The boiler room where the burner is installed must fulfill all rules and recommendations given by
local authorities.
Boiler room must provide constant air supply of 1500 m³ per hour (ca. 1600 cm
2
air inlet opening).
In order to mount the burner to the boiler door, it must have mounting holes. See Figure 3 .
Notice!
If the burner is installed to the boiler, the door’s or the installation flange´s thickness should be
8-14mm.
Cutting contour of hole to be cut to boilers door in order to install PV1000 burner.
Dimension
Unit
Value
⌀
D
hole for burning chamber neck
mm
400
⌀
D1
flange bolt ring diameter
mm
490
⌀
D2
bolt holes
mm
6 x 13
Bolt hole offset angle
deg
30
Angle between bolt holes
deg
60
Figure 3 Boiler door mounting opening
Figure 4 Contour of cutting