PerFormance Pro t4000 serIes

InstallatIon GUIDe

warnInG

• READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO INSTALL, 

OPERATE OR SERVICE THIS THERMOSTAT.

• Failure to observe safety information and comply with instructions could result in 

PERSONAL INJURY, DEATH AND/OR PROPERTY DAMAGE.

• To avoid electrical shock or damage to equipment, disconnect power before 

installing or servicing and use only wiring with insulation rated for full thermostat 

operating voltage.

• To avoid potential fi re and/or explosion do not use in potentially fl ammable or 

explosive atmospheres.

• Retain these instructions for future reference. 

• This product, when installed, will be part of an engineered system whose 

specifi cations and performance characteristics are not designed or controlled 

by PECO. Review application and national and local codes to assure that the 

installation will be functional and safe.

!

the Peco

®

 PerFormance Pro

 thermostat

Thank you for choosing a PECO

® 

Performance PRO™ thermostat. The Performance 

PRO T4000 Series is intended for use in residential and commercial environments. It 

is designed for and can support up to 2-HEAT/ 2-COOL confi gurations in conventional 

systems and 3-HEAT/ 2-COOL confi gurations in heat pump applications. The Performance 

PRO also provides the capability to meet the requirements for ASHRAE 90.1-2004 and 

California Building Code Title 24 (2008 edition). 

The Performance PRO T4000 Series is comprised of the T4000 non-programmable 

thermostat models and the T4500 programmable thermostat models. The T4000 Series 

feature a 4 square inch blue backlit display with dynamic menus, accessed using soft 

keys. All Performance PRO T4000 Series offer the following standard features: auto-

changeover, optional remote sensors, occupancy sensor, keypad lockout, a PIN access 

code, a furnace fi lter change reminder, and a heat/cool Demand Indicator. In addition, the 

T4500 programmable models offer: programmability with up to four scheduled events per 

day, temporary override, a 365-day calendar, 20 holidays, and holiday override. 

The T4000 Series can be powered off of 24 VAC or batteries or both (recommended). 

The T4000 Series can control a minimum of 5 outputs, can monitor at least two external 

sensors, and can mount onto any PECO Performance PRO Series backplate.

aPPlIcatIons anD FeatUres

The PECO Performance PRO is intended for use in conventional and heat pump 

applications. 

• System mode selections: Off-Heat-Cool-Auto

• Stages: 1 Heat/1 Cool, 2 Heat/1 Cool, 1 Heat/2 Cool; 2 Heat/ 2 Cool; 3 Heat/ /2 Cool

• Fan control: Cycling (Auto) or Continuous (On); 1 Speed 

• Permanent memory: All device settings are stored in permanent memory 

• Connections for Remote Sensors (indoor and occupancy) 

caUtIon!

• 24 vac low-voltage thermostat. Do not install on voltages higher than 30 vac. 

• Use copper wire only; insulate or cap off (with wire nuts) all unused leads.

• Use care to avoid electrostatic discharge to the thermostat.

Front Panel reFerence: t4000/t4500 controls & DIsPlaY

ProDUct sPecIFIcatIons

Temperature Control 

Range: 

 

50° to 90° F (10° to 32° C) 

Differential:   

1° F (0.5°C)

Input Power: 

24 VAC (20-30 VAC) 50/60 Hz (+/- 10%) or AA alkaline batteries 

 

 

(both recommended); 5mm terminals accept 14-24 AWG 

 

 

 

stranded or solid wire.

Operating Temperature: 0° to 120°F (-17° to 48°C)

Shipping Temperature:  -20° to 130°F (-28° to 54°C)

Operating Humidity: 

5% to 95% RH, non-condensing 

Physical Dimensions:  T4000/T4500 Thermostat: 4.3” H x 5.7” W x 1.3”D

 

 

with 2.7” x 1.5” / 4.05 square inch liquid crystal display (LCD)

Output Ratings

Voltage (50/60 Hz): 

20-30 VAC

Current:   

0.02-1.0 A per terminal; W1 (B/O), W2 (AUX), G, A, E, Y1, Y2.

 

 

Note: Collectively, total current draw must not exceed 2.5 A.

InstallatIon InstrUctIons

Select an appropriate thermostat location

Locate the thermostat about four feet (1.2m) above the fl oor on a wall in an area with good 

ventilation and an average temperature, where it will be responsive to changes in room 

temperature. 

The Performance PRO T4000 Series may be mounted on a: 

• Horizontal or vertical 2” X 4” device box 

• Horizontal 4” X 4” device box 

• Flat surface 

Do not locate the thermostat where it can be affected by: 

• Direct sunlight

• Drafts or dead areas behind doors

• Radiant heat from appliances

• Concealed pipes or chimneys

• Outside walls/ or unheated areas 

Required components (not included, unless otherwise specifi ed):

• Two new AA batteries (included)

• Screws and wall anchors (included)

• Screwdrivers: Phillips (for wallplate); small fl athead (for terminal blocks)

• Drill with 3/16” drill bit (or 7/32” for plaster)

• Wirecutter and stripper

• Level

• T4000/ T4500 Performance PRO Thermostat (included)

• PECO Performance PRO T4000 Series Operating Manual (included)

!

Digital display with backlight

Override key

Keypad Lockout, 

Battery Indicator, 

Service Indicator

System mode

System key

Temperature 

(indoor)

Current day

Up and Down 

keys 

▲/ ▼

 

Fan key

More key

Current time
Demand 

Indicator

Fan (On/Auto)
Recovery mode

Setpoint 

temperature

Figure 1. T4000/T4500 

Thermostat (Home Display)

Mounting holes

Mounting holes

Figure 2. T4000/ T4500 Thermostat back 

view (with wallplate attached) 

Wiring passage

Содержание Performance pro T4000 series

Страница 1: ...d heat pump applications System mode selections Off Heat Cool Auto Stages 1 Heat 1 Cool 2 Heat 1 Cool 1 Heat 2 Cool 2 Heat 2 Cool 3 Heat 2 Cool Fan control Cycling Auto or Continuous On 1 Speed Perman...

Страница 2: ...n SC Sensor Common S1 Indoor Remote Sensor S1 Indoor Remote Sensor S2 Occupancy Setback Input S2 Occupancy Setback Input System Type 1 1H 1C Conventional System Type 2 1H 1C Heat Pump TERM Function TE...

Страница 3: ...llplate Assure that the metal jumper connects RC and RH Connect power side to the RC RH and assure that the jumper remains in place two transformer system The T4000 T4500 is shipped with a jumper conn...

Страница 4: ...Ith sYstem tests System test verification is highly recommended to verify thermostat operation Follow at least one procedure in the system tests below Refer to the Service Menus see Table 2 for more t...

Страница 5: ...ostat press the lower left and lower right keys simultaneously for about five seconds Next Go Back and Done appear see Fig 14 2 Press Next until Service Menu 341 Enable Disable PIN Access appears in t...

Страница 6: ...trols heating fan 130 Changeover valve B O terminal 0 1 0 0 B O terminal controls valve in cooling 1 B O terminal controls valve in heating 140 Auxiliary Heat 0 1 0 0 Electric backup heat 1 Fossil fue...

Страница 7: ...duled event 1 1 Hour 2 2 Hours 3 3 Hours 4 4 Hours 400 Cycles Per Hour CPH Cooling Stage 1 0 6 CPH 3 CPH Defines the number of cycles per hour for cooling Stage 1 Select 0 to enable ON OFF control for...

Страница 8: ...isable 1 Enable Note Press Done key to complete process 600 System Test Main Output Cool 0 2 0 Select an option to activate the fan output for 10 minutes select 0 Done or a different Service Menu to d...

Страница 9: ...esent check wire connection between the heating equipment and the thermostat If Demand Indicator light is red Heating is occurring No action is required If Demand Indicator light is green Cooling is o...

Страница 10: ...mount peco indoor remote zone sensor sP155 017 WARNING READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO INSTALL OPERATE OR SERVICE THIS SENSOR Failure to observe safety information and comply w...

Страница 11: ...or maXImUm lenGth anD wIre sIze Distance from Unit to control recommended wire size 000 150 feet 22 gauge 151 240 feet 20 gauge 241 385 feet 18 gauge 386 610 feet 16 gauge 611 970 feet 14 gauge wIrInG...

Страница 12: ...r message If the Indoor Remote Zone Sensor is not connected properly check the following Make sure sensor is wired properly and connected to terminals S1 and SC on the thermostat wallplate see Table 1...

Страница 13: ...eratura de funcionamiento 0 a 120 F 17 a 48 C Temperatura de env o 20 a 130 F 28 a 54 C Humedad durante el funcionamiento 5 a 95 RH no condensante Dimensiones f sicas Termostato T4000 T4500 pantalla d...

Страница 14: ...Sensor com n S1 Sensor remoto interior S1 Sensor remoto interior S2 Sensor de ocupaci n S2 Sensor de ocupaci n Tipo de sistema 1 1C 1F Convencional Tipo de sistema 2 1C 1F Bomba de calor TERMINAL Func...

Страница 15: ...de que el puente permanezca en su lugar transformador doble del sistema El T4000 T4500 se env a con un puente que conecta las terminales RH y RC Si el equipo de calefacci n y de refrigeraci n no util...

Страница 16: ...el funcionamiento del termostato Siga al menos un procedimiento en las pruebas de sistema a continuaci n Consulte los Men s de Servicio vea la Tabla 2 para m s pruebas Para todas las pruebas oprima n...

Страница 17: ...lla vea la Fig 14 2 Oprima Next siguiente hasta que el Men de Servicio 341 Acceso PIN para activar o desactivar se muestre en la pantalla El valor predeterminado de 00 aparece debajo del Men de Servic...

