IO&M Manual 

 

 

 

 

Paragon Controls Inc,

 Rev J 2/3/2021 

3.  MTSE CONFIGURATIONS 

The MTSE can be configured to measure airflow in up to 3 unique Systems and monitor up to 4 
additional differential pressure (ΔP) points up to a total of 9 sensing points. 

3.1. 

Display Overview 

Shown below is a fully loaded MTSE monitoring (3) independent systems and (4) ΔPs. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Figure 3.1 – Normal Active Display showing 3 Systems and 4 ΔP measurement points. 

 
1)

 

System Number:  Static text indicating the specific system number. 

2)

 

System Tagging:  Custom entered tagging information for a more meaningful representation of 
where measurement is taking place. 

3)

 

System Measurement:  Live measurement of flow, velocity, or pressure for the System. 

4)

 

System Bar Graph:  0 to 100% graphical representation of System Measurement.  100% represents 
Operating Range (Max). 

5)

 

Units:  Field selectable units for the System Measurement. 

6)

 

Max Operating Range:  Upper limit of allowed flow measurement value.  System Bar graph and 
System Analog Output are scaled to this value (Max = 10V or 20mA). 

7)

 

Temperature:  System Temperature reading from Input source. 

8)

 

ΔP1 Tag:  Customer field entered tagging information for individual, non-System measured 
differential pressures. 

9)

 

ΔP Pressure Measurement:  Live measurement of individual, non-System measured pressures. 

10)

 

ΔP Alarm Value:  Field adjustable alarm setpoint value for ΔP Pressure Measurement.  Can be high 
or low triggered setpoint. 

11)

 

Setup Menus 

12)

 

Diagnostics Menus 

13)

 

K-Factor Menu Shortcut 

14)

 

Notification:  Alarms and Warning Notifications 

15)

 

(?) Troubleshooting and Support Pages  

 

 

Содержание MTSE

Страница 1: ...Multi Trans Smart Ecosystem MTSE Installation Operation Maintenance Manual...

Страница 2: ...1 3 3 2 Keypad 11 4 MENU INFORMATION 12 4 1 Levels of Menus 12 4 2 Setup Menus 13 4 2 1 Operating Range Menu 15 4 2 2 K Factor 16 4 2 3 Analog I O Configuration 17 4 2 4 System Filters 17 4 2 5 Networ...

Страница 3: ...TP Modbus RTU Slave Protection Circuit Polarity Protected Self Resetting Fuse Max communication length 4000 ft EIA 485 Power Consumption 8 5W 15 3VA Max Operating Temperature 20 F to 158 F 29 C to 70...

Страница 4: ...ION The MTSE is rated for either indoor or outdoor installation When installed outdoors do not install the MTSE where the display screen is in direct sunlight Avoid locations that are subject to high...

Страница 5: ...NOT CONNECT TO THESE PINS J4 Network Communication BACnet Modbus communication pins J5 Digital Inputs and Digital Outputs Not Used J6 Future Sensor Module Expansion Will provide power for additional M...

Страница 6: ...When connecting multiple MTSE units on a common communication network connect shielding wires together and connect only one side of the shielding wire to earth ground at the building automation system...

Страница 7: ...MTSE IO M Manual 5 Paragon Controls Inc Rev J 2 3 2021 Figure 2 4 Typical 3 System connection to 24VAC DC power 4 20mA loop powered temperature transmitters analog receiving devices or network communi...

Страница 8: ...MTSE IO M Manual 6 Paragon Controls Inc Rev J 2 3 2021 Figure 2 5 Typical 3 System connection to 24VAC DC power 0 10V three wire temperature transmitters analog receiving devices or network communica...

Страница 9: ...TSE for each sensing point a high or Total and a low or Static connection Transducers in the MTSE are numbered sequentially therefore all connections for System 1 must be made in order starting at Sen...

Страница 10: ...ty or pressure for the System 4 System Bar Graph 0 to 100 graphical representation of System Measurement 100 represents Operating Range Max 5 Units Field selectable units for the System Measurement 6...

Страница 11: ...addition to the 3 Systems there are also two other sensor measurement types with their own unique properties which are described below Sub System Commonly used as 2nd OA Many air handling unit manufac...

Страница 12: ...hange the appearance of the Normal Active Display Shown below are images of a single system and a two system configuration with no P points of measurement If P points of measurement were ordered they...

Страница 13: ...the settings These values will be entered through a popup keypad like the one shown below 1 Parameter Information Indicates what parameter is currently being entered 2 Max Maximum allowable value to...

Страница 14: ...re data for each individual sensor System Overview View system and parameter configuration information Factory Defaults Reset MTSE to Factory Default Settings Caution resetting will remove parameters...

Страница 15: ...only entered for one or two systems at the Factory All Setup Menu pages will write each System s parameters to internal memory and also be backed up on the microSD card Some settings are not System sp...

Страница 16: ...n Fixed Variable or Network for each system If Fixed temp enter Temp in last column If Variable enter min and max Temp representing min and max analog input for scaling Toggle select between Altitude...

Страница 17: ...ould be selected if the MTSE is connected to a flow station or flow sensors with known cross sectional area Piezometer should be selected if connected to a fan s piezometer ring that has a manufacture...

Страница 18: ...pplied fan coefficient and therefore the MTSE removes standard density for airflow calculations This is not to be confused with correction to standard flow or velocity that selection is made in Units...

Страница 19: ...5V 0 10V and 4 20mA Default will be 0 10V for Analog Outputs and 4 20mA for Analog Inputs The Analog IO page is shown below 4 2 4 System Filters The System Filters menu allows the user to independent...

Страница 20: ...e the number of samples and or interval time to make the response time faster 4 2 5 Network Communications Modbus and BACnet communications are selectable in this menu page Shown below is the Network...

Страница 21: ...range from a value of 1 002 to 4 194 302 The default is 1002 Displayed only if BACnet is selected Modbus ID The Modbus ID menu allows the user to enter the unique device address when connect to a Modb...

Страница 22: ...from two different atmospheric pressure standards Altitude or Barometric Actual air density will be calculated accordingly dependent upon the selection Toggling between the Altitude Selection of Alti...

Страница 23: ...an alarm value and the user does not want unnecessary alarm faults from a fluctuating flow value Values accepted are from 0 to 999 seconds and default is 30 seconds Lockdown Lockdown is useful in appl...

Страница 24: ...lockdown value cannot be reduced when the system flows fluctuate momentarily below the lockdown value the system will still show flow until this delay time is exceeded The Lockdown Delay will be glob...

Страница 25: ...Figures Allows user to change number of digits shown to the right of the decimal point When a new engineering unit is selected the Decimal Point will be automatically updated according to the table b...

Страница 26: ...a KPa mm W C and Changing the engineering units will not convert the Alarm Setpoint value the user must enter the Alarm Setpoint value in the correct engineering units 4 3 Diagnostics Menu The diagnos...

Страница 27: ...failure or a problem with the pneumatics i e closed fan backdraft damper kinked or blocked signal tubing etc 5 Verification of either flow or no flow if air handling unit is off can be confirmed for i...

Страница 28: ...calibration outside 20 of factory calibrated zero 4 3 2 System Overview The system overview pages display many of the parameters configured on the device and can be used to quickly diagnose and troub...

Страница 29: ...to update software and you have received a new uSD card ensure the POWER SWITCH is in the OFF position replace the uSD card in the MTSE to update the software the uSD card slot is located just below...

Страница 30: ...the longevity of the touchscreen the touchscreen will automatically dim after 90 minutes Select this button to toggle on and off the ScreenSaver 4 3 6 AutoZero Settings AutoZero if included at the Fac...

Страница 31: ...ication that one or more alarm conditions are present as shown in the image below The alarm notifications are displayed on the Normal Active Display per the following sequence listed below 1 Notificat...

Страница 32: ...t respective system exceeds the high flow alarm value set in the setup menu Section 4 2 7 Alarms then a High Flow Alarm will occur Low Flow Alarm If any system alarm is enabled and the flow for that r...

Страница 33: ...value exceeds the entered Operating Range value for any system a Flow Exceeds Operating Range alarm will occur Firmware Update During the bootup sequence of the MTSE the host MCU will check its firmw...

Страница 34: ...DRAFT MTSE IO M Manual 32 Paragon Controls Inc Rev J 2 3 2021 ATTACHMENT A BACnet PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT...

Страница 35: ...1 for details Analog Input Analog Output Analog Value Binary Input Binary Output Binary Value Multistate Input Multistate Value CharacterString Value Data Link Layer Options MS TP master Clause 9 bau...

Страница 36: ...Analog Value 1 System 1 Operating Range No No Description Eng Units R W REAL Min 0 Max Varies Analog Value 2 System 2 Operating Range No No Description Eng Units R W REAL Min 0 Max Varies Analog Valu...

Страница 37: ...2 Note Unit Selection Dependent on Multi State Value 9 Multi State Value 4 Temperature Engineering Units No No Description R W UNSIGNED 1 F 2 C Multi State Value 5 System 1 Temperature Source No No D...

Страница 38: ...AL Analog Input 40 Sub System Sensor 10 Pressure No No Description Eng Units R REAL Multi State Input 20 Sub System Sensor 10 Status No No Description R UNSIGNED 1 Normal 2 Caution 3 Failure Note Sens...

Страница 39: ...DRAFT MTSE IO M Manual 37 Paragon Controls Inc Rev J 2 3 2021 ATTACHMENT B MODBUS SOFTWARE CONFIGURATION PARAMETERS...

Страница 40: ...Decimal 40000 40999 Holding Register address 16 bit Data type Byte order Motorola Default High Byte bits 15 8 Low Byte bits 7 0 32 bit Data type Byte order Mid Little Endian CD AB Float Data type Byt...

Страница 41: ...99 99 0 R 40441 4 Pressure Units in W C Sensor 4 Pressure 0 99 99 0 R 40443 4 Pressure Units in W C Sensor 5 Pressure 0 99 99 0 R 40445 4 Pressure Units in W C Sensor 6 Pressure 0 99 99 0 R 40447 4 Pr...

Страница 42: ...lay 0 999 0 W 40150 2 System 1 Tagging 0 12 0 W 40197 6 Note 4 System 2 Tagging 0 12 0 W 40203 6 Note 4 System 3 Tagging 0 12 0 W 40209 6 Note 4 SubSystem Tagging 0 12 0 W 40215 6 Note 4 System 1 Temp...

Страница 43: ...Paragon Controls Incorporated http www paragoncontrols com Phone 707 579 1424...

Отзывы: