45
BOILER CONTROL: INTERNAL WIRING & OPERATION
Parameter
Parameter Description
Unit/Option
Default Option
(122) Prog. Input 7.
Do Not Change Without Factory Approval.
Select the function for programmable input 7
# 0-5
0: Disabled
1: Flue 2 Sensor
3: Cascade Sensor
5: CH Sensor
3: Cascade Sensor
(123) Prog. Input 8.
Do Not Change Without Factory Approval.
Select the function for programmable input 8
# 0-8
0: Disabled
1: DHW Return Sensor
3: Air Pressure Switch (NO)
4: Air Pressure Switch (NC)
5: Flue Pressure Switch (NO)
6: Flue Pressure Switch (NC)
6: Flue Pressure
Switch (NC)
(124) Prog. Input RT.
Do Not Change Without Factory Approval.
Select the function for the programmable RT input
# 0-1
0: Disabled
1: Roomstat Input
1: Roomstat Input
(125) Prog. Output 1.
Do Not Change Without Factory Approval.
Select the function for programmable
output 1
0: Disabled
1: Module Pump
2: CH Pump
3: DHW Pump
4: System Pump
5: Cascade Pump
6: Alarm Relay
7: Filling Valve
8: LPG Tank
9: External Igniter
10: Air Damper
2: CH Pump
(126) Prog. Output 2.
Do Not Change Without Factory Approval.
Select the function for programmable
output 2
0: Disabled
1: Module Pump
2: CH Pump
3: DHW Pump
4: System Pump
5: Cascade Pump
6: Alarm Relay
7: Filling Valve
8: LPG Tank
9: External Igniter
10: Air Damper
6: Alarm Relay
(127) Prog. Output 3.
Do Not Change Without Factory Approval.
Select the function for programmable
output 3
0: Disabled
1: Module Pump
2: CH Pump
3: DHW Pump
4: System Pump
5: Cascade Pump
6: Alarm Relay
7: Filling Valve
8: LPG Tank
9: External Igniter
10: Air Damper
0: Disabled
Table 8.J.2.1 (cont.): Settings -> Boiler Settings -> Boiler Parameters
Содержание PureFire PFC-625
Страница 1: ...PureFire Boilers PFC 625 PFC 750 Gas Installation Operation Maintenance Manual ...
Страница 24: ...22 WATER PIPING CONTROLS Figure 4 4 Recommended Piping One Boiler with Multiple CH Zones One DHW Tank ...
Страница 25: ...23 WATER PIPING CONTROLS Figure 4 5 Recommended Piping Multiple Boilers with Multiple CH Zones One DHW Tank ...
Страница 36: ...34 ELECTRICAL CONNECTIONS INTERNAL WIRING Figure 7 4 Internal Wiring Schematic for PFC 625 PFC 750 boilers ...
Страница 58: ...56 J LIGHTING OPERATING INSTRUCTIONS Figure 9 1 Lighting Operating Instructions START UP PROCEDURE ...
Страница 76: ...74 REPAIR PARTS 2 9 8 7 2 4 2 1 3 6 6 5 2 10 5 Figure 13 3 Supply Return Piping ...
Страница 78: ...76 REPAIR PARTS 18 16 17 6 14 15 9 4 3 1 8 13 18 7 19 2 10 11 12 5 Figure 13 4 Jacket Assembly ...
Страница 82: ...80 REPAIR PARTS Figure 13 6 Condensate System 1 2 4 7 5 15 15 8 11 3 10 15 6 15 15 12 15 13 15 9 15 14 15 ...
Страница 87: ...85 SERVICE LOG SERVICE LOG Date Serviced By Description of Service Serial Number ...