Propylene Glycol Flow
The table below summarizes the flow for the P-K STORM appliances with different Propylene Glycol
mixtures:
Model
ST-1250
ST-1500
ST-1750
ST-2000
Mixture
Flow
Pressure Flow
Pressure Flow
Pressure Flow
Pressure
0%
121 GPM 18.8 ft
146 GPM 23 ft
170 GPM 20 ft
194 GPM 26 ft
10%
123 GPM 19.4 ft
148 GPM 23.6 ft
172 GPM 20.5 ft
197 GPM 26.8 ft
20%
124 GPM 19.7 ft
149 GPM 24.0 ft
174 GPM 21.0 ft
198 GPM 27.1 ft
30%
126 GPM 20.4 ft
152 GPM 25.0 ft
177 GPM 21.7 ft
202 GPM 28.2 ft
40%
131 GPM 22.0 ft
158 GPM 27.0 ft
184 GPM 23.4 ft
210 GPM 30.5 ft
50%
137 GPM 24.1 ft
165 GPM 29.4 ft
192 GPM 25.5 ft
219 GPM 33.1 ft
60%
144 GPM 26.6 ft
173 GPM 32.3 ft
202 GPM 28.2 ft
230 GPM 36.5 ft