![Pego 100N MASTER Скачать руководство пользователя страница 6](http://html1.mh-extra.com/html/pego/100n-master/100n-master_use-and-maintenance-manual_1521986006.webp)
PLUS
300 EXPERT
U THR
Pag. 6
USE AND MAINTENANCE MANUAL
Rev. 01-18
IMPORTANT GENERAL INFORMATION FOR THE INSTALLER
1.
Install the device in places where the protection rating is observed and try not to
damage the box when drilling holes for wire/pipe seats;
2.
Do not use multi-polar cables in which there are wires connected to inductive/power
loads or signaling wires (e.g. probes and digital inputs);
3.
Do not fit power supply wiring and signal wiring (probes and digital inputs) in the same
raceways or ducts;
4.
Minimize the length of connector wires so that the wiring does not have a spiral shape;
5.
All wiring must be of a cross-section suitable for relevant power levels;
6
. Place a general protection fuse upstream from the electronic controller;
7.
When it is necessary to extend the probes, the wires must have a cross-section of at
least 1mm². The probes extension or shortening could alter the factory calibration; then
check and calibrate through an external thermometer.
KIT FOR MOUNTING
PLUS300 EXPERT U THR
electronic controller kit, for assembling and using, contains:
• N° 4 seals, to be fitted between the fixing screws and the box back panel.
• N° 1 use and maintenance manual.
• N° 1 electrical drawing.
• N° 1 drilling layout.
• N° 2 probes NTC 10K 1% .
CHAPTER 2: INSTALLATION
CHAP. 2 - Installation
2.1
2.2