taBle 2. aDvanceD conFIGUratIon (cont.)

menU

 

FeatUre

oPtIons

stD.moDel 

DeFaUlt

DescrIPtIon / comments

340

Keypad Lockout

0-3

0

Restricts access to certain features of device; Service Menu still available if enabled.

0 =   No key pad lockout (Default)

1 =   Disables Schedule and System keys

2 =   Disables Schedule, System, and Fan keys

3 =   Disables all keys

341

Enable Pin Access

0,1

0

Applies a 3 digit  access code to enter Service Menu 342

0 =  Disable,  

1 =   Enable

342

Set PIN Access 

Code

000-999

000

Choose a 3-digit code. 

350

Fan Mode 

Enable 

1-3

3

1 =    ON: Fan is turned on regardless of demand. 

2 =   Auto: Fan is turned on according to heating or cooling demand.

3 =   ON or Auto: Allows occupant to select either 1 or 2 above.

360

System Mode 

Enable

0-3

1

Allows ability to determine which system modes the occupant can select. 

0 =  OFF, Auto

1 =   OFF, Heat, Cool, Auto

2 =   OFF, Heat, Cool

3 =   Heat, Cool, Auto

380

Minimum Deadband 

Adjustment

3-10°F, 1.5-5°C

3°F 

Select a changeover deadband value to prevent short cycling between heating and cooling modes.  

The value is adjustable to meet various HVAC system requirements.

390

Pre-Occupancy 

Purge

0-3 hours

0 hours

Select to energize fan for selected number of hours (0-3) prior to all occupied events. 

395

Maximum Override 

Time Limit

0=Time until next 

event; or  

1-4 hours

3

Restricts the duration that a temporary hold can be set. The temporary hold is limited by the maximum 

amount of time as defined in this Service Menu. 

0 =   Remainder of time until the next scheduled event.

1 =   1 Hour

2 =   2 Hours

3 =   3 Hours

4 =   4 Hours

400

Cycles Per Hour 

(CPH)  

Cooling Stage 1

0-6 CPH 

3 CPH

Defines the number of cycles per hour for cooling (Stage 1). Select 0 to enable ON-OFF control for 

Stage 1 cooling.

410

Cycles Per Hour 

(CPH) 

Cooling Stage 2

0-6 CPH

3 CPH

Defines the number of cycles per hour for cooling (Stage 2). Select 0 to enable ON-OFF control for 

Stage 2 cooling.

420

Cycles Per Hour 

(CPH)  

Heating Stage 1

0-12 CPH

5 CPH

Defines the number of cycles per hour for heating (Stage 1). Select 0 to enable ON-OFF control for 

Stage 1 heating. 

430

Cycles Per Hour 

(CPH)  

Heating Stage 2

0-12 CPH

5 CPH

Defines the number of cycles per hour for heating (Stage 2). Select 0 to enable ON-OFF control for 

Stage 2 heating. 

450

Cycles Per Hour 

(CPH)   

Heating Stage 3

0-12 CPH

5 CPH

Defines the number of cycles per hour for heating. Select 0 to enable ON-OFF control for 

Heating Stage 3.

460

Heat Recovery Rate

0-18°F/Hr  

0-10°C/Hr

5°F/Hr

Defines the rate at which the device achieves the heat comfort setpoint. Select 0 to disable ramp 

recovery.

470

Cool Recovery Rate

0-18°F/Hr  

0-10°C/Hr

5°F/Hr

Defines the rate at which the device achieves the cool comfort setpoint. Select 0 to disable ramp 

recovery.

480

Minimum Off Time

1-10 minutes

4 minutes

Sets the minimum off time for both the heat and cool output.

490

Humidity Control 

Enable

(Select models only)

Selects how humidity will be controlled. When dehumidify control is enabled, the Y2 terminal becomes 

dehumidify.

0 =   Disabled

1 =   Dehumidify Control 

500

Programmable/ 

Intermittent Fan

0-2

0

0 =   Disable

1 =   Programmable Fan: Fan operates continuously in occupied periods or with demand in  

unoccupied periods. 

2 =   Intermittent Fan: Fan operates based on the on and off times set in menus 501 and 502.

Содержание Performance pro T4000 series

Страница 1: ...d heat pump applications System mode selections Off Heat Cool Auto Stages 1 Heat 1 Cool 2 Heat 1 Cool 1 Heat 2 Cool 2 Heat 2 Cool 3 Heat 2 Cool Fan control Cycling Auto or Continuous On 1 Speed Perman...

Страница 2: ...n SC Sensor Common S1 Indoor Remote Sensor S1 Indoor Remote Sensor S2 Occupancy Setback Input S2 Occupancy Setback Input System Type 1 1H 1C Conventional System Type 2 1H 1C Heat Pump TERM Function TE...

Страница 3: ...llplate Assure that the metal jumper connects RC and RH Connect power side to the RC RH and assure that the jumper remains in place two transformer system The T4000 T4500 is shipped with a jumper conn...

Страница 4: ...Ith sYstem tests System test verification is highly recommended to verify thermostat operation Follow at least one procedure in the system tests below Refer to the Service Menus see Table 2 for more t...

Страница 5: ...ostat press the lower left and lower right keys simultaneously for about five seconds Next Go Back and Done appear see Fig 14 2 Press Next until Service Menu 341 Enable Disable PIN Access appears in t...

Страница 6: ...trols heating fan 130 Changeover valve B O terminal 0 1 0 0 B O terminal controls valve in cooling 1 B O terminal controls valve in heating 140 Auxiliary Heat 0 1 0 0 Electric backup heat 1 Fossil fue...

Страница 7: ...duled event 1 1 Hour 2 2 Hours 3 3 Hours 4 4 Hours 400 Cycles Per Hour CPH Cooling Stage 1 0 6 CPH 3 CPH Defines the number of cycles per hour for cooling Stage 1 Select 0 to enable ON OFF control for...

Страница 8: ...isable 1 Enable Note Press Done key to complete process 600 System Test Main Output Cool 0 2 0 Select an option to activate the fan output for 10 minutes select 0 Done or a different Service Menu to d...

Страница 9: ...esent check wire connection between the heating equipment and the thermostat If Demand Indicator light is red Heating is occurring No action is required If Demand Indicator light is green Cooling is o...

Страница 10: ...mount peco indoor remote zone sensor sP155 017 WARNING READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO INSTALL OPERATE OR SERVICE THIS SENSOR Failure to observe safety information and comply w...

Страница 11: ...or maXImUm lenGth anD wIre sIze Distance from Unit to control recommended wire size 000 150 feet 22 gauge 151 240 feet 20 gauge 241 385 feet 18 gauge 386 610 feet 16 gauge 611 970 feet 14 gauge wIrInG...

Страница 12: ...r message If the Indoor Remote Zone Sensor is not connected properly check the following Make sure sensor is wired properly and connected to terminals S1 and SC on the thermostat wallplate see Table 1...

Страница 13: ...eratura de funcionamiento 0 a 120 F 17 a 48 C Temperatura de env o 20 a 130 F 28 a 54 C Humedad durante el funcionamiento 5 a 95 RH no condensante Dimensiones f sicas Termostato T4000 T4500 pantalla d...

Страница 14: ...Sensor com n S1 Sensor remoto interior S1 Sensor remoto interior S2 Sensor de ocupaci n S2 Sensor de ocupaci n Tipo de sistema 1 1C 1F Convencional Tipo de sistema 2 1C 1F Bomba de calor TERMINAL Func...

Страница 15: ...de que el puente permanezca en su lugar transformador doble del sistema El T4000 T4500 se env a con un puente que conecta las terminales RH y RC Si el equipo de calefacci n y de refrigeraci n no util...

Страница 16: ...el funcionamiento del termostato Siga al menos un procedimiento en las pruebas de sistema a continuaci n Consulte los Men s de Servicio vea la Tabla 2 para m s pruebas Para todas las pruebas oprima n...

Страница 17: ...lla vea la Fig 14 2 Oprima Next siguiente hasta que el Men de Servicio 341 Acceso PIN para activar o desactivar se muestre en la pantalla El valor predeterminado de 00 aparece debajo del Men de Servic...

Страница 18: ...0 1 0 0 La terminal B O controla la v lvula en la refrigeraci n 1 La terminal B O controla la v lvula en la calefacci n 140 Calor auxiliar 0 1 0 0 Calor de reserva el ctrico 1 Calor de reserva de comb...

Страница 19: ...ordatorio de tiempo hasta el pr ximo evento programado 1 1 hora 2 2 horas 3 3 horas 4 4 horas 400 Ciclos por hora CPH Etapa de refrigeraci n 1 0 6 CPH 3 CPH Define un n mero de ciclos por hora para re...

Страница 20: ...r 1 Activar Nota Oprima la tecla Done finalizar para completar el proceso 600 Salida principal de la prueba de sistema Fr o 0 2 0 Seleccione una opci n para activar la salida del ventilador por 10 min...

Страница 21: ...Indicador de Demanda aparece de color rojo Est funcionando la calefacci n No se necesita realizar ninguna acci n Si la luz del Indicador de Demanda aparece de color verde Est funcionando la refrigera...

Страница 22: ...ADVERTENCIA LEA CUIDADOSAMENTE ESTAS INSTRUCCIONES ANTES DE INTENTAR INSTALAR OPERAR O DARLE MANTENIMIENTO A ESTE SENSOR El incumplimiento de la informaci n de seguridad y de las instrucciones puede...

Страница 23: ...e 18 De 386 a 610 pies de 117 6 m a 185 9 m calibre 16 De 611 a 970 pies de 186 2 m a 295 6 m calibre 14 caBleaDo 1 Funcionamiento de los cables Tienda los cables entre la placa de pared del termostat...

Страница 24: ...na interna no est conectado de manera apropiada verifique lo siguiente Aseg rese de que los cables del sensor est n conectados de manera apropiada a las terminales S1 y SC en la placa de pared del ter...

Страница 25: ...WG ou un fil rigide Temp rature de fonctionnement 17 48 0 120 F Temp rature de transport 28 54 C 20 130 F Humidit de fonctionnement 5 95 d humidit relative sans condensation Dimensions Thermostat T400...

Страница 26: ...rieur S2 Capteur de r glage d occupation S2 Capteur de r glage d occupation Type d installation 1 Conventionnel 1H 1C Type d installation 2 Pompe chaleur 1H 1C TERM Fonction TERM Fonction C Commun C C...

Страница 27: ...al relie RC et RH Connectez le c t de l alimentation au RC RH et veillez ce que le cavalier reste en place syst me double transformateur Le T4000 T4500 est livr avec un cavalier qui relie les bornes R...

Страница 28: ...e proc dure des tests syst me ci dessous Consultez les menus de configuraton voir tableau 2 pour plus de tests Pour tous les tests cliquez sur next Suivant pour passer au test syst me suivant qui est...

Страница 29: ...min s affichent voir figure 14 2 Appuyez sur Next Suivant jusqu ce que le menu de configuration 341 Activer D sactiver l acc s par code NIP s affiche l cran La valeur par d faut 00 s affiche en dessou...

Страница 30: ...contr le le ventilateur d air chaud 130 Valve de basculement Terminal B O 0 1 0 0 La borne B O commande la valve de climatisation 1 La borne B O commande la valve de chauffage 140 Chauffage auxiliair...

Страница 31: ...4 heures 400 Cycles par heure CPH 1 re phase de climatisation 0 6 CPH 3 CPH D finit le nombre de cycles par heure pour la climatisation Phase 1 S lectionnez 0 pour activer le contr le ON OFF MARCHE AR...

Страница 32: ...e la sortie principale Climatisation 0 2 0 S lectionnez une option pour activer la sortie du ventilateur pendant 10 minutes s lectionnez 0 Done Termin ou un autre menu de configuration pour d sactiver...

Страница 33: ...nde est rouge Le chauffage ne s enclenche pas Aucune action n est requise Si le voyant t moin de demande est vert La climatisation s enclenche Aucune action n est requise Si le voyant t moin de demand...

Страница 34: ...017 AVERTISSEMENT LIRE ATTENTIVEMENT CES INSTRUCTIONS AVANT DE TENTER D INSTALLER DE FAIRE FONCTIONNER OU DE R PARER CE CAPTEUR N gliger de respecter les informations sur la s curit et les instructio...

Страница 35: ...117 m tres Calibre 18 117 185 m tres Calibre 16 186 295 m tres Calibre 14 c BlaGe 1 Faites courir les fils Faites courir les fils entre la plaque murale du thermostat et le panneau de montage du capte...

Страница 36: ...s suivants Assurez vous que le capteur est install correctement et raccord aux bornes S1 et SC sur la plaque murale du thermostat voir le tableau 1 D signations des bornes et Types de syst mes Si vous...

Отзывы: