Step 1.

Carry out all works in line with HSE requirements using MS/RA for each installation.

Step 2.

Remove tap-off  from packaging and ensure no damage is visible to the device. 

Step 3.

Off er the tap off  box up to the housing and visually line up the earth/ground strip and 

the interlock channel on the iMPB casing. Insert the ground strip as shown. Pull back the 

mechanical interlock and rotate the box into position, then release the mechanical interlock 

when parallel with the busbar. Ensure the box is fully supported during this procedure. Verify 

that the ground strip has rotated within the interlcok channel and the machanical interlock 

Tap off  Enclosure

Busbar

Ensure earth/ground strip and 
interlock channel are correctly aligned

has released. Verify the Tap Off  box is in place. Note the box cannot be inserted in the 

wrong polarity as the design of the ground strip, interlock and housing prevent this. 

Step 4.

The cutout for the contacts on the claw and the contact guard line up when the tap 

off  is fi tted to the busbar. To engage the contacts the engager handle is rotated 90 

degrees. 

Step 5. (optional)

If the Tap off  boxes have meteringethrenet ports on the front of the boxes need 

populated with RJ45 connections and cables which run up the side of the busbar 

and daisy chain from box to box.  For more detailed assistance please contact the 

Powerbar engineering team.  

Rotary handle

www.powerbarsystems.com

Spring loaded interlock 

    Tap Off  Modules 

The Powerbar iMPB range of tap-off  modules comprise an arrangement of enclosure, circuit breaker, monitoring device, on load isolator and safety interlocks which provide a unique 

set of safety features for installation

 and allow the tap-off modules to be installed or removed while the busbar is energized.

 

The proprietary spring loaded mechanical interlock ensures that the tap-off  box can only be inserted on to the iMPB busbar system with the on-load isolator in the off  position.

 

The proprietary spring loaded mechanical interlock is a defi nitive locating mechanism that ensures the tap-off  module is correctly located and fi xed to the busbar frame. 

 

The proprietary spring loaded mechanical interlock ensures that the tap-off  is fully grounded/earthed to the iMPB case prior to any phase contact operation. 

 

The proprietary spring loaded mechanical interlock ensures that the tap-off  conductors can be inserted onto the iMPB bar whilst ensuring no conductors are exposed to the installer. 

 

The busbar housing, earth strip and mechanical housing ensure that the tap-off  cannot be inserted the wrong way with reverse polarity. 

 

The rotary handle of the on-load isolator has a further positive engagement tab which must be operated to allow the rotary handle to be operated. 

The 

tap-off  box is fully grounded/earthed before any phase connections are made and the earth/ground remains intact after any phase connections are broken in the event of Tap-

off  box isolation/withdrawal. This safety features ensures electrical safety throughout the operation.  

Engagement Tab

Earth/Ground Strip 

Interlock Channel 

Note: The Sprung Engagment Tab on the 

rotary handle is fully pushed in before 

rotating the handle 90 degrees to engage or 

disengage the tap off  box.

Содержание iMPB

Страница 1: ...iMPB Installation Manual...

Страница 2: ...must be safely secured to the lifting apparatus before lifting Always check that the load does not exceed the safe working load of the lifting apparatus Ensure that equipment is used as per manufactur...

Страница 3: ...ts Care is to be taken not to damage ends of the busbar during installation Powerbar recommends the hanging brackets be mounted no more than 1 5 metres 5 apart Ensure that each section of busbar has a...

Страница 4: ...ar orientation and site conditions may restrict installers from adhering to this methodology In these cases installers must be cautious and ensure the joint pack is installed correctly Ensure all part...

Страница 5: ...ally the first component to be mounted on a run The entire route should initially be inspected for any obstructions before installation The box should be installed at the correct height in accordance...

Страница 6: ...omprise an arrangement of enclosure circuit breaker monitoring device on load isolator and safety interlocks which provide a unique set of safety features for installation and allow the tap off module...

Страница 7: ...ll connected load to the Busbar Trunking via tap offs for example should be isolated prior to energizing the bar The Main Supply switch to the Busbar is to be energized first The Protection Settings s...

Страница 8: ...66536 E I Engineering Corporation USA Manufacturing Location 400 Supreme Industrial Drive Anderson South Carolina 29621 Tel 1 864 375 1757 E I Engineering LTD European Manufacturing Location Ballydero...

Отзывы: