LA6 Signal Tower Complete Operation Manual

1.3.  About this Product

This product is designed to display and announce information with LED lighting and alarm* functions for the operation state 
of major applications, such as equipment status, to indicate elapsed time, factory automation applications, waiting in line at 
institutions, such as stores and banks, etc.
This product can be controlled with signal inputs to drive the Alarm and signal towers like a standard Signal Tower in the “Signal 
Tower Mode”, but also has a new function, the “Smart Mode.”  In the “Smart Mode”, the customer can use the binary input to 
create a diverse display of light flashing controls, like a level meter, dimming or chase-light controls, etc., with the setup of 
programmed data.
* Only for Flashing/Alarm Type

Please

• 

 

Connect an external fuse between the power supply circuit and the internal circuit to protect the Main Unit. 

•   Do not use in an environment exposed to strong radio waves or inductance noise. Failure to comply will result in 

malfunction due to the influence of noise. 

•   Do not use in an environment where corrosive gas is present.  Possible cause of failure may occur. 

•   Discharge any static electricity from the body before handling static sensitive parts, such as the Micro-USB Cable.  To prevent 

damage from static electricity, touch hands or other body parts to metals or an earth ground to discharge the body from 

static charge. 

•   Do not lose parts, such as the Head Cover, when removing while working with the product. 

•   When this product is used for security purposes, it should be inspected daily and it is recommended this product should be 

used together with other security products in case a malfunction should occur. 

•   Do not remove parts, other than ones indicated as removable on the product. 

•   Do not modify or change the product in any way. 

•   The specific parts written in this book should be used for replacement at any cost. 

•   By following the attachment and the handling method written in this book, this product can be used to comply for a Type1 

Enclosure.  (For UL Standard Compliance) 

•   Use a “Class 2” power source which complies with UL1310.  (For UL Standard Compliance) 

[ B  Flashing/Alarm Type

]

•   The alarm sound is unidirectional, therefore it is most easily audible in the direction from the source. Position the signal 

tower so that the alarm sound is facing in the desired sound direction. 

•   Sound pressure may decrease if the alarm is used in an environment which has water, steam, etc., nearby. 

[ D  DC24V Type

]

•   Use a “class 2” power supply specified in the guidelines under UL1310.  (UL Standardized conditions)

Note

•   This complete operation manual should be stored in a safe location and it is recommended to be periodically read before 

maintenance is performed. 

Содержание LA6 series

Страница 1: ...B95100496_01 Signal Tower Complete Operation Manual Type LA6...

Страница 2: ...5 5 1 3 Connecting to a PLC PNP DC 24V Type 16 5 1 4 Connecting to Relay Contacts AC 100 240V Type 17 5 1 5 Connecting to a PLC NPN AC 100 240V Type 17 5 2 Current Capacity 18 5 2 1 Contact Capacity D...

Страница 3: ...and wiring ensure the power is disconnected and the Main Unit is turned off Failure to comply may result in electric shock Be sure the wiring is correct If an error is made in wiring the internal circ...

Страница 4: ...To prevent damage from static electricity touch hands or other body parts to metals or an earth ground to discharge the body from static charge Do not lose parts such as the Head Cover when removing...

Страница 5: ...ry default setting R Red Y Amber G Green B Blue C White The LED light color for each tier can be changed after purchase or Tiers Off white Silver B N WJ LJ Direct mount with cable connection Mounting...

Страница 6: ...is indicated according to its model number Refer to the model numbers as a reference to its appearance WJ LJ TN A B N B N B N B N B N B N WJ LJ TN D Lens Tiers 5 Lens Tiers 3 Rated Voltage Number of L...

Страница 7: ...40 70 Overall Height 320 254 280 214 16 10 8 5 1Maximum Board thickness 4 mm 2 Spec Underside View 1 3 4 6 7 9 10 2 5 60 1 40 70 16 20 8 5 1 3 4 6 8 9 2 5 14 Direct mount with cable connection Direct...

Страница 8: ...Parts Micro USB connector Micro B Female Note To open the USB Cover insert a minus driver blade edge width of 3 mm thickness of 0 5 mm or less in the indented part and lightly pry it open Use an obje...

Страница 9: ...9 LA6 Signal Tower Complete Operation Manual 3 3 Attachment Angle Part Names and Dimensions Unit mm 32 5 4 5 31 81 66 Top View Side View Rear View 60 20 81 2 11 L Bracket 22 5 5...

Страница 10: ...emicals outside water thinner benzine gasoline oil etc product damage may occur Do not disassemble this product beyond it s usable parts refer to 3 2 Part Names and Outer Appearance on page 7 Failure...

Страница 11: ...mark holes with a punch etc 3 Making holes for wiring and installation Use a drill etc to make holes for installation and wiring Punch etc Installation Template WJ TN Note Figure is for or installati...

Страница 12: ...30 N m Standard Recommended Torque Threaded hole for cable gland attachment Effective Screw Length for M16x1 5 is 12 mm in length B N Notes Do not pull the lead wire connected to the Terminal Block br...

Страница 13: ...c shock or short circuiting For TN Direct Mount Terminal Buss Wire the product so that the lead wire does not protrude from the terminal Failure to comply may result in electric shock or short circuit...

Страница 14: ...Blue 5 White 6 Gray 7 Black 8 Yellow 9 Gray 10 Black 11 Purple LED1 Input1 LED2 Input2 LED3 Input3 LED4 Input4 LED5 Input5 Alarm 1 Input6 Alarm 2 Input7 Power Wire Flashing Pulse Enable Common Power...

Страница 15: ...N With flashing alarm Output Unit 2 For Flashing Pulse Enable Output Unit 1 For Lighting Red Orange Green Blue White Brown Purple Pink Skyblue Yellow Gray LA6 24V DC Class 2 No polarity LED Tier 1 Inp...

Страница 16: ...ogramming 24V DC Class2 LA6 LED Tier 1 Input 1 LED Tier 2 Input 2 LED Tier 3 Input 3 LED Tier 4 Input 4 LED Tier 5 Input 5 Power Supply Wire Flashing Pulse Enable Common line Alarm 1 Input 6 Mode Chan...

Страница 17: ...Wire Lighting Common line Alarm 2 Input 7 With Flashing Alarm L N 5 1 5 Connecting to a PLC NPN AC 100 240V Type 5 1 4 Connecting to Relay Contacts AC 100 240V Type External Contact For Flashing Puls...

Страница 18: ...eakage Current 0 1mA or less ON Voltage Vsat 1V or less Table 2 Power Supply Inrush Current Inrush Current at 25o C 16A 2ms Inrush Current at 50o C 50A 2ms Table 3 Power Consumption LA6 5AWJWB 7 5W Ta...

Страница 19: ...ange in the OFF condition the Multi function button can be used for the recombination of colors changing the amount of alarm sounds and other product functionalities 6 1 Signal Tower mode The Signal T...

Страница 20: ...that can be used in groups The Time trigger mode operates in accordance with time and the pattern transition timing operates during this group operation In addition the maximum memory of 15 groups can...

Страница 21: ...ng Select all LEDs to turn on or flash Flashing rates are selectable from 30 times per min ute 60 times per minute or 120 times per minute Alarm Tone Alarm Silence or one tone can be selected from 11...

Страница 22: ...combination of ON OFF to inputs 1 4 performs a call This setup can be made in the EDITOR for LA series software application Visit our homepage at http www patlite com to download the software applica...

Страница 23: ...tion Pulse trigger mode Operation Example The following are examples of the Pulse trigger mode operation In addition to trigger input and pattern changes the figure shows the operation of the Mute inp...

Страница 24: ...software application and other features for the LA6 Setup Parameters This mode has parameters that can be set up as shown in the following table Setup Range Setting Index Description Every Group LED...

Страница 25: ...9 ON ON 25 ON ON ON 10 ON ON 26 ON ON ON 11 ON ON ON 27 ON ON ON ON 12 ON ON 28 ON ON ON 13 ON ON ON 29 ON ON ON ON 14 ON ON ON 30 ON ON ON ON 15 ON ON ON ON 31 ON ON ON ON ON 16 ON An empty cell ind...

Страница 26: ...anged The following figure shows the timing when pushing the Multi function Button to perform these operations As a caution no signal inputs are received during each setup 6 3 1 Alarm Sound Control Th...

Страница 27: ...s into the status selected 6 3 2 1 LED Color Change The LED color which operates in the Signal Tower mode can be changed First the LED color change starts from the1st tier where the red LED turns on A...

Страница 28: ...ers will flash in accordance to the current firmware version indicated from top to bottom The following table indicates the meaning for each flashing LED color and the corresponding number LED Color C...

Страница 29: ...becomes faster while holding the Multiple function Button down until the White LED is in its full flashing state The first flashing lasts about 15 seconds before the flash rate increases and by contin...

Страница 30: ...n table at the end of the group table indicates the LED color indicated according to the color number in the group tables Group No STOP Operation Repeat Setup Pattern No LED Color Tier Flashing Setup...

Страница 31: ...3 4 5 ON 0 1 16 5 6 7 8 9 ON 0 1 17 9 10 11 12 13 ON 0 1 18 13 14 15 16 17 ON 0 1 19 17 18 19 20 21 ON 0 1 12 The pattern is displayed when an input occurs NO 1 22 22 22 22 22 ON 0 1 2 22 22 22 22 13...

Страница 32: ...0 0 5 16 22 22 22 22 13 ON 0 0 5 17 13 22 22 22 22 ON 0 0 5 18 22 13 22 22 22 ON 0 0 5 19 22 22 13 22 22 ON 0 0 5 20 22 22 22 13 22 ON 0 1 21 22 22 22 22 13 ON 0 1 14 The pattern is displayed when an...

Страница 33: ...urs YES 1 5 5 5 ON 0 1 3 Thepatternisdisplayedwhenaninputoccurs YES 1 9 9 9 ON 0 1 4 Thepatternisdisplayedwhenaninputoccurs YES 1 13 13 13 ON 0 1 5 Thepatternisdisplayedwhenaninputoccurs YES 1 21 21 2...

Страница 34: ...10 8 8 8 ON 0 1 11 11 11 11 ON 0 1 12 1 1 1 60fpm 0 1 13 22 22 22 ON 0 1 14 9 5 1 ON 0 1 15 1 2 3 ON 0 1 16 4 5 6 ON 0 1 17 7 8 9 ON 0 1 18 10 11 12 ON 0 1 19 13 14 15 ON 0 1 20 16 17 18 ON 0 1 21 19...

Страница 35: ...On 0 0 5 8 13 22 22 On 0 0 5 9 22 13 22 On 0 0 5 10 22 22 13 On 0 0 5 11 13 22 22 On 0 0 5 12 22 13 22 On 0 0 5 13 22 22 13 On 0 0 5 14 The pattern is displayed when an input occurs YES 1 9 9 9 On 0...

Страница 36: ...n Blue White Model Number LA6 Model RYGBC Color LED Tiers W U Body Color Rated Voltage Flashing Alarm Option Mounting Wiring Installation Color for each tier in Signal Tower Mode Factory default setti...

Страница 37: ...device must acceptanyinterference received including interference that may cause undesired operation Personal Computer LA6 back Micro USB cable Not included with this product USB Cover Micro USB Conn...

Страница 38: ...nal inputs except for the Multi function Button Data lead time is 60 milliseconds 8 1 Basic Signal Input Time Chart If an input signal status is maintained by the data lead time indicated for this pro...

Страница 39: ...Check the rated supply voltage Is the setup data correct Check the setup data contents Check that the product type has a Alarm included or not The Alarm function is only included with products with a...

Страница 40: ...Cover Silver B31310001 9F1 USB Cover Off white B22100071 7F1 USB Cover Silver B22100071 9F1 Waterproof Ring B 2 pc Set B25110042 F1 Pole Bracket Set Pole Bracket Pole Waterproofing Ring Tapping screw...

Страница 41: ...ht Inverted Direction Protection Rating IP65 Alarm specification IP54 IEC 60529 Environmental Condition Upright Installation Vibration Resistance LA6 LJ Sweep Durability Total amplitude 0 3 mmp p 10 5...

Страница 42: ...from maximum standard 10dB drop from maximum standard OFF Returns to Maximum Data Transfer Interface Main Unit USB micro B Terminal Female USB2 0 1 1 Interface Transmission Rate USB2 0 1 1 1 0 Transfe...

Отзывы: