 Part vII: PerForm aDvanceD conFIGUratIon

Perform advanced confi guration before attaching the thermostat to the wallplate. 

Advanced confi guration is done by simultaneously pressing the lower left and lower right 

keys for about fi ve seconds (see Fig. 7), which gives the user access to Service Menus. 

Use Table 2 of this Installation Guide to set each desired Service Menu item. Advanced 

confi guration allows the user to confi gure the thermostat to match the system type and to 

customize several thermostat settings.

It is also recommended to review the T4000 Series Operating Manual to learn how to 

program basic settings, such as setting the temperature display mode and other useful 

functions. 

Part vIII: moUnt the t4500 onto the wallPlate

1.  Position the thermostat slightly above the mounted wallplate (see Fig. 8), then secure 

the hooks on the back side of the thermostat to the hinge pockets on the wallplate. 

note: the top back side of the thermostat should slip into the hinge pockets 

easily. Do not use excessive force. 

2.  Align the pins on the back side of the thermostat with the terminal blocks on the 

wallplate. 

3.  Gently bring down the thermostat onto the wallplate so the pins on the back of the 

thermostat fi t into the terminal blocks on the wallplate. 

4.  Attach the retaining screw to the underside of the thermostat as shown (see Fig. 9). 

Part IX: verIFY thermostat oPeratIon wIth sYstem tests

System test verifi cation is highly recommended to verify thermostat operation. Follow at 

least one procedure in the system tests below. Refer to the Service Menus (see Table 2) 

for more tests. For all tests, press next to continue to the following system test, which is 

the next available Service Menu. Press Done only if fi nished performing all system tests. 

Pressing Done exits the Service Menus and turns off all active outputs. 

sYstem test maIn oUtPUt (heat) 

1.  On the thermostat, press the lower left and lower right keys simultaneously for about 

fi ve seconds. 

Next

,

 

Go Back

, and 

Done

 appear (see Fig. 10).

2.  Press 

Next 

until Service Menu 610 appears in the display. 

(Default value “00” appears below Service Menu.) 

3.  In Service Menu 610, press ▲/ ▼to select option “01,” Heat Stage 1 (see Fig.11).

note: If 01 is selected, the thermostat will activate the associated output for 10 minutes. 

The user should observe that the fan output (with heat) turns on. The user may also 

test more stages of heat according to what is available for the system type. 

4.  Press 

Done

 to complete the system test and exit the Service Menus. After verifying 

the system test, the outputs are disabled and the fan will stop. 

Figure 8. 

Secure the hooks 

on the back side of 

the thermostat to the 

wallplate.

Retaining screw

Figure 9. 

Mount the thermostat 

onto the wallplate. 

Figure 7. 

Access Service Menus 

by pressing the lower 

right and lower left 

keys simultaneously. 

Figure 11.  

Press Done 

to complete 

testing and 

exit Service 

Menus, 

or Next to 

continue 

tests. 

Figure 10.

Service Menu 610 

allows the user to 

perform System 

Test (Heat).

Service Menu

Default value 

(appears 

automatically)

Содержание Performance pro T4000 series

Страница 1: ...d heat pump applications System mode selections Off Heat Cool Auto Stages 1 Heat 1 Cool 2 Heat 1 Cool 1 Heat 2 Cool 2 Heat 2 Cool 3 Heat 2 Cool Fan control Cycling Auto or Continuous On 1 Speed Perman...

Страница 2: ...n SC Sensor Common S1 Indoor Remote Sensor S1 Indoor Remote Sensor S2 Occupancy Setback Input S2 Occupancy Setback Input System Type 1 1H 1C Conventional System Type 2 1H 1C Heat Pump TERM Function TE...

Страница 3: ...llplate Assure that the metal jumper connects RC and RH Connect power side to the RC RH and assure that the jumper remains in place two transformer system The T4000 T4500 is shipped with a jumper conn...

Страница 4: ...Ith sYstem tests System test verification is highly recommended to verify thermostat operation Follow at least one procedure in the system tests below Refer to the Service Menus see Table 2 for more t...

Страница 5: ...ostat press the lower left and lower right keys simultaneously for about five seconds Next Go Back and Done appear see Fig 14 2 Press Next until Service Menu 341 Enable Disable PIN Access appears in t...

Страница 6: ...trols heating fan 130 Changeover valve B O terminal 0 1 0 0 B O terminal controls valve in cooling 1 B O terminal controls valve in heating 140 Auxiliary Heat 0 1 0 0 Electric backup heat 1 Fossil fue...

Страница 7: ...duled event 1 1 Hour 2 2 Hours 3 3 Hours 4 4 Hours 400 Cycles Per Hour CPH Cooling Stage 1 0 6 CPH 3 CPH Defines the number of cycles per hour for cooling Stage 1 Select 0 to enable ON OFF control for...

Страница 8: ...isable 1 Enable Note Press Done key to complete process 600 System Test Main Output Cool 0 2 0 Select an option to activate the fan output for 10 minutes select 0 Done or a different Service Menu to d...

Страница 9: ...esent check wire connection between the heating equipment and the thermostat If Demand Indicator light is red Heating is occurring No action is required If Demand Indicator light is green Cooling is o...

Страница 10: ...mount peco indoor remote zone sensor sP155 017 WARNING READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO INSTALL OPERATE OR SERVICE THIS SENSOR Failure to observe safety information and comply w...

Страница 11: ...or maXImUm lenGth anD wIre sIze Distance from Unit to control recommended wire size 000 150 feet 22 gauge 151 240 feet 20 gauge 241 385 feet 18 gauge 386 610 feet 16 gauge 611 970 feet 14 gauge wIrInG...

Страница 12: ...r message If the Indoor Remote Zone Sensor is not connected properly check the following Make sure sensor is wired properly and connected to terminals S1 and SC on the thermostat wallplate see Table 1...

Страница 13: ...eratura de funcionamiento 0 a 120 F 17 a 48 C Temperatura de env o 20 a 130 F 28 a 54 C Humedad durante el funcionamiento 5 a 95 RH no condensante Dimensiones f sicas Termostato T4000 T4500 pantalla d...

Страница 14: ...Sensor com n S1 Sensor remoto interior S1 Sensor remoto interior S2 Sensor de ocupaci n S2 Sensor de ocupaci n Tipo de sistema 1 1C 1F Convencional Tipo de sistema 2 1C 1F Bomba de calor TERMINAL Func...

Страница 15: ...de que el puente permanezca en su lugar transformador doble del sistema El T4000 T4500 se env a con un puente que conecta las terminales RH y RC Si el equipo de calefacci n y de refrigeraci n no util...

Страница 16: ...el funcionamiento del termostato Siga al menos un procedimiento en las pruebas de sistema a continuaci n Consulte los Men s de Servicio vea la Tabla 2 para m s pruebas Para todas las pruebas oprima n...

Страница 17: ...lla vea la Fig 14 2 Oprima Next siguiente hasta que el Men de Servicio 341 Acceso PIN para activar o desactivar se muestre en la pantalla El valor predeterminado de 00 aparece debajo del Men de Servic...

Страница 18: ...0 1 0 0 La terminal B O controla la v lvula en la refrigeraci n 1 La terminal B O controla la v lvula en la calefacci n 140 Calor auxiliar 0 1 0 0 Calor de reserva el ctrico 1 Calor de reserva de comb...

Страница 19: ...ordatorio de tiempo hasta el pr ximo evento programado 1 1 hora 2 2 horas 3 3 horas 4 4 horas 400 Ciclos por hora CPH Etapa de refrigeraci n 1 0 6 CPH 3 CPH Define un n mero de ciclos por hora para re...

Страница 20: ...r 1 Activar Nota Oprima la tecla Done finalizar para completar el proceso 600 Salida principal de la prueba de sistema Fr o 0 2 0 Seleccione una opci n para activar la salida del ventilador por 10 min...

Страница 21: ...Indicador de Demanda aparece de color rojo Est funcionando la calefacci n No se necesita realizar ninguna acci n Si la luz del Indicador de Demanda aparece de color verde Est funcionando la refrigera...

Страница 22: ...ADVERTENCIA LEA CUIDADOSAMENTE ESTAS INSTRUCCIONES ANTES DE INTENTAR INSTALAR OPERAR O DARLE MANTENIMIENTO A ESTE SENSOR El incumplimiento de la informaci n de seguridad y de las instrucciones puede...

Страница 23: ...e 18 De 386 a 610 pies de 117 6 m a 185 9 m calibre 16 De 611 a 970 pies de 186 2 m a 295 6 m calibre 14 caBleaDo 1 Funcionamiento de los cables Tienda los cables entre la placa de pared del termostat...

Страница 24: ...na interna no est conectado de manera apropiada verifique lo siguiente Aseg rese de que los cables del sensor est n conectados de manera apropiada a las terminales S1 y SC en la placa de pared del ter...

Страница 25: ...WG ou un fil rigide Temp rature de fonctionnement 17 48 0 120 F Temp rature de transport 28 54 C 20 130 F Humidit de fonctionnement 5 95 d humidit relative sans condensation Dimensions Thermostat T400...

Страница 26: ...rieur S2 Capteur de r glage d occupation S2 Capteur de r glage d occupation Type d installation 1 Conventionnel 1H 1C Type d installation 2 Pompe chaleur 1H 1C TERM Fonction TERM Fonction C Commun C C...

Страница 27: ...al relie RC et RH Connectez le c t de l alimentation au RC RH et veillez ce que le cavalier reste en place syst me double transformateur Le T4000 T4500 est livr avec un cavalier qui relie les bornes R...

Страница 28: ...e proc dure des tests syst me ci dessous Consultez les menus de configuraton voir tableau 2 pour plus de tests Pour tous les tests cliquez sur next Suivant pour passer au test syst me suivant qui est...

Страница 29: ...min s affichent voir figure 14 2 Appuyez sur Next Suivant jusqu ce que le menu de configuration 341 Activer D sactiver l acc s par code NIP s affiche l cran La valeur par d faut 00 s affiche en dessou...

Страница 30: ...contr le le ventilateur d air chaud 130 Valve de basculement Terminal B O 0 1 0 0 La borne B O commande la valve de climatisation 1 La borne B O commande la valve de chauffage 140 Chauffage auxiliair...

Страница 31: ...4 heures 400 Cycles par heure CPH 1 re phase de climatisation 0 6 CPH 3 CPH D finit le nombre de cycles par heure pour la climatisation Phase 1 S lectionnez 0 pour activer le contr le ON OFF MARCHE AR...

Страница 32: ...e la sortie principale Climatisation 0 2 0 S lectionnez une option pour activer la sortie du ventilateur pendant 10 minutes s lectionnez 0 Done Termin ou un autre menu de configuration pour d sactiver...

Страница 33: ...nde est rouge Le chauffage ne s enclenche pas Aucune action n est requise Si le voyant t moin de demande est vert La climatisation s enclenche Aucune action n est requise Si le voyant t moin de demand...

Страница 34: ...017 AVERTISSEMENT LIRE ATTENTIVEMENT CES INSTRUCTIONS AVANT DE TENTER D INSTALLER DE FAIRE FONCTIONNER OU DE R PARER CE CAPTEUR N gliger de respecter les informations sur la s curit et les instructio...

Страница 35: ...117 m tres Calibre 18 117 185 m tres Calibre 16 186 295 m tres Calibre 14 c BlaGe 1 Faites courir les fils Faites courir les fils entre la plaque murale du thermostat et le panneau de montage du capte...

Страница 36: ...s suivants Assurez vous que le capteur est install correctement et raccord aux bornes S1 et SC sur la plaque murale du thermostat voir le tableau 1 D signations des bornes et Types de syst mes Si vous...

Отзывы: