DRAFT
MTSE
IO&M Manual
36
Paragon Controls Inc,
Rev J 2/3/2021
Multi State
Input-4
Sub System Status
No
No
• Description
R
UNSIGNED
1 = Normal
2 = Low Alarm
3 = High Alarm
CharacterString
Value-1
System 1 Tag
No
No
• Description
R
STRING
CharacterString
Value-2
System 2 Tag
No
No
• Description
R
STRING
CharacterString
Value-3
System 3 Tag
No
No
• Description
R
STRING
CharacterString
Value-4
Sub System Tag
No
No
• Description
R
STRING
Analog Input-21
System 1 Sensor 1 Flow
No
No
• Description
• Eng Units
R
REAL
Analog Input-22
System 1 Sensor 1
Pressure
No
No
• Description
• Eng Units
R
REAL
Multi State
Input-11
System 1 Sensor 1 Status
No
No
• Description
R
UNSIGNED
1 = Normal
2 = Caution
3 = Failure
/..
../
Analog Input-39
Sub System Sensor 10
Flow
No
No
• Description
• Eng Units
R
REAL
Analog Input-40
Sub System Sensor 10
Pressure
No
No
• Description
• Eng Units
R
REAL
Multi State
Input-20
Sub System Sensor 10
Status
No
No
• Description
R
UNSIGNED
1 = Normal
2 = Caution
3 = Failure
Note:
Sensors # assignment is as follows:
The Analog Input and Multi State Input objects numbers are assigned based on the System # and the Sensor # within that
system. Order of Systems is as follows: System 1, System 2, System 3, Sub System, ΔP. Sub System follows the last System
in use.
Analog Input-xx
System x Sensor xx Flow
Analog Input-xx
System x Sensor xx Pressure
Multi State Input-xx
System x Sensor xx Status
TABLE 3 – MSV4 Sub System Engineering Units State_Text List
1: Inch W.C.
2: Pa
3: KPa
4: mm W.C.
5: % (Pressure %)
``
Multi State
Value-9, 10, 11
1. Standard Flow
Units
2. Actual Flow
Units
3. Standard Velocity
Units
4, Actual
Velocity Units
5. Pressure
Units
Engineering
Units
SCFM
ACFM
SFPM
AFPM
In. W.C.
SCFH
L/S
Sm/s
Am/s
Pa
SL/S
Am
3/
S
%
%
kPa
Sm
3
/S
Am
3/
M
mm W.C.
Sm
3
/M
Am
3/
HR
%
Sm
3
/HR
%
%