PCI MTSE Скачать руководство пользователя страница 3

 

 

          

DRAFT

 MTSE 

IO&M Manual 

 

 

 

 

Paragon Controls Inc,

 Rev J 2/3/2021 

1.  INTRODUCTION 

1.1. 

Description 

The Multi-Trans Smart Ecosystem (MTSE) is a flow and pressure transmitter which can simultaneously 
provide airflow measurement of up to three flow systems (e.g., supply, return, and outside air) and four 
differential pressure points (e.g., total fan static, duct static, pre and final filters) in any combination for 
a total of 9 sensing points.  The MTSE can connect to and receive a differential pressure signal from 
each fan’s piezometer-ring airflow sensors or field installed airflow stations.  This signal is scaled and 
linearized before being displayed locally and transmitted out as a 4-20mA or 0-10VDC signal, as well as 
on Modbus or BACnet network communication.  A true AutoZero feature corrects potential zero offset 
caused by large ambient temperature changes for outside air applications.  A temperature compensation 
feature compensates the flow signal for density changes caused by variations in the air temperature.   
 

1.2. 

Specifications 

Power Requirements 

20 - 28VAC/VDC 

Supported Protocols 

BACnet MS/TP  

 

Modbus RTU Slave 

Protection 

 Circuit Polarity Protected 

 

 Self-Resetting Fuse 

Max communication length 

4000 ft. (EIA-485) 

Power Consumption 

8.5W, 15.3VA Max 

 

Operating Temperature 

-20°F to 158°F 

 

 (-29°C to 70°C) 

Digital Outputs 

(2) Open Collector Digital 

 

Outputs 

Temperature Compensated Range  -4°F to 158°F 
 

 (-20°C to70°C) 

Digital Inputs 

(2) Dry Contact Digital Inputs 

Storage Temperature 

-40°F to 257°F  

 

 (-40°C to 125°C) 

Analog Outputs 

(4) 16-bit Analog Outputs 

 

Field Selectable 0-10V & 4-20mA 

 

Overvoltage and Overcurrent Protected 

Enclosure 

 Impact Resistant Polycarbonate

 

 IP-66, NEMA 4X Rated 

 

 Fire Retardant UL 94 V-0 

Analog Inputs 

 (4) 12-bit Analog Inputs 

 

Field Selectable 0-5V, 0-10V & 4-20mA 

Dimensions 

9.50" L x 5.69" W x 3.56" H 

Terminal Blocks 

Pluggable Screw Type 

 

16 to 24 AWG 

Pressure Connections 

1/4" OD Barbed

 

Brass Fittings 

Accuracy 

+/- 0.25% F.S. 

 

 

1.3. 

Safety 

1.3.1.  Electrical Connections 

Before any electrical connections are made, ensure the 

POWER SWITCH

 is in the 

OFF

 position. 

1.3.2.  Static Electricity 

The circuit board contains components which are susceptible to damage caused by static electrical 
discharge.  Should it be necessary to remove the circuit board from the enclosure, appropriate 
precautions must first be taken to ensure that the operator and the circuit board are at the same electrical 
potential. 

Содержание MTSE

Страница 1: ...Multi Trans Smart Ecosystem MTSE Installation Operation Maintenance Manual...

Страница 2: ...1 3 3 2 Keypad 11 4 MENU INFORMATION 12 4 1 Levels of Menus 12 4 2 Setup Menus 13 4 2 1 Operating Range Menu 15 4 2 2 K Factor 16 4 2 3 Analog I O Configuration 17 4 2 4 System Filters 17 4 2 5 Networ...

Страница 3: ...TP Modbus RTU Slave Protection Circuit Polarity Protected Self Resetting Fuse Max communication length 4000 ft EIA 485 Power Consumption 8 5W 15 3VA Max Operating Temperature 20 F to 158 F 29 C to 70...

Страница 4: ...ION The MTSE is rated for either indoor or outdoor installation When installed outdoors do not install the MTSE where the display screen is in direct sunlight Avoid locations that are subject to high...

