire sizes 24V Accepts 24 VAC supply power when a C450YNN power module is not connected and provide...

Страница 5: ...nd Down for 5 seconds to access the Setup Start screens 7 Menu button Press M to move through the sensor and output setup start screens When moving through the status or setup screens press M to retur...

Страница 6: ...s of the assembly outputs which requires setting up the outputs again See Figure 4 for an explanation of the System 450 display screen and the 4 button touch pad features and functions See Table 3 for...

Страница 7: ...s that the Analog Output is set up with SP EP and OSP OEP and Relay Output 2 has 17 hours of total runtime relay ON Figure 7 System Status screens Accessing the System 450 Setup screens 1 Apply power...

Страница 8: ...screens are view only selections cannot be made in Setup Start screens 2 In the Sn 1 Sensor Type Selection screen press Up or Down to select a Sensor Type F C or Press Next to save your selection and...

Страница 9: ...Setup Start screen Setting up the System 450 Reset Setpoint The System 450 Reset Control Modules feature temperature and humidity setpoint reset capability based on a Master temperature sensor Sn 1 an...

Страница 10: ...screen The remaining figures in this procedure show the setup parameter values selected for the RSP high and low temperature shutdown unoccupied setback and load balancing that are used by the output...

Страница 11: ...en The following figure shows an Shutdown High Temperature value of 65 F selected Figure 20 Shutdown High Temperature Selection screen 7 In the Shutdown Low Temperature Selection screen press Up or Do...

Страница 12: ...e the following sections Setting up a Relay Output with Reset Setpoint Setting up an Analog Output with Reset Setpoint Setting up a Standard Relay Output A standard relay output provides On Off contro...

Страница 13: ...mains off after reaching the OFFT value Minimum Relay OFF Time range is 0 to 300 seconds Press Next to save your selection and go to the next screen The following figure shows 10 seconds selected for...

Страница 14: ...et up in Setting up the System 450 Reset Setpoint Figure 35 Relay Output Setup Start screen 2 In the Sensor Selection screen press Up or Down to select the Reset Setpoint Sensor rES for the output to...

Страница 15: ...nge is 0 to 300 seconds Press Next to save your selection and go to the next screen The following figure shows 0 seconds selected for the minimum OFF Time for Output 2 Figure 40 Minimum Relay OFF Time...

Страница 16: ...gth at End Point OEP The LCD displays different Control Ramp icons for the four control actions The following figure shows an example of the analog output setup values and the resulting output signal...

Страница 17: ...e To set up a Standard Analog Output you must select Sn 1 Sn 2 or Sn 3 in this screen and the selected sensor must already be set up in the System 450 UI See Setting up System 450 Sensors for informat...

Страница 18: ...re limits to set point excursion The following figure shows 0 selected for the Unoccupied Setback value for Output 3 Figure 51 Unoccupied Setback Selection screen 8 In the Integration Constant Selecti...

Страница 19: ...sensor is not selected the remaining output setup screens do not appear If a sensor is already selected for the output the Sensor Selection screen does not appear here the next screen in the setup se...

Страница 20: ...tput When properly set up P I control can drive the load closer to Setpoint than proportional only control Press Next to save your selection and go to the next screen Initially you should select the I...

Страница 21: ...wing figure shows 12 hour clock format selected Figure 67 12 or 24 Hour Clock Selection screen 3 In the Time of Day Setup screen press Up or Down to set the current time Set the clock to real time Pre...

Страница 22: ...e unoccupied times The load balancing feature is not effected in its function as a result of Occupied Unoccupied modes See Figure 3 1 In the Occupied Unoccupied Schedule Setup Start screen press Next...

Страница 23: ...eriods for that day and the entire day is occupied and all outputs operate at their occupied setpoint value Occupied and Unoccupied time periods are available at 15 minute intervals only For example 1...

Страница 24: ...nd menu flow example System screens Description 1 Main screens Note The Main menu screens auto scroll during normal operation After two minutes of inactivity in any screen the display returns to the m...

Страница 25: ...eed 8 Standard analog output setup start screens Mixing valve output 9 Time and day clock setup start screens Note You can set Time and day and occupied or unoccupied schedule for any control system T...

Страница 26: ...VAC AC Full load Amperes 4 9 A AC Locked Rotor Amperes 29 4 A _____________________________________ 10 Amperes AC noninductive at 24 240 VAC Pilot Duty 125 VA at 24 240 VAC Clock accuracy 4 minutes pe...

Страница 27: ...or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different fro...

Страница 28: ...2020 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice www penncontrols com...

Отзывы: