P-K SOLIS™
Gas Fired Boiler
Technical Service 1.877.728.5351
Revised: March 15, 2021
Released: March 15, 2021
Patterson-Kelley 2021
All Rights Reserved.
2701000090 P-K SOLIS NURO Installation and
Owners Manual (Rev A).docx
Page 45
Condensate Drain
The condensate is acidic (pH between 3.0 and 5.0) and may be corrosive to some building drain systems.
A condensate neutralization system may be required and is available from Patterson-Kelley. If
the
condensate drainage system is exposed to freezing temperatures, it must be field heat traced. The boiler
could generate up to one gallon of condensate per 100,000 BTU input. As an example, an SL-3000 boiler
at full fire can produce 30 gallons per hour of condensate
. Disposal of condensate must comply with all
state and local codes.
Piping with Refrigeration Systems
When installed in a two-pipe system that provides both chilled and hot water, the control system should
be configured so as to limit the time rate of change of temperature at the boiler. Consult your
authorized Patterson-Kelley boiler representative for application guidance.
Piping with air handling units
The boiler piping system of a hot water heating boiler connected to heating coils located in air handling
units, where they may be exposed to refrigerated air circulation, must be equipped with flow control
valves or other automatic means to prevent gravity circulation of the boiler water during the cooling
cycle.
3.8 Water Quality
The P-K SOLIS™ boiler’s heat exchanger is made of stainless steel. The heat exchanger requires
proper water conditions to remain efficient and function properly. Information of proper water treatment
can be found on our website
www.pattersonkelley.com
type in search: “water quality”. For information,
please refer to Patterson-Kelley Multi-Metal Systems Water Quality Standards as it appears in
Appendix C – Water Quality Standards Quality Standards for Hydronic Boilers in Multi-Metal
Systems
as this applies to the warranty of your heat exchanger. Under no circumstances should
Soften Water be used in boiler.
If the piping system attached to this unit will be chemically cleaned, the boiler must be disconnected
from the system and a bypass installed so that the chemical cleaning solution does not circulate
through the boiler. Following chemical cleaning, the system should be thoroughly rinsed to remove
cleaning agents prior to reconnecting the boiler to the system.
NOTICE!
The chemical manufacturer for use must certify glycol or other treatment chemicals
added to the system in multi-metal systems that include a stainless steel; heat exchanger.
Under no circumstances should petroleum based cleaning or sealing compounds be used in the
boiler system.
Under no circumstances should the hydronic system be flushed while the appliance is attached to
the system since the debris or corrosion products may accumulate in the appliance and obstruct the
appliance’s heat exchanger.