Страница 5: ...NOT CONNECT TO THESE PINS J4 Network Communication BACnet Modbus communication pins J5 Digital Inputs and Digital Outputs Not Used J6 Future Sensor Module Expansion Will provide power for additional M...

Страница 6: ...When connecting multiple MTSE units on a common communication network connect shielding wires together and connect only one side of the shielding wire to earth ground at the building automation system...

Страница 7: ...MTSE IO M Manual 5 Paragon Controls Inc Rev J 2 3 2021 Figure 2 4 Typical 3 System connection to 24VAC DC power 4 20mA loop powered temperature transmitters analog receiving devices or network communi...

Страница 8: ...MTSE IO M Manual 6 Paragon Controls Inc Rev J 2 3 2021 Figure 2 5 Typical 3 System connection to 24VAC DC power 0 10V three wire temperature transmitters analog receiving devices or network communica...

Страница 9: ...TSE for each sensing point a high or Total and a low or Static connection Transducers in the MTSE are numbered sequentially therefore all connections for System 1 must be made in order starting at Sen...

Страница 10: ...ty or pressure for the System 4 System Bar Graph 0 to 100 graphical representation of System Measurement 100 represents Operating Range Max 5 Units Field selectable units for the System Measurement 6...

Страница 11: ...addition to the 3 Systems there are also two other sensor measurement types with their own unique properties which are described below Sub System Commonly used as 2nd OA Many air handling unit manufac...

Страница 12: ...hange the appearance of the Normal Active Display Shown below are images of a single system and a two system configuration with no P points of measurement If P points of measurement were ordered they...

Страница 13: ...the settings These values will be entered through a popup keypad like the one shown below 1 Parameter Information Indicates what parameter is currently being entered 2 Max Maximum allowable value to...

Страница 14: ...re data for each individual sensor System Overview View system and parameter configuration information Factory Defaults Reset MTSE to Factory Default Settings Caution resetting will remove parameters...

Страница 15: ...only entered for one or two systems at the Factory All Setup Menu pages will write each System s parameters to internal memory and also be backed up on the microSD card Some settings are not System sp...

Страница 16: ...n Fixed Variable or Network for each system If Fixed temp enter Temp in last column If Variable enter min and max Temp representing min and max analog input for scaling Toggle select between Altitude...

Страница 17: ...ould be selected if the MTSE is connected to a flow station or flow sensors with known cross sectional area Piezometer should be selected if connected to a fan s piezometer ring that has a manufacture...

Страница 18: ...pplied fan coefficient and therefore the MTSE removes standard density for airflow calculations This is not to be confused with correction to standard flow or velocity that selection is made in Units...

Страница 19: ...5V 0 10V and 4 20mA Default will be 0 10V for Analog Outputs and 4 20mA for Analog Inputs The Analog IO page is shown below 4 2 4 System Filters The System Filters menu allows the user to independent...

Страница 20: ...e the number of samples and or interval time to make the response time faster 4 2 5 Network Communications Modbus and BACnet communications are selectable in this menu page Shown below is the Network...

Страница 21: ...range from a value of 1 002 to 4 194 302 The default is 1002 Displayed only if BACnet is selected Modbus ID The Modbus ID menu allows the user to enter the unique device address when connect to a Modb...

Страница 22: ...from two different atmospheric pressure standards Altitude or Barometric Actual air density will be calculated accordingly dependent upon the selection Toggling between the Altitude Selection of Alti...

Страница 23: ...an alarm value and the user does not want unnecessary alarm faults from a fluctuating flow value Values accepted are from 0 to 999 seconds and default is 30 seconds Lockdown Lockdown is useful in appl...

Страница 24: ...lockdown value cannot be reduced when the system flows fluctuate momentarily below the lockdown value the system will still show flow until this delay time is exceeded The Lockdown Delay will be glob...

Страница 25: ...Figures Allows user to change number of digits shown to the right of the decimal point When a new engineering unit is selected the Decimal Point will be automatically updated according to the table b...

Страница 26: ...a KPa mm W C and Changing the engineering units will not convert the Alarm Setpoint value the user must enter the Alarm Setpoint value in the correct engineering units 4 3 Diagnostics Menu The diagnos...

Страница 27: ...failure or a problem with the pneumatics i e closed fan backdraft damper kinked or blocked signal tubing etc 5 Verification of either flow or no flow if air handling unit is off can be confirmed for i...

Страница 28: ...calibration outside 20 of factory calibrated zero 4 3 2 System Overview The system overview pages display many of the parameters configured on the device and can be used to quickly diagnose and troub...

Страница 29: ...to update software and you have received a new uSD card ensure the POWER SWITCH is in the OFF position replace the uSD card in the MTSE to update the software the uSD card slot is located just below...

Страница 30: ...the longevity of the touchscreen the touchscreen will automatically dim after 90 minutes Select this button to toggle on and off the ScreenSaver 4 3 6 AutoZero Settings AutoZero if included at the Fac...

Страница 31: ...ication that one or more alarm conditions are present as shown in the image below The alarm notifications are displayed on the Normal Active Display per the following sequence listed below 1 Notificat...

Страница 32: ...t respective system exceeds the high flow alarm value set in the setup menu Section 4 2 7 Alarms then a High Flow Alarm will occur Low Flow Alarm If any system alarm is enabled and the flow for that r...

Страница 33: ...value exceeds the entered Operating Range value for any system a Flow Exceeds Operating Range alarm will occur Firmware Update During the bootup sequence of the MTSE the host MCU will check its firmw...

Страница 34: ...DRAFT MTSE IO M Manual 32 Paragon Controls Inc Rev J 2 3 2021 ATTACHMENT A BACnet PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT...

Страница 35: ...1 for details Analog Input Analog Output Analog Value Binary Input Binary Output Binary Value Multistate Input Multistate Value CharacterString Value Data Link Layer Options MS TP master Clause 9 bau...

Страница 36: ...Analog Value 1 System 1 Operating Range No No Description Eng Units R W REAL Min 0 Max Varies Analog Value 2 System 2 Operating Range No No Description Eng Units R W REAL Min 0 Max Varies Analog Valu...

Страница 37: ...2 Note Unit Selection Dependent on Multi State Value 9 Multi State Value 4 Temperature Engineering Units No No Description R W UNSIGNED 1 F 2 C Multi State Value 5 System 1 Temperature Source No No D...

Страница 38: ...AL Analog Input 40 Sub System Sensor 10 Pressure No No Description Eng Units R REAL Multi State Input 20 Sub System Sensor 10 Status No No Description R UNSIGNED 1 Normal 2 Caution 3 Failure Note Sens...

Страница 39: ...DRAFT MTSE IO M Manual 37 Paragon Controls Inc Rev J 2 3 2021 ATTACHMENT B MODBUS SOFTWARE CONFIGURATION PARAMETERS...

Страница 40: ...Decimal 40000 40999 Holding Register address 16 bit Data type Byte order Motorola Default High Byte bits 15 8 Low Byte bits 7 0 32 bit Data type Byte order Mid Little Endian CD AB Float Data type Byt...

Страница 41: ...99 99 0 R 40441 4 Pressure Units in W C Sensor 4 Pressure 0 99 99 0 R 40443 4 Pressure Units in W C Sensor 5 Pressure 0 99 99 0 R 40445 4 Pressure Units in W C Sensor 6 Pressure 0 99 99 0 R 40447 4 Pr...

Страница 42: ...lay 0 999 0 W 40150 2 System 1 Tagging 0 12 0 W 40197 6 Note 4 System 2 Tagging 0 12 0 W 40203 6 Note 4 System 3 Tagging 0 12 0 W 40209 6 Note 4 SubSystem Tagging 0 12 0 W 40215 6 Note 4 System 1 Temp...

Страница 43: ...Paragon Controls Incorporated http www paragoncontrols com Phone 707 579 1424...

Отзывы: