MACH® Series
Gas-Fired Boiler
Installation
Page 26
Analyzer probe in boiler exhaust
Table 3-1 Combustion Reading For Setting Gas Safety Shut Off / Control Valves
Nominal
High Fire Setting
Low Fire Setting
Fuel
Gas Pressure
% O
2
%
CO
2
%
O
2
%
CO
2
Natural Gas
7" W.C
4.8 + 0.2
9.2 + 0.1
5.0 + 0.2
9.1 + 0.1
C1500/C2000 Adjusting Low and High
High fire adjustment
Low fire adjustment
Содержание MACH C1500
Страница 2: ...MACH Series Gas Fired Boiler Table of Contents...
Страница 49: ...MACH Series Gas Fired Boiler Limited Warranty Page 45...
Страница 50: ...MACH Series Gas Fired Boiler Appendix Page 46...
Страница 51: ...MACH Series Gas Fired Boiler Appendix Page 47 8 0 APPENDIX Date Hi Low Fire O2 CO CO2 Stack Temp pH Action By...