DRAFT
MTSE
IO&M Manual
34
Paragon Controls Inc,
Rev J 2/3/2021
Objec
t
Objec
t
Name
(ma
x 32 Cha
r)
Create
Objec
t
Servi
ce
Dele
te Object
Servi
ce
Optiona
l
Propertie
s
Suppo
rted
Writea
ble
Propertie
s
Property
Data
Typ
e
Data
Valu
e
Desc
ription
(State
Text)
DEVICE
No
No
• Object Name
• Description
• Location
• Object Identifier
• APDU Timeout
• Max Info Frames
• Max Master
•
Descri
ption
•
Locati
on
Analog Input-1
System 1 Total Flow
No
No
• Description
• Eng Units
R
REAL
Analog Input-2
System 2 Total Flow
No
No
• Description
• Eng Units
R
REAL
Analog Input-3
System 3 Total Flow
No
No
• Description
• Eng Units
R
REAL
Analog Input-4
Sub System Flow
No
No
• Description
• Eng Units
R
REAL
Analog Input-5
System 1 Temperature
No
No
• Description
• Eng Units
R/W
REAL
Min = -99
Max = 9,999
*Note: Only Write Access when Multi State Value-6 is set to Network
Analog Input-6
System 2 Temperature
No
No
• Description
• Eng Units
R/W
REAL
Min = -99
Max = 9,999
*Note: Only Write Access when Multi State Value-7 is set to Network
Analog Input-7
System 3 Temperature
No
No
• Description
• Eng Units
R/W
REAL
Min = -99
Max = 9,999
*Note: Only Write Access when Multi State Value-8 is set to Network
Analog
Input-8
Sub System Temperature
No
No
• Description
• Eng Units
R/W
REAL
Min = -99
Max = 9,999
Analog Value-1
System 1 Operating
Range
No
No
• Description
• Eng Units
R/W
REAL
Min = 0
Max = Varies
Analog Value-2
System 2 Operating
Range
No
No
• Description
• Eng Units
R/W
REAL
Min = 0
Max = Varies
Analog Value-3
System 3 Operating
Range
No
No
• Description
• Eng Units
R/W
REAL
Min = 0
Max = Varies
Analog Value-4
Sub System Operating
Range
No
No
• Description
• Eng Units
R/W
REAL
Min = 0
Max = Varies
Analog Value-5
System 1 High Alarm
Value
No
No
• Description
• Eng Units
R/W
REAL
Min = 0
Max = Varies
Analog Value-6
System 2 High Alarm
Value
No
No
• Description
• Eng Units
R/W
REAL
Min = 0
Max = Varies
Analog Value-7
System 3 High Alarm
Value
No
No
• Description
• Eng Units
R/W
REAL
Min = 0
Max = Varies
Analog Value-8
Sub System High Alarm
Value
No
No
• Description
• Eng Units
R/W
REAL
Min = 0
Max = Varies
Analog Value-9
System 1 Low Alarm
Value
No
No
• Description
• Eng Units
R/W
REAL
Min = 0
Max = Varies
Analog Value-
10
System 2 Low Alarm
Value
No
No
• Description
• Eng Units
R/W
REAL
Min = 0
Max = Varies
Analog Value-
11
System 3 Low Alarm
Value
No
No
• Description
• Eng Units
R/W
REAL
Min = 0
Max = Varies
Analog Value-
12
Sub System Low Alarm
Value
No
No
• Description
• Eng Units
R/W
REAL
Min = 0
Max = Varies
Analog Value-
13
Controller 1 Output
No
No
• Description
• Eng Units
R/W
REAL
Min = 0
Max = 100
Analog Value-
14
Controller 2 Output
No
No
• Description
• Eng Units
R/W
REAL
Min = 0
Max = 100
Analog Value-
15
Controller 3 Output
No
No
• Description
• Eng Units
R/W
REAL
Min = 0
Max = 100