Страница 18: ...0 1 0 0 La terminal B O controla la v lvula en la refrigeraci n 1 La terminal B O controla la v lvula en la calefacci n 140 Calor auxiliar 0 1 0 0 Calor de reserva el ctrico 1 Calor de reserva de comb...

Страница 19: ...ordatorio de tiempo hasta el pr ximo evento programado 1 1 hora 2 2 horas 3 3 horas 4 4 horas 400 Ciclos por hora CPH Etapa de refrigeraci n 1 0 6 CPH 3 CPH Define un n mero de ciclos por hora para re...

Страница 20: ...r 1 Activar Nota Oprima la tecla Done finalizar para completar el proceso 600 Salida principal de la prueba de sistema Fr o 0 2 0 Seleccione una opci n para activar la salida del ventilador por 10 min...

Страница 21: ...Indicador de Demanda aparece de color rojo Est funcionando la calefacci n No se necesita realizar ninguna acci n Si la luz del Indicador de Demanda aparece de color verde Est funcionando la refrigera...

Страница 22: ...ADVERTENCIA LEA CUIDADOSAMENTE ESTAS INSTRUCCIONES ANTES DE INTENTAR INSTALAR OPERAR O DARLE MANTENIMIENTO A ESTE SENSOR El incumplimiento de la informaci n de seguridad y de las instrucciones puede...

Страница 23: ...e 18 De 386 a 610 pies de 117 6 m a 185 9 m calibre 16 De 611 a 970 pies de 186 2 m a 295 6 m calibre 14 caBleaDo 1 Funcionamiento de los cables Tienda los cables entre la placa de pared del termostat...

Страница 24: ...na interna no est conectado de manera apropiada verifique lo siguiente Aseg rese de que los cables del sensor est n conectados de manera apropiada a las terminales S1 y SC en la placa de pared del ter...

Страница 25: ...WG ou un fil rigide Temp rature de fonctionnement 17 48 0 120 F Temp rature de transport 28 54 C 20 130 F Humidit de fonctionnement 5 95 d humidit relative sans condensation Dimensions Thermostat T400...

Страница 26: ...rieur S2 Capteur de r glage d occupation S2 Capteur de r glage d occupation Type d installation 1 Conventionnel 1H 1C Type d installation 2 Pompe chaleur 1H 1C TERM Fonction TERM Fonction C Commun C C...

Страница 27: ...al relie RC et RH Connectez le c t de l alimentation au RC RH et veillez ce que le cavalier reste en place syst me double transformateur Le T4000 T4500 est livr avec un cavalier qui relie les bornes R...

Страница 28: ...e proc dure des tests syst me ci dessous Consultez les menus de configuraton voir tableau 2 pour plus de tests Pour tous les tests cliquez sur next Suivant pour passer au test syst me suivant qui est...

Страница 29: ...min s affichent voir figure 14 2 Appuyez sur Next Suivant jusqu ce que le menu de configuration 341 Activer D sactiver l acc s par code NIP s affiche l cran La valeur par d faut 00 s affiche en dessou...

Страница 30: ...contr le le ventilateur d air chaud 130 Valve de basculement Terminal B O 0 1 0 0 La borne B O commande la valve de climatisation 1 La borne B O commande la valve de chauffage 140 Chauffage auxiliair...

Страница 31: ...4 heures 400 Cycles par heure CPH 1 re phase de climatisation 0 6 CPH 3 CPH D finit le nombre de cycles par heure pour la climatisation Phase 1 S lectionnez 0 pour activer le contr le ON OFF MARCHE AR...

Страница 32: ...e la sortie principale Climatisation 0 2 0 S lectionnez une option pour activer la sortie du ventilateur pendant 10 minutes s lectionnez 0 Done Termin ou un autre menu de configuration pour d sactiver...

Страница 33: ...nde est rouge Le chauffage ne s enclenche pas Aucune action n est requise Si le voyant t moin de demande est vert La climatisation s enclenche Aucune action n est requise Si le voyant t moin de demand...

Страница 34: ...017 AVERTISSEMENT LIRE ATTENTIVEMENT CES INSTRUCTIONS AVANT DE TENTER D INSTALLER DE FAIRE FONCTIONNER OU DE R PARER CE CAPTEUR N gliger de respecter les informations sur la s curit et les instructio...

Страница 35: ...117 m tres Calibre 18 117 185 m tres Calibre 16 186 295 m tres Calibre 14 c BlaGe 1 Faites courir les fils Faites courir les fils entre la plaque murale du thermostat et le panneau de montage du capte...

Страница 36: ...s suivants Assurez vous que le capteur est install correctement et raccord aux bornes S1 et SC sur la plaque murale du thermostat voir le tableau 1 D signations des bornes et Types de syst mes Si vous...

Отзывы: