System Type 9: 1H/2C Conventional

System Type 10: 2H/2C Heat Pump

TERM

Function

TERM

Function

C

Common

C

Common

W1

Heat

B/O

Reversing Valve

W2

AUX

G

Fan

G

Fan

A

A

E

E

Y1

Cool 1

Y1

Compressor 1

Y2

Cool 2

Y2

Compressor 2

RH

Power for Heating

RH

Power for Heating

RC

Power for Cooling

RC

Power for Cooling

System Type 11: 3H/2C Heat Pump 
TERM

Function

C

Common

B/O

Reversing Valve

AUX

Auxiliary Heat

G

Fan

A
E

Y1

Compressor 1

Y2

Compressor 2

RH

Power for Heating 

RC

Power for Cooling

Part II: attach wIres to thermostat wallPlate (cont.)

2.  Using a small fl athead screwdriver, loosen the screws on the terminal blocks that 

correspond to the system type (see Table 1 ). 

3.  Strip the insulation of each wire at a proper length (about 1/4” or 64 cm).

4.  On the wallplate, insert wires into the terminal blocks that correspond to the system 

type, then re-tighten each screw for each terminal (see Fig. 4).

note: Do not over-tighten screws or use excessive force.  

5.  Assure that no uninsulated wires are exposed: Cap off and place a wire-nut on any 

unused wires. Assure that the attached wires fi t into the cavity on the back side of the 

thermostat. 

Part III: connect Power to the thermostat

1.  Choose from the following options to power the thermostat. 

Power options

The Performance PRO T4000 Series will operate on 24VAC power and/or two AA 

batteries (both are recommended).   Choose from three methods to connect power to the 

thermostat. 

• Batteries only (AA alkaline)

• 24 VAC direct connection only

• 24 VAC with AA battery backup (highly recommended)

wiring 24 vac common

• single-transformer system: Connect the common side of the transformer to 

the “C” screw terminal of the thermostat wallplate. Assure that the metal jumper 

connects “RC” and “RH.” Connect power side to the RC/RH and assure that the 

jumper remains in place. 

• two-transformer system: The T4000/T4500 is shipped with a jumper connecting 

terminals RH and RC. If the heating and cooling equipment do not use separate 

transformers, leave this jumper in place. If separate transformers are required, 

remove this jumper. With the jumper removed, connect RC to the power side of the 

cooling transformer. Connect RH to the power side of the heating transformer; then 

connect both the heating and cooling commons together to terminal C (Common). 

Part Iv: Install BatterIes

Insert two AA batteries (included) into the back compartment of the thermostat, where 

indicated (see Fig. 5). 

Part v: set the clock, month, anD DaY

When power is fi rst applied to the thermostat, it will activate the clock display. It 

is recommended that the time and day are entered before performing advanced 

confi guration. Follow the procedure below to set the clock, month, and day (see Fig. 6). 

1.  Press ▲/ ▼ to select 12 or 24 HR mode, then press 

Next.

2.  Press ▲/ ▼to select clock hour, then press 

Next

.  

3.  Press ▲/▼to select clock minutes, then press 

Next

4.  Press ▲/ ▼ to select clock year, then press 

Next

5.  Press ▲/ ▼ to select current month, then press 

Next

note

Mo

 (month) appears.

6.  Press ▲/ ▼to select current date. note

Days

 appears. 

7.  Press 

Done

 to fi nish clock mode. 

Part vI: verIFY sYstem settInG Is tUrneD oFF

1.  Press any key to enter the Home Display.

2.  Press 

System

 to enter system settings. 

3.  Press ▲/ ▼to select “Off,” then press 

Done

4.  Press 

Fan

 key to enter fan mode. 

5.  Press ▲/ ▼to select “Auto,” then press Done. 

note: the fl ashing option is the selection. 

Figure 5. 

Insert two AA batteries  

in back of thermostat.

Figure 4. 

Insert wires into 

appropriate terminal 

blocks.

Enlarged area 

shows wire 

insertion point 

above terminal 

block

• caUtIon: Do not connect 

unused wires together.

▲ 

!

Figure 6.

Clock must 

be set before 

performing  

advanced 

confi guration. 

Содержание Performance pro T4000 series

Страница 1: ...d heat pump applications System mode selections Off Heat Cool Auto Stages 1 Heat 1 Cool 2 Heat 1 Cool 1 Heat 2 Cool 2 Heat 2 Cool 3 Heat 2 Cool Fan control Cycling Auto or Continuous On 1 Speed Perman...

Страница 2: ...n SC Sensor Common S1 Indoor Remote Sensor S1 Indoor Remote Sensor S2 Occupancy Setback Input S2 Occupancy Setback Input System Type 1 1H 1C Conventional System Type 2 1H 1C Heat Pump TERM Function TE...

Страница 3: ...llplate Assure that the metal jumper connects RC and RH Connect power side to the RC RH and assure that the jumper remains in place two transformer system The T4000 T4500 is shipped with a jumper conn...

Страница 4: ...Ith sYstem tests System test verification is highly recommended to verify thermostat operation Follow at least one procedure in the system tests below Refer to the Service Menus see Table 2 for more t...

Страница 5: ...ostat press the lower left and lower right keys simultaneously for about five seconds Next Go Back and Done appear see Fig 14 2 Press Next until Service Menu 341 Enable Disable PIN Access appears in t...

Страница 6: ...trols heating fan 130 Changeover valve B O terminal 0 1 0 0 B O terminal controls valve in cooling 1 B O terminal controls valve in heating 140 Auxiliary Heat 0 1 0 0 Electric backup heat 1 Fossil fue...

Страница 7: ...duled event 1 1 Hour 2 2 Hours 3 3 Hours 4 4 Hours 400 Cycles Per Hour CPH Cooling Stage 1 0 6 CPH 3 CPH Defines the number of cycles per hour for cooling Stage 1 Select 0 to enable ON OFF control for...

Страница 8: ...isable 1 Enable Note Press Done key to complete process 600 System Test Main Output Cool 0 2 0 Select an option to activate the fan output for 10 minutes select 0 Done or a different Service Menu to d...

Страница 9: ...esent check wire connection between the heating equipment and the thermostat If Demand Indicator light is red Heating is occurring No action is required If Demand Indicator light is green Cooling is o...

Страница 10: ...mount peco indoor remote zone sensor sP155 017 WARNING READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO INSTALL OPERATE OR SERVICE THIS SENSOR Failure to observe safety information and comply w...

Страница 11: ...or maXImUm lenGth anD wIre sIze Distance from Unit to control recommended wire size 000 150 feet 22 gauge 151 240 feet 20 gauge 241 385 feet 18 gauge 386 610 feet 16 gauge 611 970 feet 14 gauge wIrInG...

Страница 12: ...r message If the Indoor Remote Zone Sensor is not connected properly check the following Make sure sensor is wired properly and connected to terminals S1 and SC on the thermostat wallplate see Table 1...

Страница 13: ...eratura de funcionamiento 0 a 120 F 17 a 48 C Temperatura de env o 20 a 130 F 28 a 54 C Humedad durante el funcionamiento 5 a 95 RH no condensante Dimensiones f sicas Termostato T4000 T4500 pantalla d...

Страница 14: ...Sensor com n S1 Sensor remoto interior S1 Sensor remoto interior S2 Sensor de ocupaci n S2 Sensor de ocupaci n Tipo de sistema 1 1C 1F Convencional Tipo de sistema 2 1C 1F Bomba de calor TERMINAL Func...

Страница 15: ...de que el puente permanezca en su lugar transformador doble del sistema El T4000 T4500 se env a con un puente que conecta las terminales RH y RC Si el equipo de calefacci n y de refrigeraci n no util...

Страница 16: ...el funcionamiento del termostato Siga al menos un procedimiento en las pruebas de sistema a continuaci n Consulte los Men s de Servicio vea la Tabla 2 para m s pruebas Para todas las pruebas oprima n...

Страница 17: ...lla vea la Fig 14 2 Oprima Next siguiente hasta que el Men de Servicio 341 Acceso PIN para activar o desactivar se muestre en la pantalla El valor predeterminado de 00 aparece debajo del Men de Servic...

Страница 18: ...0 1 0 0 La terminal B O controla la v lvula en la refrigeraci n 1 La terminal B O controla la v lvula en la calefacci n 140 Calor auxiliar 0 1 0 0 Calor de reserva el ctrico 1 Calor de reserva de comb...

Страница 19: ...ordatorio de tiempo hasta el pr ximo evento programado 1 1 hora 2 2 horas 3 3 horas 4 4 horas 400 Ciclos por hora CPH Etapa de refrigeraci n 1 0 6 CPH 3 CPH Define un n mero de ciclos por hora para re...

Страница 20: ...r 1 Activar Nota Oprima la tecla Done finalizar para completar el proceso 600 Salida principal de la prueba de sistema Fr o 0 2 0 Seleccione una opci n para activar la salida del ventilador por 10 min...

Страница 21: ...Indicador de Demanda aparece de color rojo Est funcionando la calefacci n No se necesita realizar ninguna acci n Si la luz del Indicador de Demanda aparece de color verde Est funcionando la refrigera...

Страница 22: ...ADVERTENCIA LEA CUIDADOSAMENTE ESTAS INSTRUCCIONES ANTES DE INTENTAR INSTALAR OPERAR O DARLE MANTENIMIENTO A ESTE SENSOR El incumplimiento de la informaci n de seguridad y de las instrucciones puede...

Страница 23: ...e 18 De 386 a 610 pies de 117 6 m a 185 9 m calibre 16 De 611 a 970 pies de 186 2 m a 295 6 m calibre 14 caBleaDo 1 Funcionamiento de los cables Tienda los cables entre la placa de pared del termostat...

Страница 24: ...na interna no est conectado de manera apropiada verifique lo siguiente Aseg rese de que los cables del sensor est n conectados de manera apropiada a las terminales S1 y SC en la placa de pared del ter...

Страница 25: ...WG ou un fil rigide Temp rature de fonctionnement 17 48 0 120 F Temp rature de transport 28 54 C 20 130 F Humidit de fonctionnement 5 95 d humidit relative sans condensation Dimensions Thermostat T400...

Страница 26: ...rieur S2 Capteur de r glage d occupation S2 Capteur de r glage d occupation Type d installation 1 Conventionnel 1H 1C Type d installation 2 Pompe chaleur 1H 1C TERM Fonction TERM Fonction C Commun C C...

Страница 27: ...al relie RC et RH Connectez le c t de l alimentation au RC RH et veillez ce que le cavalier reste en place syst me double transformateur Le T4000 T4500 est livr avec un cavalier qui relie les bornes R...

Страница 28: ...e proc dure des tests syst me ci dessous Consultez les menus de configuraton voir tableau 2 pour plus de tests Pour tous les tests cliquez sur next Suivant pour passer au test syst me suivant qui est...

Страница 29: ...min s affichent voir figure 14 2 Appuyez sur Next Suivant jusqu ce que le menu de configuration 341 Activer D sactiver l acc s par code NIP s affiche l cran La valeur par d faut 00 s affiche en dessou...

Страница 30: ...contr le le ventilateur d air chaud 130 Valve de basculement Terminal B O 0 1 0 0 La borne B O commande la valve de climatisation 1 La borne B O commande la valve de chauffage 140 Chauffage auxiliair...

Страница 31: ...4 heures 400 Cycles par heure CPH 1 re phase de climatisation 0 6 CPH 3 CPH D finit le nombre de cycles par heure pour la climatisation Phase 1 S lectionnez 0 pour activer le contr le ON OFF MARCHE AR...

Страница 32: ...e la sortie principale Climatisation 0 2 0 S lectionnez une option pour activer la sortie du ventilateur pendant 10 minutes s lectionnez 0 Done Termin ou un autre menu de configuration pour d sactiver...

Страница 33: ...nde est rouge Le chauffage ne s enclenche pas Aucune action n est requise Si le voyant t moin de demande est vert La climatisation s enclenche Aucune action n est requise Si le voyant t moin de demand...

Страница 34: ...017 AVERTISSEMENT LIRE ATTENTIVEMENT CES INSTRUCTIONS AVANT DE TENTER D INSTALLER DE FAIRE FONCTIONNER OU DE R PARER CE CAPTEUR N gliger de respecter les informations sur la s curit et les instructio...

Страница 35: ...117 m tres Calibre 18 117 185 m tres Calibre 16 186 295 m tres Calibre 14 c BlaGe 1 Faites courir les fils Faites courir les fils entre la plaque murale du thermostat et le panneau de montage du capte...

Страница 36: ...s suivants Assurez vous que le capteur est install correctement et raccord aux bornes S1 et SC sur la plaque murale du thermostat voir le tableau 1 D signations des bornes et Types de syst mes Si vous...

Отзывы: