LA6 Signal Tower Complete Operation Manual
5.2. Current Capacity
5.2.1. Contact Capacity [DC 24V Type]
Table 1 Signal Contact Capacity
Current Capacity
100mA or more
Withstand Voltage
DC 35V or more
Leakage Current
0.1mA or less
ON Voltage (Vsat)
1V or less
Table 2 Power Supply Inrush Current
Inrush Current Value
16A/5us
Table 3 Supply Current
Model
Current
LA6-3D N
170mA
LA6-3D B
210mA
LA6-5D N
260mA
LA6-5D B
300mA
5.2.2. Contact Capacity [ AC 100 - 240V Type]
Table 1 Signal Contact Capacity
Current Capacity
100mA or more
Withstand Voltage
DC 35V or more
Leakage Current
0.1mA or less
ON Voltage (Vsat)
1V or less
Table 2 Power Supply Inrush Current
Inrush Current at 25
o
C
16A/2ms
Inrush Current at 50
o
C
50A/2ms
Table 3 Power Consumption
LA6-5AWJWB
7.5W
Table 4z Fuse Ratings
250V/ 1A
5 x 20mm Fast-blow Glass Tube Fuse
24V DC
(
Class2
)
(
No polarity
)
LA6
Relay
PLC (NPN)
/
⑨
Each LED/
Alarm
Input1 - 7
/
~
① ⑦
Do not connect!
24V DC
(
Class2
)
PLC (PNP)
24V DC
(
Class2
)
16 A , 5 µsec
Inrush Current
Voltage Contact Relay or PLC
Without flashing/alarm
B
N
With flashing/alarm
Flashing/Pulse Enable
Common line
/
⑪
/
⑩
/
⑧
Power Supply Wire
Mode Change
※
Power Supply Wire
Pink
※
There is no inrush current on the wire
for “Mode Change.”
Each Color
Pink
Yellow
Gray
Brown
Note
• When a regulated power supply is not being used, select a fuse that meets class CC or more.